Copper Conductor, XLPE Insulated, PVC Sheathed

Cu / XLPE / PVC 0.6/1 kV, N2XY

Copper Conductor

# Application
XLPE Insulated Used as power cable for indoors, outdoors, cable trunking, and burried in the ground.
Also used for power stations, industries and switchgear as well as for urban supply
networks, where there is low exposure to mechanical damage.

# Specification
PVC Outer Sheath IEC 60502 - 1

# Classification
Low Voltage 0.6/1 kV

Technical Properties
Current Short Circuit
Nominal Thickness Approximately
Number DC resistance Carrying Current Standard
Size
of Cores at 20 °C Capacity at Capacity at 1 Length
Overall 30 oC in air sec
Insulation Outer sheath Net Weight
diameter
mm2 mm mm mm Kg/Km Ω/km A kA m
1.5 0.7 1.4 5.9 47 12,1 35 0.21 1000
2.5 0.7 1.4 6.3 58 7,41 43 0.36 1000
4 0.7 1.4 6.7 75 4,61 57 0.57 1000
6 0.7 1.4 7.2 96 3,08 72 0.86 1000
10 0.7 1.4 8.5 145 1,83 98 1.43 1000
16 0.7 1.4 9.5 205 1,15 132 1000
1 CORES

2.29
25 0.9 1.4 11.2 305 0,727 187 3.58 1000
35 0.9 1.4 12.3 401 0,524 217 5.01 1000
50 1.0 1.4 13.8 522 0,387 263 7.15 1000
70 1.1 1.4 15.8 727 0,268 331 10.02 1000
95 1.1 1.5 17.8 982 0,193 408 13.59 1000
120 1.2 1.5 19.6 1216 0,153 474 17.17 1000
150 1.4 1.6 21.7 1498 0,124 550 21.46 1000
185 1.6 1.6 24 1855 0,0991 633 26.47 1000
240 1.7 1.7 26.9 2415 0,0754 750 34.34 1000