Project: ETAP

Page: 1

Location:
19.0.1C Date: 13-12-2023
Contract:
SN:
Engineer: Revision: Base
Study Case: LF
Filename: FURQAN KHAN Config.: Normal

LOAD FLOW REPORT

Bus Voltage Generation Load Load Flow XFMR

ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap

* A1 13.000 100.000 0.0 85.181 85.111 0.000 0.000 B 85.181 85.111 5347.8 70.7

* A2 13.000 100.000 0.0 85.181 85.111 0.000 0.000 B 85.181 85.111 5347.8 70.7

B 132.000 94.994 3.1 0.000 0.000 0.000 0.000 C 150.872 364.289 1815.5 38.3

C 2.091 -194.172 894.1 -1.1

A2 -76.481 -85.059 526.7 66.9

A1 -76.481 -85.059 526.7 66.9

Bus1 132.000 19.224 -25.7 0.000 0.000 60.000 30.000 E -30.560 42.725 1195.1 -58.2

C -29.342 -64.411 1610.4 41.5

C -0.098 -8.314 189.2 1.2

C 132.000 33.170 -20.0 0.000 0.000 60.000 30.000 B -98.268 -96.428 1815.5 71.4

B -1.262 -25.301 334.0 5.0

Bus1 39.394 115.595 1610.4 32.3

Bus1 0.136 -23.866 314.7 -0.6

E 132.000 50.166 75.6 0.000 0.000 0.000 0.000 Bus1 93.868 99.895 1195.1 68.5

F -93.868 -99.895 1195.1 68.5

F 12.500 57.166 68.6 120.000 100.000 0.000 0.000 E 120.000 100.000 12620.7 76.8

* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA