You are on page 1of 1

Project: ETAP Page: 1

Location: 16.0.0C Date: 05-12-2021

Contract: SN: 4359168

Engineer: Revision: Base


Study Case: LF
Filename: modul3 Config.: Normal

LOAD FLOW REPORT

Bus Voltage Generation Load Load Flow XFMR


ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap

* Bus1 150.000 100.000 0.0 2.818 1.340 0 0 bus4 0.949 0.181 3.7 98.2

bus3 1.868 1.158 8.5 85.0

bus3 20.000 97.863 -1.6 0 0 0 0 bus7 1.541 0.747 50.5 90.0

bus8 0.318 0.335 13.6 68.9

Bus1 -1.859 -1.082 63.5 86.4

bus4 150.000 99.974 0.0 0 0 0 0 Bus1 -0.949 -0.435 4.0 90.9

bus12 0.949 0.435 4.0 90.9

bus5 0.400 94.948 -3.6 0 0 0.777 0.258 bus7 -0.777 -0.258 1245.3 94.9

bus6 0.400 94.220 -3.4 0 0 0.735 0.412 bus7 -0.735 -0.412 1291.0 87.2

bus7 20.000 97.446 -1.6 0 0 0 0 bus3 -1.534 -0.745 50.5 90.0

bus5 0.788 0.294 24.9 93.7

bus6 0.746 0.451 25.8 85.6

bus8 20.000 97.766 -1.6 0 0 0 0 bus3 -0.318 -0.335 13.6 68.8

bus11 -0.655 -0.120 19.7 98.3

bus9 0.973 0.456 31.7 90.6

bus9 0.600 95.243 -3.8 0 0 0.964 0.406 bus8 -0.964 -0.406 1057.2 92.2

* Bus10 11.000 100.000 0.0 0.952 0.443 0 0 bus13 0.952 0.443 55.1 90.7

bus11 20.000 97.931 -1.6 0 0 0 0 bus12 -0.941 -0.401 30.1 92.0

bus13 -0.944 -0.408 30.3 91.8

bus8 0.656 0.121 19.7 98.3

bus14 1.229 0.688 41.5 87.3

bus12 20.000 98.183 -1.6 0 0 0 0 bus11 0.943 0.401 30.1 92.0

bus4 -0.943 -0.401 30.1 92.0

bus13 20.000 98.184 -1.6 0 0 0 0 bus11 0.947 0.409 30.3 91.8

Bus10 -0.947 -0.409 30.3 91.8

bus14 0.400 94.300 -4.4 0 0 1.215 0.603 bus11 -1.215 -0.603 2075.9 89.6

* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it)