ETAP

Project: Page: 1
12.6.0H
Location: Date: 04-04-2018
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: 13 bus system project Config.: Normal

Bus Input Data

Load
Bus Initial Voltage Constant kVA Constant Z Constant I Generic

ID kV Sub-sys % Mag. Ang. MW Mvar MW Mvar MW Mvar MW Mvar

Bus1 13.800 1 100.0 0.0

Bus2 69.000 1 100.0 0.0

Bus3 0.480 1 4.8 0.0 0.480 0.424 0.120 0.106

Bus4 69.000 1 100.0 0.0

Bus5 13.800 1 100.0 0.0 1.792 1.600 0.448 0.400

Bus6 13.800 1 100.0 0.0

Bus7 0.480 1 100.0 0.0 0.920 0.232 0.230 0.058

Bus8 4.160 1 100.0 0.0 1.048 0.904 0.262 0.226

Bus9 13.800 1 100.0 0.0

Bus10 0.480 1 100.0 0.0 0.648 0.640 0.162 0.160

Bus11 13.800 1 100.0 0.0

Bus12 0.480 1 100.0 0.0 0.296 0.264 0.074 0.066

Bus13 2.400 1 100.0 0.0

Total Number of Buses: 13 5.184 4.064 1.296 1.016 0.000 0.000 0.000 0.000

Generation Bus Voltage Generation Mvar Limits


ID kV Type Sub-sys % Mag. Angle MW Mvar % PF Max Min

Bus1 13.800 Swing 1 100.0 0.0

Bus2 69.000 Voltage Control 1 100.0 0.0 6.000 6.200 0.000

6.000 0.000