Professional Documents
Culture Documents
978-1-4799-3254-2/13/$31.00
manage the system protection. This technology will depend • System phase balance
on measurement of data at strategic locations and • Supply reliability
communicating these data to intelligent relays for protection These issues are needed to be given special attention due to
of the feeders. the stochastic (intermittent) nature of the RES.
Therefore, protection coordination will become an integral
part of distribution automation (DA). Large numbers of II. TYPES OF DISTRIBUTED GENERATION
distributed generation could also lead to stability and
frequency control problems. The problems that were only Different types of DGs include:
relevant to transmission systems will become relevant to • Synchronous generators,
distribution systems too. Therefore, new technologies to • Photovoltaic generators
operate and manage the DG at the distribution system will be • Asynchronous generators
needed. Distribution automation is the evolving computer There are different types of transformer connections
and communications technology to improve operating interfacing between the DGs and the distribution
performance of distribution systems, that is, the evolution of systems. They include:
supervisory control and data acquisition (SCADA) systems, o Delta(HV)/Delta(LV);
which have been in use for monitoring the generation and o Delta(HV)/Wye-Gnd(LV);
transmission systems, will also be used in the field of o Wye-Ungnd(HV)/Delta-Ungnd(LV);
distribution automation. Distribution systems are a o Wye-Gnd(HV)/Delta;
significant part of power systems, but distribution control o Wye-Gnd(HV)/Wye-Gnd(LV) [4].
technology has never been used as in generation and Asynchronous generators, two types are commonly used in
transmission systems [1]. wind generators:
The following three scenarios have to be considered in the • Squirrel Cage Induction generator (Fixed Speed
analysis of any DG interconnection to the distribution system. Wind Turbines),
They are its rated power production capability, the • Doubly fed Induction generator Model
technology used in the connection and mode of control and
operation. The problems of the protective device Synchronous generator
coordination include: Synchronous generator has the capability of producing
• In-feed and bi-directional current flow active and reactive power on site. This is considered to be an
• Issues related to ground fault detection advantage over capacitors (capacitors produces reactive
• Unintentional islanding in the system which causes only). The external field control makes it possible for it to
voltage variations and contributing to poor power produce and absorb reactive power which has always been
quality to the consumers. the exclusive privilege of Transmission system. But the
• Synchronizing and auto-reclosing problems energy production is limited to a few MW. Micro gas
Among the merits of DG, THD reduction, loss reduction turbines, combined heat and power (CPH) turbines,
and voltage profile improvement are of importance, if the Diesel/gas engines and Run-of-flow hydro fall into this
optimal locations and optimal sizes of DG are properly category.
coordinated through studies before installation. Non-optimal
locations and sizes can lead to poor power quality, i.e. Photovoltaic generator
increase in losses, bad effect on voltage profile and harmonics The photovoltaic generator (PV) is stochastic in nature,
[2]. It is necessary to determine the new distribution collecting power from the direct sunlight and converting it
protection device locations such that outages are reduced, electric power, usually direct current (DC). Power converters
power system reliability is enhanced. In the conventional (Inverters) convert the dc to ac through the use of high power
distribution systems, the non-linear loads are the sources of electronics to the desired output. Most inverters do the
harmonic currents and therefore of voltages. Such sources of conversion at unity power factor. Other DGs that use these
harmonic generators in the distribution system include converters include micro-turbines, fuel cells and wind
inverters, rectifiers, variable speed drives, arc furnaces, turbines with doubly-fed, variable speed induction generators
compact florescent lamps (CFL), etc. With the introduction having insulated gate bipolar transistor (IGBT) converter in
of DG into the distribution systems, there is need to study the their rotor circuit. This latest development has helped to
interaction of the interfaces with the already existing sources reduce the harmonic inherent in wind turbines to near zero.
of harmonic, since DG interfaces are harmonic producing
sources. Harmonic current flows are now bi-directional
(from source to the line and from the load to the line). The Asynchronous generator
net distortion must be within the limits of international These are the induction motors made to run at above the
regulations e.g. IEEE 519: 1992 limits [3]. Other power synchronous speed, thus becoming a generator. The external
quality issues include: prime mover is the wind turbine. Induction machines are
• Voltage variations (sags and swells) very cheap, so most wind turbines use induction machines as
• Frequency variations their mode of generation. They are either squirrel cage type
(fixed speed), or doubly-fed type (variable speed). As and if the relay setting of CB 1 is too low. This is also called
mentioned above the new development of IGBT has helped to nuisance tripping.
solve virtually all the harmonic problems (flicker) generated
by the wind turbine at fixed frequency of 50Hzs. In exchange Protection blinding
these power electronic equipments introduce their own Fault tripping of feeders leads to protection blinding
harmonic problems into the system. especially if the DG is close to the substation. The
contribution to the fault current by the DGs leads to the
reduction of fault current from the substation, this leads to
III. PQ & PROTECTIVE RELAY IN THE
PRESENCE OF DGS protection blinding of the CB protection from the substation.
The Recloser and the DG fuses may likely operate first before Relay coordination
the CB 1 if their relay settings are not properly coordinated
The normal electric distribution systeems are radial in
nature, with the supply coming from a maiin source, (main or
slack bus). Simple protection system consisting of over-
current relays, line reclosers and fuses are used in the
distribution system. The main relay coordiination problems in
distribution systems are therefore:
1. Over-current relay - Recloser coorrdination,
2. Recloser – Fuse coordination,
3. Fuse – Fuse coordination.
The introduction of DGs has brougght in protection
coordination problems among these elem ments, because the
system is no more unidirectional in nature.. Few additions of
DGs will not change the relay coordinationn significantly, but
heavy penetration reverses the power flow and the network is
no more passive circuit, unidirectional, but active. The
voltage profile, loading limits and the reacttive power margins
of the distribution system will also changee. The presence of
such generation units leads to losingg coordination of
protection devices. Experiments were perfo formed that showed
that DG causes mal-operation in reclosers anda transient faults
are not cleared. Synchronisation is not n possible after
islanding operation when trying a recllosure and heavy Fig. 4. Harmonic Analysis showinng the Bus voltage (RMS) and the
damages could result when trying a reclosure in an operating voltage.
asynchronous network. [4].
The plot of the comparison of the
t harmonic voltage spectrum
of the slack bus and bus 23 of thhe PV generator were made in
V. CASE STUDY
figure 3. The 11th and 13thh harmonics were the worst
The harmonic analyses with different typpes of DGs located individual harmonic distortions (IHD) in the case study. The
in the 24bus radial distribution system werre carried out. The %, but it was upto 3.31%. The
distortions should not exceed 3%
total installed load in the circuit was 10.9MW;
1 carrying harmonic voltage Analysis of the bus voltages and the
6.99MW at peak, and the total DG load waas 10.45MVA with operating voltages are displayeed in figure 4. Table I gives
maximum generation of 3.54MVA. Fourr different types of the value of the total harmonicc distortion THD (5.07%) for
DGs were connected to the circuit. A num mber of simulations the same bus 23. The internatioonal recommended figures are
were carried out for the harmonic analysiss and the effects of supposed to be 3% for the IH HD, and 5% for the THD, all
excluding and including the Fixed-turbine wind generator on measured at the point of comm mon coupling (PCC) [2]. The
bus 20 on the relay coordination were noteed and analysed to inverters of the solar paneels are responsible for the
distortions. The installation of
o the single tuned harmonic
study the miscoordination.
filters at bus 23 will reduce the
t harmonic contents in the
voltage waveform.
TABL
LE I
HARMONIC FLOW ANALYSIIS VIEW OUTPUT REPORT
Fig. 3. Harmonic Voltage Spectrum (comparing swinng bus and bus 23 of the
PV generator). The 11th & 13th harmonics are the worst
w of the 50 IHDs.
that of the IG, but has largger steady state RMS fault
contribution. Power electronics interface, static power
converter (SPC) disconnects thhe DG instantaneously when
the fault current contribution is higher than 20% of rated
current [10].
Fig. 9. The TCC curves of the affected parts of the circuit connected with the
Wind Turbinee Generator2
REFEREENCES
[1] C. F. Henville, ’’Power Quality Impacts on Protective Relays –and
Vice Versa,’’ Power Engineering Society Summer Meeting, 2001 vol.1
pp. 587 – 592
[2] O. Amanifar; M. E. Hamedani Golshan,
G ‘’Optimal DG allocation and
sizing for mitigating voltage sag in
i distribution systems with respect to
economic consideration using Particle Swarm Optimization.’’ IEEE
Conference Publications, Electrrical Power Distribution Networks
(EPDC), 2012 Proceedings of 17thh Conference 2012, pp.1 – 8
[3] IEEE Recommended Practices and Requirements for Harmonics
Control in Electrical Systems: IEE
EE, 1992,
[4] K. Kauhaniemi; L. Kumpulainen, ‘’Impact of distributed generation on
the protection of distribution networks,‘’
n Developments in Power
System Protection, Eighth IEE International Conference, 5-8 April
2004, Vol.1, pp.315 – 318
[5] Impact of Distributed Resources on Distribution Relay Protection: A
report on Line Protection Subcom mmittee of the Power System Relay
Committee of The IEEE Poweer Engineering Society prepared by
working group D3, August 2004, pp.p 12-13
[6] A Dysko; I. A. Zamora; A. J. Maazon; V. Valverde; J. I. S. Martin; G.
Buigues; ‘’Influence of power quality
q on the performance of digital
protection relays,’’ Power Tech, 2005 IEEE Russia . Digital Object
Identifier: 10.1109/PTC.2005.4524550, pp. 1 - 7
[7] T. Gallery; I. Martinez; D. Klopotan, ‘’Impact of Distributed
Generation on Distributed Netwoork Protection,’’ Item 515 of the 40th
International Universities Poweer Engineering, Conference, Cork
Ireland, UPEC2005, 7th - 8th Septtember, 2005
[8] K. Jennett; C. Booth; M. Lee, ‘’’Analysis of the sympathetic tripping
problem for networks with high peenetrations of distributed generation,’’
International Conference of AdvaancedPower System Automation and
Protection, (APAP) Beijing;Vol. 1.1 16-20 Oct. 2011, pp.384-389.
[9] H. Tin; Abu-Saida; M. S. Masooum, ‘’Impact of Harmonics on the
Performance of Over-current Relaays,‘’ Universities Power Engineering
Conference (AUPEC), 21st Austraalasian , 2011 , pp. 1 – 4
[10] N. Pholborisut; T. Saksornchai; B.
B Eua-arporn, ‘’Evaluating the impact
of distributed generation on prrotection system coordination using
protection miscoordination index,,’’ IEEE 8th International Conference
on Electrical Engineering/Electroonics, Computer, Telecommunications
and Information Technology (ECT TI-CON), 2011, pp. 865 - 868
Fig. 8. Protective Device Sequence-of-Operationn (with WTG2) closed.