You are on page 1of 5

HASIL UJI LOAD FLOW TRAFO

Project: ETAP Page: 1


Location: 19.0.1C Date: 10-01-2024
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: 0 Config.: Normal

Bus Loading Summary Report

Directly Connected Load Total Bus Load

Bus Constant kVA Constant Z Constant I Generic


Percent
ID kV Rated Amp MW Mvar MW Mvar MW Mvar MW Mvar MVA % PF Amp Loading

Bus17 0.380
Bus1 11.000 0.283 85.1 14.9
Bus2 0.380 0.272 86.0 430.0
Bus3 0.380 0.001 0.000 0.000 - 0.271 86.0 430.0
Bus4 0.380 0.012 0.007 0.003 0.002 0.017 85.0 27.2
Bus6 0.380 0.013 0.008 0.003 0.002 0.019 85.0 30.1
Bus7 0.380 0.011 0.007 0.003 0.002 0.016 85.0 26.1
Bus8 0.380 0.036 0.022 0.008 0.005 0.052 85.0 83.8
Bus14 0.380 0.032 0.020 0.007 0.004 0.046 85.0 74.2
Bus15 0.380 0.071 0.044 0.015 0.009 0.101 85.0 169.1
Bus16 0.380 0.008 0.005 0.002 0.001 0.011 85.0 18.0
Bus18 0.380 0.271 86.0 430.0

* Indicates operating load of a bus exceeds the bus critical limit (100.0% of the Continuous Ampere rating).
# Indicates operating load of a bus exceeds the bus marginal limit (95.0% of the Continuous Ampere rating).
Project: ETAP Page: 2
Location: 19.0.1C Date: 10-01-2024
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: 0 Config.: Normal

Branch Loading Summary Report

Transformer
CKT / Branch Busway / Cable & Reactor
Loading (input) Loading (output)
Ampacity Loading Capability
(Amp) Amp (MVA)
ID Type % MVA % MVA %

* Cable3 Cable 299.85 430.00 143.41

Cable4 Cable 48.42 27.21 56.19

* Cable6 Cable 48.42 74.18 153.19

* Cable7 Cable 48.42 169.12 349.26

Cable8 Cable 48.42 17.99 37.15

Cable10 Cable 48.42 30.08 62.11

Cable11 Cable 48.42 26.10 53.91

* Cable12 Cable 48.42 83.79 173.03

* T1 Transformer 0.275 0.283 102.9 0.272 99.1

* Indicates a branch with operating load exceeding the branch capability.


Project: ETAP Page: 3
Location: 19.0.1C Date: 10-01-2024
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: 0 Config.: Normal

Branch Losses Summary Report

Vd
From-To Bus Flow To-From Bus Flow Losses % Bus Voltage
% Drop
Branch ID MW Mvar MW Mvar kW kvar From To in Vmag

Cable10 0.016 0.010 -0.016 -0.010 0.2 0.0 95.9 95.0 0.89

Cable11 0.014 0.009 -0.014 -0.009 0.2 0.0 95.9 95.1 0.77

Cable12 0.045 0.027 -0.044 -0.027 1.6 0.0 95.9 93.4 2.47

Cable3 0.234 0.139 -0.233 -0.139 1.0 0.4 96.3 95.9 0.39

Cable4 0.015 0.009 -0.014 -0.009 0.2 0.0 95.9 95.1 0.80

Cable6 0.040 0.024 -0.039 -0.024 1.2 0.0 95.9 93.7 2.19

Cable7 0.092 0.053 -0.086 -0.053 6.4 0.2 95.9 90.9 5.02

Cable8 0.010 0.006 -0.010 -0.006 0.1 0.0 95.9 95.4 0.53

T1 0.241 0.149 -0.234 -0.139 6.5 9.7 100.0 96.3 3.73

17.3 10.3
* This Transmission Line includes Series Capacitor.
Project: ETAP Page: 4
Location: 19.0.1C Date: 10-01-2024
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: 0 Config.: Normal

Alert Summary Report

% Alert Settings
Critical Marginal
Loading
Bus 100.0 95.0
Cable / Busway 100.0 80.0
Reactor 100.0 95.0
Line 100.0 95.0
Transformer 100.0 80.0
Panel 100.0 95.0
Protective Device 100.0 95.0
Generator 100.0 80.0
Inverter/Charger 100.0 95.0

Bus Voltage
OverVoltage 105.0 105.0
UnderVoltage 95.0 95.0

Generator Excitation
OverExcited (Q Max.) 100.0 95.0
UnderExcited (Q Min.) 100.0

Critical Report

Device ID Type Condition Rating/Limit Unit Operating % Operating Phase Type

Bus14 Bus Under Voltage 0.380 kV 0.356 93.7 3-Phase

Bus15 Bus Under Voltage 0.380 kV 0.345 90.9 3-Phase

Bus6 Bus Under Voltage 0.380 kV 0.361 95.0 3-Phase

Bus8 Bus Under Voltage 0.380 kV 0.355 93.4 3-Phase

Cable12 Cable Overload 48.422 Amp 83.787 173.0 3-Phase

Cable3 Cable Overload 299.846 Amp 430.004 143.4 3-Phase

Cable6 Cable Overload 48.422 Amp 74.179 153.2 3-Phase

Cable7 Cable Overload 48.422 Amp 169.121 349.3 3-Phase

Gen1 Generator Under Excited 0.000 Mvar 0.000 0.0 3-Phase

Gen1 Generator Under Power 0.000 MW 0.000 0.0 3-Phase

T1 Transformer Overload 0.275 MVA 0.283 102.9 3-Phase


Project: ETAP Page: 5
Location: 19.0.1C Date: 10-01-2024
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: 0 Config.: Normal

SUMMARY OF TOTAL GENERATION , LOADING & DEMAND

MW Mvar MVA % PF

Source (Swing Buses): 0.241 0.149 0.283 85.06 Lagging

Source (Non-Swing Buses): 0.000 0.000 0.000

Total Demand: 0.241 0.149 0.283 85.06 Lagging

Total Motor Load: 0.184 0.114 0.216 85.00 Lagging

Total Static Load: 0.040 0.025 0.047 85.00 Lagging

Total Constant I Load: 0.000 0.000 0.000

Total Generic Load: 0.000 0.000 0.000

Apparent Losses: 0.017 0.010

System Mismatch: 0.000 0.000

Number of Iterations: 3