SHORT-CIRCUIT REPORT

3-phase fault at bus: Bus1

Prefault voltage = 13.200 kV = 100.00 % of nominal bus kV (13.200 kV)


= 100.00 % of base (13.200 kV)

Contribution 1/2 Cycle 1.5 to 4 Cycle


From Bus To Bus %V kA kA Imag. kA Symm. %V kA kA Imag. kA Symm.
ID ID From Bus Real Imaginary /Real Magnitude From Bus Real Imaginary /Real Magnitude

Bus1 Total 0.00 0.754 -15.844 21.0 15.862 0.00 0.710 -15.791 22.2 15.807

Bus21 Bus1 0.01 0.111 -0.195 1.7 0.224 0.01 0.075 -0.168 2.2 0.184

Bus18 Bus1 0.03 0.260 -0.345 1.3 0.432 0.03 0.253 -0.319 1.3 0.407

Incoming Supply Bus1 100.00 0.383 -15.304 40.0 15.309 100.00 0.383 -15.304 40.0 15.309

NACD Ratio = 1.00

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a fault current through a tie circuit breaker.
If the faulted bus is involved in loops formed by protection devices, the short-circuit contributions through these protective devices will not be reported.
Project:
ETAP Page: 2
19.0.1C
Location: Date: 11-26-2021
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: PART 1 CIRCUIT DIAGRAM Config.: Normal

3-phase fault at bus: Bus_2

Prefault voltage = 0.240 kV = 100.00 % of nominal bus kV (0.240 kV)


= 100.00 % of base (0.240 kV)

Contribution 1/2 Cycle


From Bus To Bus %V kA kA Imag. kA Symm.
ID ID From Bus Real Imaginary /Real Magnitude

Bus_2 Total 0.00 2.584 -2.173 0.8 3.377

T2 Feeder Bus Bus_2 97.21 2.584 -2.173 0.8 3.377

Bus 11 Bus_2 0.00 0.000 0.000 999.9 0.000

Bus 12 Bus_2 0.00 0.000 0.000 999.9 0.000

Bus 13 Bus_2 0.00 0.000 0.000 999.9 0.000

Bus14 Bus_2 0.00 0.000 0.000 999.9 0.000

Bus15 Bus_2 0.00 0.000 0.000 999.9 0.000

NACD Ratio = 1.00

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a fault current through a tie circuit breaker.
If the faulted bus is involved in loops formed by protection devices, the short-circuit contributions through these protective devices will not be reported.
Project:
ETAP Page: 3
19.0.1C
Location: Date: 11-26-2021
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: PART 1 CIRCUIT DIAGRAM Config.: Normal

3-phase fault at bus: Bus_3

Prefault voltage = 0.240 kV = 100.00 % of nominal bus kV (0.240 kV)


= 100.00 % of base (0.240 kV)

Contribution 1/2 Cycle


From Bus To Bus %V kA kA Imag. kA Symm.
ID ID From Bus Real Imaginary /Real Magnitude

Bus_3 Total 0.00 2.698 -2.659 1.0 3.788

T2 Feeder Bus Bus_3 97.19 2.584 -2.173 0.8 3.376

Bus16 Bus_3 1.20 0.057 -0.243 4.3 0.249

Bus 17 Bus_3 1.20 0.057 -0.243 4.3 0.249

Bus 18 Bus_3 0.00 0.000 0.000 999.9 0.000

NACD Ratio = 1.00

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a fault current through a tie circuit breaker.
If the faulted bus is involved in loops formed by protection devices, the short-circuit contributions through these protective devices will not be reported.
Project:
ETAP Page: 4
19.0.1C
Location: Date: 11-26-2021
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: PART 1 CIRCUIT DIAGRAM Config.: Normal

3-phase fault at bus: Bus9

Prefault voltage = 0.240 kV = 100.00 % of nominal bus kV (0.240 kV)


= 100.00 % of base (0.240 kV)

Contribution 1/2 Cycle


From Bus To Bus %V kA kA Imag. kA Symm.
ID ID From Bus Real Imaginary /Real Magnitude

Bus9 Total 0.00 5.632 -5.951 1.1 8.194

T2 Feeder Bus Bus9 94.47 4.945 -4.315 0.9 6.563

Lumped Load 2 Bus9 100.00 0.687 -1.636 2.4 1.774

NACD Ratio = 1.00

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a fault current through a tie circuit breaker.
If the faulted bus is involved in loops formed by protection devices, the short-circuit contributions through these protective devices will not be reported.
Project:
ETAP Page: 5
19.0.1C
Location: Date: 11-26-2021
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: PART 1 CIRCUIT DIAGRAM Config.: Normal

3-phase fault at bus: Bus14

Prefault voltage = 0.240 kV = 100.00 % of nominal bus kV (0.240 kV)


= 100.00 % of base (0.240 kV)

Contribution 1/2 Cycle


From Bus To Bus %V kA kA Imag. kA Symm.
ID ID From Bus Real Imaginary /Real Magnitude

Bus14 Total 0.00 2.229 -1.864 0.8 2.906

Bus_2 Bus14 13.94 2.229 -1.864 0.8 2.906

NACD Ratio = 1.00

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a fault current through a tie circuit breaker.
If the faulted bus is involved in loops formed by protection devices, the short-circuit contributions through these protective devices will not be reported.
Project:
ETAP Page: 6
19.0.1C
Location: Date: 11-26-2021
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: PART 1 CIRCUIT DIAGRAM Config.: Normal

3-phase fault at bus: Bus15

Prefault voltage = 0.240 kV = 100.00 % of nominal bus kV (0.240 kV)


= 100.00 % of base (0.240 kV)

Contribution 1/2 Cycle


From Bus To Bus %V kA kA Imag. kA Symm.
ID ID From Bus Real Imaginary /Real Magnitude

Bus15 Total 0.00 2.229 -1.864 0.8 2.906

Bus_2 Bus15 13.94 2.229 -1.864 0.8 2.906

NACD Ratio = 1.00

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a fault current through a tie circuit breaker.
If the faulted bus is involved in loops formed by protection devices, the short-circuit contributions through these protective devices will not be reported.
Project:
ETAP Page: 7
19.0.1C
Location: Date: 11-26-2021
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: PART 1 CIRCUIT DIAGRAM Config.: Normal

3-phase fault at bus: Bus18

Prefault voltage = 13.200 kV = 100.00 % of nominal bus kV (13.200 kV)


= 100.00 % of base (13.200 kV)

Contribution 1/2 Cycle 1.5 to 4 Cycle


From Bus To Bus %V kA kA Imag. kA Symm. %V kA kA Imag. kA Symm.
ID ID From Bus Real Imaginary /Real Magnitude From Bus Real Imaginary /Real Magnitude

Bus18 Total 0.00 0.873 -15.755 18.0 15.779 0.00 0.830 -15.703 18.9 15.725

Bus1 Bus18 0.96 0.613 -15.409 25.1 15.421 0.96 0.577 -15.383 26.7 15.394

T2 Feeder Bus Bus18 28.40 0.260 -0.345 1.3 0.432 26.76 0.253 -0.319 1.3 0.407

NACD Ratio = 1.00

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a fault current through a tie circuit breaker.
If the faulted bus is involved in loops formed by protection devices, the short-circuit contributions through these protective devices will not be reported.
Project:
ETAP Page: 8
19.0.1C
Location: Date: 11-26-2021
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: PART 1 CIRCUIT DIAGRAM Config.: Normal

3-phase fault at bus: Bus19

Prefault voltage = 0.240 kV = 100.00 % of nominal bus kV (0.240 kV)


= 100.00 % of base (0.240 kV)

Contribution 1/2 Cycle


From Bus To Bus %V kA kA Imag. kA Symm.
ID ID From Bus Real Imaginary /Real Magnitude

Bus19 Total 0.00 2694.670 -50951.950 18.9 51023.150

T2 Feeder Bus Bus19 79.31 13.847 -16.310 1.2 21.396

Standby Generator 1 Bus19 100.00 2680.823 -50935.640 19.0 51006.140

NACD Ratio = 0.00

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a fault current through a tie circuit breaker.
If the faulted bus is involved in loops formed by protection devices, the short-circuit contributions through these protective devices will not be reported.
Project:
ETAP Page: 9
19.0.1C
Location: Date: 11-26-2021
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: PART 1 CIRCUIT DIAGRAM Config.: Normal

3-phase fault at bus: Bus21

Prefault voltage = 13.200 kV = 100.00 % of nominal bus kV (13.200 kV)


= 100.00 % of base (13.200 kV)

Contribution 1/2 Cycle 1.5 to 4 Cycle


From Bus To Bus %V kA kA Imag. kA Symm. %V kA kA Imag. kA Symm.
ID ID From Bus Real Imaginary /Real Magnitude From Bus Real Imaginary /Real Magnitude

Bus21 Total 0.00 0.874 -15.751 18.0 15.775 0.00 0.830 -15.698 18.9 15.720

Bus1 Bus21 0.97 0.763 -15.556 20.4 15.575 0.97 0.755 -15.530 20.6 15.549

T1 Feeder Bus Bus21 9.82 0.111 -0.195 1.7 0.224 8.05 0.075 -0.168 2.2 0.184

NACD Ratio = 1.00

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a fault current through a tie circuit breaker.
If the faulted bus is involved in loops formed by protection devices, the short-circuit contributions through these protective devices will not be reported.
Project:
ETAP Page: 10
19.0.1C
Location: Date: 11-26-2021
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: PART 1 CIRCUIT DIAGRAM Config.: Normal

3-phase fault at bus: T1 Feeder Bus

Prefault voltage = 0.240 kV = 100.00 % of nominal bus kV (0.240 kV)


= 100.00 % of base (0.240 kV)

Contribution 1/2 Cycle


From Bus To Bus %V kA kA Imag. kA Symm.
ID ID From Bus Real Imaginary /Real Magnitude

T1 Feeder Bus Total 0.00 16.826 -120.497 7.2 121.666

Bus5 T1 Feeder Bus 59.65 3.615 -5.717 1.6 6.764

Bus 7 T1 Feeder Bus 59.65 3.615 -5.717 1.6 6.764

Bus21 T1 Feeder Bus 87.23 9.597 -109.062 11.4 109.483

NACD Ratio = 1.00

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a fault current through a tie circuit breaker.
If the faulted bus is involved in loops formed by protection devices, the short-circuit contributions through these protective devices will not be reported.
Project:
ETAP Page: 11
19.0.1C
Location: Date: 11-26-2021
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: PART 1 CIRCUIT DIAGRAM Config.: Normal

3-phase fault at bus: T2 Feeder Bus

Prefault voltage = 0.240 kV = 100.00 % of nominal bus kV (0.240 kV)


= 100.00 % of base (0.240 kV)

Contribution 1/2 Cycle


From Bus To Bus %V kA kA Imag. kA Symm.
ID ID From Bus Real Imaginary /Real Magnitude

T2 Feeder Bus Total 0.00 29.622 -96.438 3.3 100.885

Bus 8 T2 Feeder Bus 11.46 0.348 -0.716 2.1 0.796

Bus9 T2 Feeder Bus 20.75 0.686 -1.268 1.8 1.441

Bus 10 T2 Feeder Bus 20.75 0.686 -1.268 1.8 1.441

Bus_2 T2 Feeder Bus 0.00 0.000 0.000 999.9 0.000

Bus_3 T2 Feeder Bus 12.86 0.136 -0.425 3.1 0.447

Bus19 T2 Feeder Bus 99.96 21.024 -16.890 0.8 26.968

Bus18 T2 Feeder Bus 91.03 6.742 -75.871 11.3 76.170

NACD Ratio = 1.00

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a fault current through a tie circuit breaker.
If the faulted bus is involved in loops formed by protection devices, the short-circuit contributions through these protective devices will not be reported.