19.0.1C Date: 03-17-2022 Contract: SN: Engineer: R.VENERO Revision: Base Study Case: SC Filename: SE-TESIS Config.: Normal
ESCENARIO #1
SHORT-CIRCUIT REPORT
3-phase fault at bus: BusGEN
Prefault voltage = 0.480 kV = 100.00 % of nominal bus kV (0.480 kV) = 100.00 % of base (0.480 kV)
Contribution 1/2 Cycle
From Bus To Bus %V kA kA Imag. kA Symm. ID ID From Bus Real Imaginary /Real Magnitude
BusGEN Total 0.00 2.016 -11.140 5.5 11.321
BusCCM BusGEN 0.18 0.270 -0.885 3.3 0.925
Bus2 BusGEN 3.39 0.560 -3.427 6.1 3.472
Bus3 BusGEN 4.05 0.578 -3.412 5.9 3.460
Bus4 BusGEN 4.71 0.596 -3.396 5.7 3.448
Bus18 BusGEN 0.01 0.012 -0.020 1.7 0.023
NACD Ratio = 0.00
# Indicates a fault current contribution from a three-winding transformer.
* Indicates a fault current through a tie circuit breaker. If the faulted bus is involved in loops formed by protection devices, the short-circuit contributions through these protective devices will not be reported.