E CORPOELEC ETAP Page: 1


19.0.1C
Date: 03-17-2022
Contract:    SN:       
Engineer: R.VENERO Revision: Base
Study Case:      SC
Filename: SE-TESIS Config.: Normal

ESCENARIO #1

SHORT-CIRCUIT    REPORT

3-phase fault at bus:        BusGEN


Prefault voltage = 0.480 kV = 100.00 % of nominal bus kV (0.480 kV)
= 100.00 % of base (0.480 kV)

Contribution 1/2 Cycle


From Bus To Bus %V kA kA Imag. kA Symm.
ID ID From Bus Real Imaginary /Real Magnitude

BusGEN Total 0.00 2.016 -11.140 5.5 11.321

BusCCM BusGEN 0.18 0.270 -0.885 3.3 0.925

Bus2 BusGEN 3.39 0.560 -3.427 6.1 3.472

Bus3 BusGEN 4.05 0.578 -3.412 5.9 3.460

Bus4 BusGEN 4.71 0.596 -3.396 5.7 3.448

Bus18 BusGEN 0.01 0.012 -0.020 1.7 0.023

NACD Ratio =    0.00

#      Indicates a fault current contribution from a three-winding transformer.


*     Indicates a fault current through a tie circuit breaker.
If the faulted bus is involved in loops formed by protection devices, the short-circuit contributions through these protective devices will not be reported.