Project:

ETAP Page: 1
12.6.0H
Location: Date: 05-01-2021
Contract: SN:
Engineer: Revision: Base
Study Case: SM
Filename: HCSD11 Config.: Normal

Short-Circuit Summary Report

3-Phase, LG, LL, LLG Fault Currents

Bus 3-Phase Fault Line-to-Ground Fault Line-to-Line Fault *Line-to-Line-to-Ground

ID kV I"k ip Ik I"k ip Ib Ik I"k ip Ib Ik I"k ip Ib Ik

Bus6 0.433 34.525 52.363 34.525 33.839 51.324 33.839 33.839 29.900 45.348 29.900 29.900 34.452 52.252 34.452 34.452

All fault currents are in rms kA. Current ip is calculated using Method C.

* LLG fault current is the larger of the two faulted line currents.
Project:
ETAP Page: 2
12.6.0H
Location: Date: 05-01-2021
Contract: SN:
Engineer: Revision: Base
Study Case: SM
Filename: HCSD11 Config.: Normal

Sequence Impedance Summary Report

Bus Positive Seq. Imp. (ohm) Negative Seq. Imp. (ohm) Zero Seq. Imp. (ohm) Fault Zf (ohm)
ID kV Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance

Bus6 0.433 0.00531 0.00544 0.00760 0.00531 0.00544 0.00760 0.00578 0.00562 0.00807 0.00000 0.00000 0.00000
Project:
ETAP Page: 3
12.6.0H
Location: Date: 05-01-2021
Contract: SN:
Engineer: Revision: Base
Study Case: SM
Filename: HCSD11 Config.: Normal

Sequence-of-Operation Event Summary Report

Symmetrical 3-Phase Fault between CB8 and CT10. Adjacent to Bus6.

Time (ms) ID If (kA) T1 (ms) T2 (ms) Condition


0.0 P123BCMCC 34.525 0.0 Phase - OC1 - 50

10.0 CB9 10.0 Tripped by P123BCMCC Phase - OC1 - 50

15.0 P127 MCC IC2 34.525 15.0 Phase - OC1 - 50

25.0 CB30 10.0 Tripped by P127 MCC IC2 Phase - OC1 - 50

30.0 P111 PCC OG2 34.525 30.0 Phase - OC1 - 50

40.0 P123BC 34.525 40.0 Phase - OC1 - 51

40.0 CB31 10.0 Tripped by P111 PCC OG2 Phase - OC1 - 50

50.0 P127 PCC IC1 34.525 50.0 Phase - OC1 - 50

50.0 CB10 10.0 Tripped by P123BC Phase - OC1 - 51

58.7 P122 HCSD OG1 1.359 58.7 Phase - OC1 - 51

60.0 CB6 10.0 Tripped by P127 PCC IC1 Phase - OC1 - 50

60.0 P122-2 1.359 60.0 Phase - OC1 - 51

68.7 CB5 10.0 Tripped by P122 HCSD OG1 Phase - OC1 - 51

70.0 CB11 10.0 Tripped by P122-2 Phase - OC1 - 51

80.0 P127-A HCSD IC1 1.359 80.0 Phase - OC1 - 50

90.0 CB4 10.0 Tripped by P127-A HCSD IC1 Phase - OC1 - 50

100 RCS96 1.359 100 Phase - OC1 - 50

110 CB3 10.0 Tripped by RCS96 Phase - OC1 - 50

141 P127-A HCSD IC1 1.359 141 Phase - OC1 - 51

151 CB4 10.0 Tripped by P127-A HCSD IC1 Phase - OC1 - 51