Project: ETAP Page: 1

Location: 16.0.0C Date: 05-27-2020

Contract: SN: 4359168

Engineer: Revision: Base


Study Case: SC
Filename: EVI-LDS Config.: Normal

Electrical Transient Analyzer Program

Short-Circuit Analysis

IEC 60909 Standard

3-Phase Fault Currents

Swing V-Control Load Total

Number of Buses: 1 0 4 5

XFMR2 XFMR3 Reactor Line/Cable Impedance Tie PD Total

Number of Branches: 3 0 0 1 0 0 4

Synchronous Power Synchronous Induction Lumped


Generator Grid Motor Machines Load Total

Number of Machines: 0 1 0 0 0 1

System Frequency: 60.00

Unit System: English

Project Filename: EVI-LDS

Output Filename: C:\ETAP 1600\EVI-LDS\Untitled.SI1S


Project: ETAP Page: 2

Location: 16.0.0C Date: 05-27-2020

Contract: SN: 4359168

Engineer: Revision: Base


Study Case: SC
Filename: EVI-LDS Config.: Normal

Adjustments

Apply Individual
Tolerance Adjustments /Global Percent

Transformer Impedance: Yes Individual

Reactor Impedance: Yes Individual

Overload Heater Resistance: No

Transmission Line Length: No

Cable Length: No

Apply Individual
Temperature Correction Adjustments /Global Degree C

Transmission Line Resistance: Yes Individual

Cable Resistance: Yes Individual


Project: ETAP Page: 3

Location: 16.0.0C Date: 05-27-2020

Contract: SN: 4359168

Engineer: Revision: Base


Study Case: SC
Filename: EVI-LDS Config.: Normal

Bus Input Data

Bus Initial Voltage


ID Type Nom. kV Base kV Sub-sys %Mag. Ang.

Celdas Load 22.900 22.900 1 100.00 0.00


N°1927 SWNG 22.900 22.900 1 100.00 0.00
Tab. de B.T. N°1 Load 0.440 0.440 1 100.00 0.00
Tab. de B.T. N°2 Load 0.440 0.440 1 100.00 0.00
Tab. de B.T. N°3 Load 0.440 0.440 1 100.00 0.00

5 Buses Total

All voltages reported by ETAP are in % of bus Nominal kV.


Base kV values of buses are calculated and used internally by ETAP.
Project: ETAP Page: 4

Location: 16.0.0C Date: 05-27-2020

Contract: SN: 4359168

Engineer: Revision: Base


Study Case: SC
Filename: EVI-LDS Config.: Normal

Line/Cable Input Data

ohms or siemens/1000 ft per Conductor (Cable) or per Phase (Line)

Line/Cable Length

ID Library Size Adj. (ft) % Tol. #/Phase T (°C) R X Y

NA2XSY - 120 mm2 35NALN1 250 4166.7 0 1 75 0.08502 0.08661 0.0000199

Line / Cable resistances are listed at the specified temperatures.


Project: ETAP Page: 5

Location: 16.0.0C Date: 05-27-2020

Contract: SN: 4359168

Engineer: Revision: Base


Study Case: SC
Filename: EVI-LDS Config.: Normal

2-Winding Transformer Input Data

Transformer Rating Z Variation % Tap Setting Adjusted

ID MVA Prim. kV Sec. kV %Z X/R + 5% - 5% % Tol. Prim. Sec. %Z

Transf. N°1 1.250 22.900 0.440 6.75 7.10 0 0 0 0 0 6.7500

Transf. N°2 1.250 22.900 0.440 6.75 7.10 0 0 0 0 0 6.7500

Transf. N°3 1.250 22.900 0.440 6.75 7.10 0 0 0 0 0 6.7500


Project: ETAP Page: 6

Location: 16.0.0C Date: 05-27-2020

Contract: SN: 4359168

Engineer: Revision: Base


Study Case: SC
Filename: EVI-LDS Config.: Normal

Branch Connections

CKT/Branch Connected Bus ID % Impedance, Pos. Seq., 100 MVAb

ID Type From Bus To Bus R X Z Y

Transf. N°1 2W XFMR Celdas Tab. de B.T. N°1 72.25 512.82 517.88

Transf. N°2 2W XFMR Celdas Tab. de B.T. N°2 72.25 512.82 517.88

Transf. N°3 2W XFMR Celdas Tab. de B.T. N°3 72.25 512.82 517.88

NA2XSY - 120 mm2 Cable N°1927 Celdas 6.76 6.88 9.64


Project: ETAP Page: 7

Location: 16.0.0C Date: 05-27-2020

Contract: SN: 4359168

Engineer: Revision: Base


Study Case: SC
Filename: EVI-LDS Config.: Normal

Power Grid Input Data

% Impedance
Power Grid Connected Bus Rating 100 MVA Base
ID ID MVASC kV R X" R/X

LDS-N°1927 N°1927 356.140 22.900 2.79395 27.93949 0.10

Total Connected Power Grids ( = 1 ): 356.140 MVA


Project: ETAP Page: 8

Location: 16.0.0C Date: 05-27-2020

Contract: SN: 4359168

Engineer: Revision: Base


Study Case: SC
Filename: EVI-LDS Config.: Normal

SHORT-CIRCUIT REPORT

3-Phase fault at bus: Celdas

Nominal kV = 22.900
Voltage c Factor = 1.10 (User-Defined)
Peak Value = 14.804 kA Method C
Steady State = 7.133 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Celdas Total 0.00 1.803 -6.902 3.8 7.133

N°1927 Celdas 24.80 1.803 -6.902 3.8 7.133

Tab. de B.T. N°1 Celdas 0.00 0.000 0.000 999.9 0.000

Tab. de B.T. N°2 Celdas 0.00 0.000 0.000 999.9 0.000

Tab. de B.T. N°3 Celdas 0.00 0.000 0.000 999.9 0.000

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 7.133 8.067 3.767

0.02 7.133 7.271 1.407

0.03 7.133 7.153 0.525

0.04 7.133 7.136 0.196

0.05 7.133 7.134 0.073

0.06 7.133 7.133 0.027

0.07 7.133 7.133 0.010

0.08 7.133 7.133 0.004

0.09 7.133 7.133 0.001

0.10 7.133 7.133 0.001

0.15 7.133 7.133 0.000

0.20 7.133 7.133 0.000

0.25 7.133 7.133 0.000

0.30 7.133 7.133 0.000


Project: ETAP Page: 9

Location: 16.0.0C Date: 05-27-2020

Contract: SN: 4359168

Engineer: Revision: Base


Study Case: SC
Filename: EVI-LDS Config.: Normal

3-Phase fault at bus: N°1927

Nominal kV = 22.900
Voltage c Factor = 1.10 (User-Defined)
Peak Value = 22.171 kA Method C
Steady State = 8.979 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

N°1927 Total 0.00 0.893 -8.934 10.0 8.979

Celdas N°1927 0.00 0.000 0.000 999.9 0.000

LDS-N°1927 N°1927 100.00 0.893 -8.934 10.0 8.979

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 8.979 12.509 8.710

0.02 8.979 10.785 5.974

0.03 8.979 9.870 4.098

0.04 8.979 9.409 2.811

0.05 8.979 9.184 1.928

0.06 8.979 9.076 1.322

0.07 8.979 9.025 0.907

0.08 8.979 9.000 0.622

0.09 8.979 8.989 0.427

0.10 8.979 8.984 0.293

0.15 8.979 8.979 0.044

0.20 8.979 8.979 0.007

0.25 8.979 8.979 0.001

0.30 8.979 8.979 0.000


Project: ETAP Page: 10

Location: 16.0.0C Date: 05-27-2020

Contract: SN: 4359168

Engineer: Revision: Base


Study Case: SC
Filename: EVI-LDS Config.: Normal

3-Phase fault at bus: Tab. de B.T. N°1

Nominal kV = 0.440
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 57.648 kA Method C
Steady State = 24.757 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Tab. de B.T. N°1 Total 0.00 3.651 -24.486 6.7 24.757

Celdas Tab. de B.T. N°1 93.06 3.651 -24.486 6.7 24.757

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 24.757 31.799 19.956

0.02 24.757 27.245 11.375

0.03 24.757 25.592 6.483

0.04 24.757 25.031 3.695

0.05 24.757 24.846 2.106

0.06 24.757 24.786 1.201

0.07 24.757 24.766 0.684

0.08 24.757 24.760 0.390

0.09 24.757 24.758 0.222

0.10 24.757 24.757 0.127

0.15 24.757 24.757 0.008

0.20 24.757 24.757 0.000

0.25 24.757 24.757 0.000

0.30 24.757 24.757 0.000


Project: ETAP Page: 11

Location: 16.0.0C Date: 05-27-2020

Contract: SN: 4359168

Engineer: Revision: Base


Study Case: SC
Filename: EVI-LDS Config.: Normal

3-Phase fault at bus: Tab. de B.T. N°2

Nominal kV = 0.440
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 57.648 kA Method C
Steady State = 24.757 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Tab. de B.T. N°2 Total 0.00 3.651 -24.486 6.7 24.757

Celdas Tab. de B.T. N°2 93.06 3.651 -24.486 6.7 24.757

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 24.757 31.799 19.956

0.02 24.757 27.245 11.375

0.03 24.757 25.592 6.483

0.04 24.757 25.031 3.695

0.05 24.757 24.846 2.106

0.06 24.757 24.786 1.201

0.07 24.757 24.766 0.684

0.08 24.757 24.760 0.390

0.09 24.757 24.758 0.222

0.10 24.757 24.757 0.127

0.15 24.757 24.757 0.008

0.20 24.757 24.757 0.000

0.25 24.757 24.757 0.000

0.30 24.757 24.757 0.000


Project: ETAP Page: 12

Location: 16.0.0C Date: 05-27-2020

Contract: SN: 4359168

Engineer: Revision: Base


Study Case: SC
Filename: EVI-LDS Config.: Normal

3-Phase fault at bus: Tab. de B.T. N°3

Nominal kV = 0.440
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 57.648 kA Method C
Steady State = 24.757 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Tab. de B.T. N°3 Total 0.00 3.651 -24.486 6.7 24.757

Celdas Tab. de B.T. N°3 93.06 3.651 -24.486 6.7 24.757

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 24.757 31.799 19.956

0.02 24.757 27.245 11.375

0.03 24.757 25.592 6.483

0.04 24.757 25.031 3.695

0.05 24.757 24.846 2.106

0.06 24.757 24.786 1.201

0.07 24.757 24.766 0.684

0.08 24.757 24.760 0.390

0.09 24.757 24.758 0.222

0.10 24.757 24.757 0.127

0.15 24.757 24.757 0.008

0.20 24.757 24.757 0.000

0.25 24.757 24.757 0.000

0.30 24.757 24.757 0.000


Project: ETAP Page: 13

Location: 16.0.0C Date: 05-27-2020

Contract: SN: 4359168

Engineer: Revision: Base


Study Case: SC
Filename: EVI-LDS Config.: Normal

Short-Circuit Summary Report

3-Phase Fault Currents

Device Capacity (kA)


Bus Device Making Short-Circuit Current (kA)
ID kV ID Type Peak Ib sym Ib asym Idc I"k ip Ib sym Ib asym Idc Ik
Celdas 22.900 Celdas Bus 7.133 14.804 7.133

22.900 F1 Fuse 25.000 33.269 7.133 14.804 7.133 8.402 4.439

22.900 F2 Fuse 25.000 33.269 7.133 14.804 7.133 8.402 4.439

22.900 F3 Fuse 25.000 33.269 7.133 14.804 7.133 8.402 4.439

N°1927 22.900 N°1927 Bus 8.979 22.171 8.979

Tab. de B.T. N°1 0.440 Tab. de B.T. N°1 Bus 24.757 57.648 24.757

0.440 -ITM1-- CB 187.000 64.000 76.511 24.757 57.648 24.757 31.799 19.956

Tab. de B.T. N°2 0.440 Tab. de B.T. N°2 Bus 24.757 57.648 24.757

0.440 -ITM2-- CB 187.000 64.000 76.511 24.757 57.648 24.757 31.799 19.956

Tab. de B.T. N°3 0.440 Tab. de B.T. N°3 Bus 24.757 57.648 24.757

0.440 -ITM3-- CB 187.000 64.000 76.511 24.757 57.648 24.757 31.799 19.956

ip is calculated using method C


Ib does not include decay of non-terminal faulted induction motors
Ik is the maximum steady state fault current
Idc is based on X/R from Method C and Ib as specified above

LV CB duty determined based on service rating.


Total through current is used for device duty.
* Indicates a device with calculated duty exceeding the device capability.
# Indicates a device with calculated duty exceeding the device marginal limit. ( 95 % times device capability)