Project: IEC Example ETAP Page: 1

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

Electrical Transient Analyzer Program

Short-Circuit Analysis

IEC 60909 Standard

3-Phase Fault Currents

Swing V-Control Load Total

Number of Buses: 1 1 12 14

Line/Cable/
XFMR2 XFMR3 Reactor Busway Impedance Tie PD Total

Number of Branches: 7 1 0 3 0 1 12

Synchronous Power Synchronous Induction Lumped


Generator Grid Motor Machines Load Total

Number of Machines: 1 1 1 3 1 7

System Frequency: 50.00

Unit System: Metric

Project Filename: Example-IEC

Output Filename: C:\ETAP 1901\Example-IEC\Duty909-1-Phase.SI1S


Project: IEC Example ETAP Page: 2

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

Adjustments

Apply Individual
Tolerance Adjustments /Global Percent

Transformer Impedance: Yes Individual

Reactor Impedance: Yes Individual

Overload Heater Resistance: No

Transmission Line Length: No

Cable / Busway Length: No

Apply Individual
Temperature Correction Adjustments /Global Degree C

Transmission Line Resistance: Yes Individual

Cable / Busway Resistance: Yes Individual


Project: IEC Example ETAP Page: 3

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

Bus Input Data

Bus Initial Voltage


ID Type Nom. kV Base kV Sub-sys %Mag. Ang.

Bus B Load 11.000 11.000 1 99.05 -0.67


Bus C Load 11.000 11.000 1 99.44 0.16
Bus3 Load 33.000 33.000 1 100.00 0.00
Bus5 Load 0.650 0.650 1 99.99 -1.46
Bus6 Gen. 6.600 6.600 1 101.00 0.00
Bus7 Load 3.300 3.300 1 102.00 3.47
Bus8 Load 3.300 3.300 1 100.11 3.06
EmergencySwBrd Load 0.400 0.400 1 98.33 -0.57
LV Bus Load 0.400 0.400 1 98.33 -0.57
LV Bus2 Load 0.650 0.650 1 100.04 -1.47
MCC1 Load 0.400 0.400 1 98.80 -1.08
Swbrd2 Load 0.400 0.400 1 99.36 -0.02
SWBRDA Load 11.000 11.000 1 98.25 -2.66
Utility Bus SWNG 33.000 33.000 1 100.00 0.00

14 Buses Total

All voltages reported by ETAP are in % of bus Nominal kV.


Base kV values of buses are calculated and used internally by ETAP .
Project: IEC Example ETAP Page: 4

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

Line/Cable/Busway Input Data

ohms or siemens/1000 m per Conductor (Cable) or per Phase (Line/Busway)

Line/Cable/Busway Length

ID Library Size Adj. (m) % Tol. #/Phase T (°C) R X Y

Cable 11 33MCUN3 120 500.0 0 1 75 0.18694 0.12200 0.0000594

Cable Main 1.0NCUS3 25 20.0 0 1 75 0.88415 0.07683 0.0000000

Cable11 11NALS3 150 800.0 0 2 75 0.25250 0.09620 0.0000000

Line / Cable / Busway resistances are listed at the specified temperatures.


Project: IEC Example ETAP Page: 5

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

2-Winding Transformer Input Data

Transformer Rating Z Variation % Tap Setting Adjusted

ID MVA Prim. kV Sec. kV %Z X/R + 5% - 5% % Tol. Prim. Sec. %Z

T1 2.000 11.000 0.400 6.25 7.10 0 0 0 0 0 6.2500

T2 2.000 11.000 0.400 6.25 7.10 0 0 0 0 0 6.2500

T3 2.500 3.300 11.000 6.25 6.00 0 0 0 0 0 6.2500

TX5 9.000 6.600 11.000 7.15 12.14 0 0 0 0 0 7.1500

Xfmr01 15.000 33.000 11.000 8.35 18.60 0 0 0 0 0 8.3500

Xfmr2 0.500 11.000 0.650 6.25 6.00 0 0 -7.5 0 0 5.7813

Xfmr04 1.250 11.000 0.400 6.25 10.67 0 0 -7.5 0 0 5.7813

3-Winding Transformer Input Data

Transformer Rating Tap Impedance Z Variation

ID Winding MVA kV % %Z X/R MVAb % Tol. + 5% - 5%

Xfmr03 Primary: 10.000 33.000 0 Zps = 8.00 15.00 10.000 0 0 0

Secondary: 5.000 11.000 0 Zpt = 7.00 12.00 10.000 0

Tertiary: 3.000 11.000 0 Zst = 7.00 12.00 10.000 0


Project: IEC Example ETAP Page: 6

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

Branch Connections

CKT/Branch Connected Bus ID % Impedance, Pos. Seq., 100 MVAb

ID Type From Bus To Bus R X Z Y

T1 2W XFMR Bus B MCC1 41.92 297.62 300.56

T2 2W XFMR Bus C Swbrd2 41.92 297.62 300.56

T3 2W XFMR Bus8 Bus C 41.42 248.50 251.93

TX5 2W XFMR Bus6 SWBRDA 6.54 79.35 79.62

Xfmr01 2W XFMR Bus3 SWBRDA 2.97 55.32 55.40

Xfmr2 2W XFMR SWBRDA LV Bus2 183.34 1100.03 1115.20

Xfmr04 2W XFMR Bus C LV Bus 41.61 444.00 445.94

Xfmr03 3W Xfmr Utility Bus Bus B 6.94 134.46 134.64

3W Xfmr Utility Bus Bus C 9.28 103.25 103.67

3W Xfmr Bus B Bus C 9.28 103.25 103.67

Cable 11 Cable Utility Bus Bus3 0.86 0.56 1.02

Cable Main Cable LV Bus2 Bus5 418.53 36.37 420.11

Cable11 Cable Bus7 Bus8 92.75 35.34 99.25

LVCB11 Tie Breaker LV Bus EmergencySwBrd


Project: IEC Example ETAP Page: 7

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

Power Grid Input Data

% Impedance
Power Grid Connected Bus Rating 100 MVA Base
ID ID MVASC kV R X" R/X

Network feeder Utility Bus 500.000 33.000 1.99007 19.90070 0.10

Total Connected Power Grids ( = 1 ): 500.000 MVA

Synchronous Generator Input Data

% Impedance in Machine Base

Synchronous Generator Connected Bus Rating Xd"


Excitation
ID Type ID MVA kV RPM % PF R Adj. Tol. R/X Xd, sat Type

GenB Steam Turbo Bus6 4.060 6.600 1500 80.00 1.000 25.00 0.0 0.04 99.00 Sal-Pole 160%

Total Connected Synchronous Generators ( = 1 ) : 4.060 MVA


Project: IEC Example ETAP Page: 8

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

Synchronous Motor Input Data

Synchronous Motor Connected Bus Rating

ID Type Qty ID HP/kW kVA kV Amp PF

Syn Motor Motor 1 Bus B 2000.00 2291.0 11.000 120.20 92.78

Total Connected Synchronous Motors ( = 1 ): 2291.0 kVA

% Impedance in Motor Base


Synchronous Motor Xd"

ID Type Qty R Adj. Tol. R/X" Exciter Type


Syn Motor Motor 1 0.466 15.38 0.0 0.03 Turbine 130%

Induction Machine Input Data

% Impedance
Induction Machine Connected Bus Rating (Motor Base)

ID Type Qty ID HP/kW kVA kV Amp PF R X" R/X" MW/PP

Ind M1 Motor 1 SWBRDA 2000.00 2350.45 11.000 123.37 88.25 3.27 21.81 0.15 1.00
Ind M2 Motor 2 SWBRDA 2000.00 2350.21 11.000 123.35 88.32 3.27 21.81 0.15 2.00
Mtr6 Motor 2 MCC1 60.00 53.74 0.400 77.56 90.82 5.90 15.59 0.38 0.02

Total Connected Induction Machines ( = 5 ): 7158.3 kVA


Project: IEC Example ETAP Page: 9

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

Lumped Load Input Data

Motor Loads
Lumped Load
% Impedance
Lumped Load Connected Bus Rating % Load Loading Machine Base

ID ID kVA kV Amp % PF MTR STAT kW kvar R X" R/X" MW/PP

LUMP2 Bus7 200.0 3.300 34.99 85.00 80 20 136.0 84.3 2.28 15.21 0.15 0.14

Total Connected Lumped Loads ( = 1 ): 200.0 kVA


Project: IEC Example ETAP Page: 10

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

SHORT-CIRCUIT REPORT

3-Phase fault at bus: Bus B

Nominal kV = 11.000
Voltage c Factor = 1.10 (Maximum If)
Peak Value = 16.904 kA Method C
Steady State = 6.446 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus B Total 0.00 0.592 -6.585 11.1 6.612

MCC1 Bus B 2.09 0.013 -0.034 2.7 0.037

Utility Bus Bus B 88.32 0.214 -3.436 16.0 3.443

Bus C Bus B 45.70 0.340 -2.289 6.7 2.314

Syn Motor Bus B 110.00 0.025 -0.826 33.0 0.826

Mtr6 MCC1 110.00 0.352 -0.941 2.7 1.005

Bus3 Utility Bus 88.37 0.011 -0.142 12.9 0.143

Bus C Utility Bus 45.70 -0.036 0.720 20.0 0.721

Network feeder Utility Bus 110.00 0.096 -1.723 17.9 1.726

Swbrd2 Bus C 45.70 0.000 0.000 999.9 0.000

Bus8 Bus C 54.20 0.217 -0.117 0.5 0.246

LV Bus Bus C 46.91 0.015 -0.012 0.8 0.019

SWBRDA Bus3 92.88 0.011 -0.142 12.9 0.143

Bus7 Bus8 58.58 0.722 -0.389 0.5 0.820

PVA3 LV Bus 46.91 0.421 -0.327 0.8 0.534

WTG1 Bus7 58.58 0.728 -0.291 0.4 0.784


Project: IEC Example ETAP Page: 11

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

3-Phase fault at bus: Bus C

Nominal kV = 11.000
Voltage c Factor = 1.10 (Maximum If)
Peak Value = 16.929 kA Method C
Steady State = 6.664 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus C Total 0.00 0.881 -6.775 7.7 6.832

Swbrd2 Bus C 0.00 0.000 0.000 999.9 0.000

Bus8 Bus C 17.20 0.294 -0.205 0.7 0.358

LV Bus Bus C 2.20 0.022 -0.013 0.6 0.026

Utility Bus Bus C 86.54 0.407 -4.362 10.7 4.381

Bus B Bus C 43.47 0.158 -2.195 13.9 2.201

Bus7 Bus8 21.43 0.980 -0.682 0.7 1.194

PVA3 LV Bus 2.20 0.615 -0.361 0.6 0.713

Bus3 Utility Bus 86.59 0.016 -0.153 9.3 0.154

Bus B Utility Bus 43.47 -0.043 0.558 13.0 0.560

Network feeder Utility Bus 110.00 0.162 -1.859 11.5 1.866

MCC1 Bus B 44.69 0.008 -0.021 2.6 0.022

Syn Motor Bus B 110.00 0.021 -0.499 23.8 0.500

LUMP2 Bus7 110.00 0.005 -0.167 30.7 0.167

WTG1 Bus7 21.43 0.975 -0.515 0.5 1.102

SWBRDA Bus3 91.46 0.016 -0.153 9.3 0.154

Mtr6 MCC1 110.00 0.219 -0.567 2.6 0.608


Project: IEC Example ETAP Page: 12

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

3-Phase fault at bus: Bus3

Nominal kV = 33.000
Voltage c Factor = 1.10 (Maximum If)
Peak Value = 22.552 kA Method C
Steady State = 9.024 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus3 Total 0.00 1.339 -9.434 7.0 9.529

Utility Bus Bus3 5.16 1.261 -8.718 6.9 8.808

SWBRDA Bus3 22.82 0.079 -0.716 9.1 0.721

Bus B Utility Bus 16.67 0.036 -0.169 4.7 0.173

Bus C Utility Bus 12.33 0.075 -0.144 1.9 0.163

Network feeder Utility Bus 110.00 1.150 -8.404 7.3 8.482

Bus6 SWBRDA 33.16 0.021 -0.684 32.8 0.684

LV Bus2 SWBRDA 26.91 0.019 -0.015 0.8 0.024

Ind M1 SWBRDA 110.00 0.065 -0.483 7.4 0.488

Ind M2 SWBRDA 110.00 0.131 -0.967 7.4 0.976

MCC1 Bus B 18.36 0.011 -0.029 2.5 0.031

Bus C Bus B 12.33 0.061 0.222 3.6 0.230

Syn Motor Bus B 110.00 0.035 -0.701 20.2 0.702

Swbrd2 Bus C 12.33 0.000 0.000 999.9 0.000

Bus8 Bus C 26.14 0.265 -0.198 0.7 0.331

LV Bus Bus C 13.67 0.020 -0.013 0.6 0.024

GenB Bus6 110.00 0.035 -1.140 32.8 1.141

Bus5 LV Bus2 26.91 0.000 0.000 999.9 0.000

Inv1-1 LV Bus2 26.91 0.017 -0.024 1.4 0.029

PVA6 LV Bus2 26.91 0.306 -0.222 0.7 0.378

PVA3 LV Bus 13.67 0.561 -0.361 0.6 0.667


Project: IEC Example ETAP Page: 13

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

3-Phase fault at bus: Bus5

Nominal kV = 0.650
Voltage c Factor = 1.05 (Maximum If)
Peak Value = 12.602 kA Method C
Steady State = 7.045 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus5 Total 0.00 3.214 -6.543 2.0 7.290

LV Bus2 Bus5 34.48 3.214 -6.543 2.0 7.290

SWBRDA LV Bus2 100.92 3.272 -6.164 1.9 6.978

Inv1-1 LV Bus2 34.48 -0.013 -0.023 1.7 0.027

PVA6 LV Bus2 34.48 -0.044 -0.356 8.1 0.359

Bus6 SWBRDA 101.42 0.015 -0.031 2.1 0.035

Bus3 SWBRDA 103.83 0.140 -0.269 1.9 0.303

Ind M1 SWBRDA 105.00 0.013 -0.021 1.6 0.025

Ind M2 SWBRDA 105.00 0.026 -0.042 1.6 0.050


Project: IEC Example ETAP Page: 14

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

3-Phase fault at bus: Bus6

Nominal kV = 6.600
Voltage c Factor = 1.10 (Maximum If)
Peak Value = 21.457 kA Method C
Steady State = 7.683 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus6 Total 0.00 0.683 -8.420 12.3 8.447

SWBRDA Bus6 62.04 0.618 -6.789 11.0 6.817

GenB Bus6 110.00 0.065 -1.631 25.0 1.632

Bus3 SWBRDA 96.61 0.246 -3.266 13.3 3.275

LV Bus2 SWBRDA 64.61 0.014 -0.010 0.7 0.017

Ind M1 SWBRDA 110.00 0.037 -0.266 7.2 0.268

Ind M2 SWBRDA 110.00 0.074 -0.532 7.2 0.537

Utility Bus Bus3 96.99 0.082 -1.089 13.3 1.092

Bus5 LV Bus2 64.61 0.000 0.000 999.9 0.000

Inv1-1 LV Bus2 64.61 0.008 -0.016 2.1 0.018

PVA6 LV Bus2 64.61 0.224 -0.147 0.7 0.268


Project: IEC Example ETAP Page: 15

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

3-Phase fault at bus: Bus7

Nominal kV = 3.300
Voltage c Factor = 1.10 (Maximum If)
Peak Value = 10.938 kA Method C
Steady State = 5.457 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus7 Total 0.00 2.944 -5.239 1.8 6.009

Bus8 Bus7 27.50 1.735 -4.526 2.6 4.847

LUMP2 Bus7 110.00 0.030 -0.198 6.7 0.200

WTG1 Bus7 0.00 1.179 -0.515 0.4 1.287

Bus C Bus8 86.98 1.735 -4.526 2.6 4.847

Swbrd2 Bus C 86.98 0.000 0.000 999.9 0.000

LV Bus Bus C 87.34 0.009 -0.004 0.4 0.010

Utility Bus Bus C 105.04 0.347 -0.899 2.6 0.963

Bus B Bus C 96.07 0.164 -0.455 2.8 0.484

PVA3 LV Bus 87.34 0.254 -0.109 0.4 0.276


Project: IEC Example ETAP Page: 16

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

3-Phase fault at bus: Bus8

Nominal kV = 3.300
Voltage c Factor = 1.10 (Maximum If)
Peak Value = 14.653 kA Method C
Steady State = 6.225 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus8 Total 0.00 1.965 -6.313 3.2 6.612

Bus7 Bus8 7.58 1.138 -0.699 0.6 1.336

Bus C Bus8 81.72 0.827 -5.614 6.8 5.675

LUMP2 Bus7 110.00 0.030 -0.184 6.1 0.187

WTG1 Bus7 7.58 1.108 -0.515 0.5 1.222

Swbrd2 Bus C 81.72 0.000 0.000 999.9 0.000

LV Bus Bus C 82.19 0.010 -0.005 0.5 0.011

Utility Bus Bus C 103.97 0.167 -1.117 6.7 1.129

Bus B Bus C 92.91 0.072 -0.563 7.9 0.567

PVA3 LV Bus 82.19 0.276 -0.131 0.5 0.306

Bus3 Utility Bus 103.99 0.008 -0.040 5.1 0.041

Bus B Utility Bus 92.91 -0.019 0.143 7.5 0.144

Network feeder Utility Bus 110.00 0.067 -0.475 7.1 0.480

MCC1 Bus B 93.22 0.002 -0.005 2.2 0.006

Syn Motor Bus B 110.00 0.012 -0.128 10.4 0.129


Project: IEC Example ETAP Page: 17

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

3-Phase fault at bus: EmergencySwBrd

Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Peak Value = 71.942 kA Method C
Steady State = 28.549 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

EmergencySwBrd Total 0.00 3.790 -28.959 7.6 29.206

Bus C LV Bus 88.90 3.165 -28.598 9.0 28.773

PVA3 LV Bus 0.00 0.625 -0.361 0.6 0.722

Swbrd2 Bus C 88.90 0.000 0.000 999.9 0.000

Bus8 Bus C 93.42 0.120 -0.071 0.6 0.139

Utility Bus Bus C 101.58 0.001 -0.645 458.1 0.645

Bus B Bus C 95.25 -0.006 -0.324 51.2 0.324

Bus7 Bus8 95.98 0.400 -0.236 0.6 0.465

Bus3 Utility Bus 101.59 0.002 -0.024 10.9 0.024

Bus B Utility Bus 95.25 0.001 0.082 71.3 0.082

Network feeder Utility Bus 105.00 -0.003 -0.274 95.7 0.274

MCC1 Bus B 95.43 0.001 -0.003 3.5 0.003

Syn Motor Bus B 105.00 -0.004 -0.073 19.6 0.074

WTG1 Bus7 95.98 0.409 -0.218 0.5 0.463

LV Bus EmergencySwBrd 0.00 3.790 -28.959 7.6 29.206


Project: IEC Example ETAP Page: 18

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

3-Phase fault at bus: LV Bus

Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Peak Value = 71.942 kA Method C
Steady State = 28.549 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

LV Bus Total 0.00 3.790 -28.959 7.6 29.206

Bus C LV Bus 88.90 3.165 -28.598 9.0 28.773

PVA3 LV Bus 0.00 0.625 -0.361 0.6 0.722

Swbrd2 Bus C 88.90 0.000 0.000 999.9 0.000

Bus8 Bus C 93.42 0.120 -0.071 0.6 0.139

Utility Bus Bus C 101.58 0.001 -0.645 458.1 0.645

Bus B Bus C 95.25 -0.006 -0.324 51.2 0.324

Bus7 Bus8 95.98 0.400 -0.236 0.6 0.465

Bus3 Utility Bus 101.59 0.002 -0.024 10.9 0.024

Bus B Utility Bus 95.25 0.001 0.082 71.3 0.082

Network feeder Utility Bus 105.00 -0.003 -0.274 95.7 0.274

MCC1 Bus B 95.43 0.001 -0.003 3.5 0.003

Syn Motor Bus B 105.00 -0.004 -0.073 19.6 0.074

WTG1 Bus7 95.98 0.409 -0.218 0.5 0.463

LV Bus EmergencySwBrd 0.00 0.000 0.000 9999.0 0.000


Project: IEC Example ETAP Page: 19

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

3-Phase fault at bus: LV Bus2

Nominal kV = 0.650
Voltage c Factor = 1.05 (Maximum If)
Peak Value = 18.696 kA Method C
Steady State = 8.161 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

LV Bus2 Total 0.00 1.691 -8.102 4.8 8.277

Bus5 LV Bus2 0.00 0.000 0.000 999.9 0.000

SWBRDA LV Bus2 99.94 1.281 -7.857 6.1 7.960

Inv1-1 LV Bus2 0.00 0.026 -0.024 0.9 0.035

PVA6 LV Bus2 0.00 0.385 -0.222 0.6 0.444

Bus6 SWBRDA 100.55 0.005 -0.040 8.6 0.040

Bus3 SWBRDA 103.57 0.053 -0.342 6.5 0.346

Ind M1 SWBRDA 105.00 0.006 -0.028 4.5 0.028

Ind M2 SWBRDA 105.00 0.012 -0.055 4.5 0.057

GenB Bus6 105.00 0.008 -0.066 8.6 0.066

Utility Bus Bus3 103.62 0.018 -0.114 6.5 0.115


Project: IEC Example ETAP Page: 20

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

3-Phase fault at bus: MCC1

Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Peak Value = 95.639 kA Method C
Steady State = 39.036 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

MCC1 Total 0.00 5.643 -39.803 7.1 40.201

Bus B MCC1 81.73 5.298 -38.888 7.3 39.248

Mtr6 MCC1 105.00 0.346 -0.914 2.6 0.977

Utility Bus Bus B 100.51 0.062 -0.730 11.7 0.733

Bus C Bus B 91.97 0.122 -0.510 4.2 0.524

Syn Motor Bus B 105.00 0.008 -0.175 21.6 0.175

Bus3 Utility Bus 100.52 0.004 -0.031 8.3 0.031

Bus C Utility Bus 91.97 0.002 0.145 78.0 0.145

Network feeder Utility Bus 105.00 0.015 -0.358 23.6 0.358

Swbrd2 Bus C 91.97 0.000 0.000 999.9 0.000

Bus8 Bus C 96.42 0.120 -0.070 0.6 0.139

LV Bus Bus C 92.47 0.008 -0.005 0.6 0.010

PVA3 LV Bus 92.47 0.231 -0.137 0.6 0.268


Project: IEC Example ETAP Page: 21

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

3-Phase fault at bus: Swbrd2

Nominal kV = 0.400
Voltage c Factor = 1.05 (Maximum If)
Peak Value = 93.664 kA Method C
Steady State = 39.275 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Swbrd2 Total 0.00 5.891 -38.946 6.6 39.389

Bus C Swbrd2 82.02 5.891 -38.946 6.6 39.389

Bus8 Bus C 85.11 0.135 -0.037 0.3 0.140

LV Bus Bus C 82.49 0.010 -0.004 0.4 0.011

Utility Bus Bus C 100.11 0.053 -0.915 17.4 0.917

Bus B Bus C 91.10 0.017 -0.460 27.8 0.460

Bus7 Bus8 87.75 0.449 -0.123 0.3 0.466

PVA3 LV Bus 82.49 0.279 -0.121 0.4 0.304

Bus3 Utility Bus 100.12 0.004 -0.033 8.3 0.033

Bus B Utility Bus 91.10 -0.005 0.117 24.2 0.117

Network feeder Utility Bus 105.00 0.018 -0.389 21.1 0.389

MCC1 Bus B 91.36 0.002 -0.004 2.9 0.005

Syn Motor Bus B 105.00 0.001 -0.104 192.6 0.104

WTG1 Bus7 87.75 0.458 -0.089 0.2 0.466


Project: IEC Example ETAP Page: 22

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

3-Phase fault at bus: SWBRDA

Nominal kV = 11.000
Voltage c Factor = 1.10 (Maximum If)
Peak Value = 25.596 kA Method C
Steady State = 8.311 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

SWBRDA Total 0.00 0.941 -10.163 10.8 10.206

Bus6 SWBRDA 13.09 0.039 -0.862 22.2 0.863

Bus3 SWBRDA 79.01 0.605 -7.461 12.3 7.485

LV Bus2 SWBRDA 5.82 0.023 -0.015 0.6 0.027

Ind M1 SWBRDA 110.00 0.091 -0.608 6.7 0.615

Ind M2 SWBRDA 110.00 0.182 -1.217 6.7 1.231

GenB Bus6 110.00 0.065 -1.437 22.2 1.438

Utility Bus Bus3 79.88 0.202 -2.487 12.3 2.495

Bus5 LV Bus2 5.82 0.000 0.000 999.9 0.000

Inv1-1 LV Bus2 5.82 0.025 -0.024 0.9 0.035

PVA6 LV Bus2 5.82 0.368 -0.222 0.6 0.430

Bus B Utility Bus 83.76 0.012 -0.050 4.3 0.051

Bus C Utility Bus 82.74 0.031 -0.045 1.5 0.055

Network feeder Utility Bus 110.00 0.159 -2.392 15.0 2.397


Project: IEC Example ETAP Page: 23

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

3-Phase fault at bus: Utility Bus

Nominal kV = 33.000
Voltage c Factor = 1.10 (Maximum If)
Peak Value = 24.155 kA Method C
Steady State = 9.292 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Utility Bus Total 0.00 1.054 -9.742 9.2 9.798

Bus3 Utility Bus 0.42 0.080 -0.714 8.9 0.719

Bus B Utility Bus 13.64 0.031 -0.175 5.7 0.177

Bus C Utility Bus 9.77 0.072 -0.148 2.0 0.165

Network feeder Utility Bus 110.00 0.870 -8.704 10.0 8.748

SWBRDA Bus3 23.02 0.080 -0.714 8.9 0.719

MCC1 Bus B 15.47 0.011 -0.030 2.8 0.032

Bus C Bus B 9.77 0.072 0.231 3.2 0.242

Syn Motor Bus B 110.00 0.009 -0.725 76.6 0.725

Swbrd2 Bus C 9.77 0.000 0.000 999.9 0.000

Bus8 Bus C 25.35 0.268 -0.200 0.7 0.335

LV Bus Bus C 11.60 0.021 -0.013 0.6 0.025

Bus6 SWBRDA 33.34 0.023 -0.682 29.9 0.683

LV Bus2 SWBRDA 27.07 0.019 -0.015 0.8 0.024

Ind M1 SWBRDA 110.00 0.067 -0.482 7.2 0.487

Ind M2 SWBRDA 110.00 0.133 -0.964 7.2 0.974

Mtr6 MCC1 110.00 0.294 -0.831 2.8 0.881

Bus7 Bus8 29.73 0.893 -0.668 0.7 1.115

PVA3 LV Bus 11.60 0.571 -0.361 0.6 0.675

Inv1-1 LV Bus2 27.07 0.016 -0.024 1.4 0.029

PVA6 LV Bus2 27.07 0.305 -0.222 0.7 0.377

WTG1 Bus7 29.73 0.894 -0.515 0.6 1.032


Project: IEC Example ETAP Page: 24

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

Short-Circuit Summary Report

3-Phase Fault Currents

Device Capacity (kA)


Bus Device Making Short-Circuit Current (kA)
ID kV ID Type Peak Ib sym Ib asym Idc I"k ip Ib sym Ib asym Idc Ik
Bus B 11.000 Bus B SwtchRack 21.000 6.612 16.904 6.446

11.000 CB31 CB 63.000 25.000 25.292 3.831 5.752 14.693 5.742 5.871 1.225

11.000 CB B1 CB 67.000 26.300 28.491 10.956 6.577 16.813 6.378 7.077 3.067

Bus C 11.000 Bus C SwtchRack 21.000 6.832 16.929 6.664

11.000 CB32 CB 40.000 16.000 17.515 7.125 6.581 16.536 6.528 6.946 2.372

11.000 CB C1 CB 67.000 26.300 28.491 10.956 6.832 16.929 6.754 7.105 2.205

11.000 Fuse C1 Fuse 63.000 83.839 6.816 16.909 6.787 9.859 7.151

11.000 CB6 CB 63.000 25.000 25.292 3.831 6.596 16.555 6.528 6.566 0.713

Bus3 33.000 Bus3 Bus 9.529 22.552 9.024

Bus5 0.650 Bus5 Bus 7.290 12.602 7.045

Bus6 6.600 Bus6 Bus 8.447 21.457 7.683

6.600 CB23 CB 67.000 26.300 28.491 10.956 6.817 17.309 6.702 7.262 2.795

Bus7 3.300 Bus7 Bus 6.009 10.938 5.457

3.300 CB11 CB 63.000 25.000 25.292 3.831 5.043 9.595 4.892 4.892 0.000

Bus8 3.300 Bus8 Bus 6.612 14.653 6.225

EmergencySwBrd 0.400 EmergencySwBrd SwtchBoard 130.000 29.206 71.942 28.549

0.400 LVCB11 CB 88.200 42.000 42.721 29.206 71.942 29.206 35.103 19.473

LV Bus 0.400 LV Bus SwtchBoard 130.000 29.206 71.942 28.549

0.400 CB9 CB 187.000 85.000 88.376 28.773 71.339 28.773 34.743 19.473

0.400 LVCB11 CB 88.200 42.000 42.721 29.206 71.942 29.206 35.103 19.473

0.400 CB8 CB 52.500 25.000 25.956 28.773 71.339 * 28.773 * 36.532 * 22.510

LV Bus2 0.650 LV Bus2 Bus 8.277 18.696 8.161

0.650 CB16 CB 3.000 3.000 3.000 7.960 18.253 * 7.960 * 8.558 * 3.143

0.650 CB15 CB 3.000 3.000 3.000 8.277 18.696 * 8.277 * 8.853 * 3.143

0.650 Fuse Main Fuse 120.000 159.693 8.277 18.696 8.277 10.682 6.752

0.650 CB13 CB 3.000 3.000 3.000 7.988 18.291 * 7.988 * 8.584 * 3.143

0.650 CB14 CB 3.000 3.000 3.000 8.248 18.656 * 8.248 * 8.827 * 3.143

MCC1 0.400 MCC1 Bus 40.201 95.639 39.036

0.400 Fuse2 Fuse 50.000 66.539 40.201 95.639 39.821 54.967 37.889

0.400 LVCB1 CB 143.000 65.000 65.000 39.248 93.367 39.248 39.248 0.004

Swbrd2 0.400 Swbrd2 Bus 39.389 93.664 39.275

0.400 LVCB2 CB 143.000 65.000 65.000 39.389 93.664 39.389 39.389 0.003

SWBRDA 11.000 SWBRDA SwtchGear 10.206 25.596 8.311

11.000 CB22 CB 67.000 26.300 28.491 10.956 9.344 23.430 8.744 9.363 3.349

11.000 CB A1 CB 67.000 8.000 8.666 3.333 10.206 25.596 9.497 * 10.178 * 3.659 *
Project: IEC Example ETAP Page: 25

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

3-Phase Fault Currents

Device Capacity (kA)


Bus Device Making Short-Circuit Current (kA)
ID kV ID Type Peak Ib sym Ib asym Idc I"k ip Ib sym Ib asym Idc Ik
SWBRDA 11.000 Fuse C3 Fuse 50.000 66.539 10.190 25.575 10.031 14.888 11.002

11.000 CB21 CB 62.500 25.000 30.895 18.152 7.485 18.780 7.485 8.924 4.860

Utility Bus 33.000 Utility Bus Open Air 9.798 24.155 9.292

33.000 CB1 CB 78.700 31.500 32.873 9.403 8.748 21.631 8.748 8.876 1.501

33.000 CB2 CB 62.500 25.000 26.090 7.463 9.079 22.383 9.016 9.148 1.547

33.000 CB3 CB 62.500 25.000 26.090 7.463 9.467 23.404 9.313 9.454 1.624

ip is calculated using method C


Ib does not include decay of non-terminal faulted induction motors
Ik is the maximum steady state fault current
Idc is based on X/R from Method C and Ib as specified above

LV CB duty determined based on service rating.


Maximum through current is used for device duty.
* Indicates a device with calculated duty exceeding the device capability.
# Indicates a device with calculated duty exceeding the device marginal limit . ( 90 % times device capability)
Project: IEC Example ETAP Page: 26

Location: Irvine, Califonia 19.0.1C Date: 29-05-2020

Contract: 987654321 SN:

Engineer: OTI Revision: Base


Study Case: Duty909
Filename: Example-IEC Config.: Normal

This is the remarks first line and it appears in the header of every report.

Short-Circuit Summary Report

Device Capacity 3-Phase Short-Circuit Duty Results


Rated Thermal Thermal
Bus ID Device ID Ithr (kA) Tkr (sec.) Energy (MJ) Ith (kA) Tkr (sec.) Energy (MJ)

Bus B CB31 26.300 3.00 2075.07 6.666 3.00 133.31

Bus B CB B1 26.300 3.00 2075.07 6.666 3.00 133.31

Bus C CB32 26.300 3.00 2075.07 6.877 3.00 141.87

Bus C CB C1 26.300 3.00 2075.07 6.877 3.00 141.87

Bus C CB6 26.300 3.00 2075.07 6.877 3.00 141.87

Bus6 CB23 26.300 3.00 2075.07 7.952 3.00 189.72

Bus7 CB11 25.000 3.00 1875.00 5.616 3.00 94.61

EmergencySwBrd LVCB11 42.000 1.00 1764.00 29.740 1.00 884.46

LV Bus CB9 85.000 1.00 7225.00 29.740 1.00 884.46

LV Bus LVCB11 42.000 1.00 1764.00 29.740 1.00 884.46

LV Bus CB8 5.000 1.00 25.00 29.740 1.00 884.46 *

LV Bus2 CB16 5.000 1.00 25.00 8.363 1.00 69.95 *

LV Bus2 CB15 5.000 1.00 25.00 8.363 1.00 69.95 *

LV Bus2 CB13 5.000 1.00 25.00 8.363 1.00 69.95 *

LV Bus2 CB14 5.000 1.00 25.00 8.363 1.00 69.95 *

MCC1 LVCB1 50.000 1.00 2500.00 40.734 1.00 1659.25

Swbrd2 LVCB2 50.000 1.00 2500.00 39.909 1.00 1592.76

SWBRDA CB22 26.300 3.00 2075.07 9.116 3.00 249.31

SWBRDA CB A1 26.300 3.00 2075.07 9.116 3.00 249.31

Utility Bus CB1 31.500 3.00 2976.75 9.855 3.00 291.34

Ithr = Rated short-time withstand current (Icw for low voltage circuit breaker)
Tkr = Rated short-time
Ith = Thermal equivalent short-time current

* Indicates a device with calculated duty exceeding the device capability.


# Indicates a device with calculated duty exceeding the device marginal limit . ( 90 % times device capability)