TEST REPORT FOR

SEL MOTOR PROTECTION SEL 710


RELAY-SEL 710
DATE: 21.06.2018

Project : SINGARENI THERMAL POWER PLANT, TELANGANA

Client : M/s STEAG ENEGY SERVICES PVT LTD

End Client : M/S SINGARENI

Panel Ref : 1A-COMPRESSOR

Relay Make & Model : SEL-710

Serial No : 3140060035

CT & VT Ratio : 150/50A

1. Phase Over Current TOC – Non Directional Current (I) – 4XFLA A , TD- 0s ,FLA:0.6

Phase Set Current (A) Inj. Current(A) Actual Tripping Trip Time(s)
Time (s)
R-N 2.4 2.4 0 0.023

Y-N 2.4 2.4 0 0.022

B-N 2.4 2.4 0 0.029

2. [50N ] Current (I) – 5A : Time Delay- 0 s

Phase Set Current (A) Inj. Current(A) Actual Tripping Trip Time(s)
Time (s)
R-N 5 5 0 0.024

Y-N 5 5 0 0.029

B-N 5 5 0 0.031

3. JAM Current (I) – 2XFLA A ,Time Delay- 5 s FLA:0.6

PROTECTION ENGG M/S STEAG ENERGY SERVICES LTD

JAYAMKONDAN V MR.JEYAKUMAR
TEST REPORT FOR
SEL MOTOR PROTECTION SEL 710
RELAY-SEL 710
DATE: 21.06.2018

Phase Set Current (A) Inj. Current(A) Actual Tripping Trip Time(s)
Time (s)
R-N 1.2 1.2 5 5.21

Y-N 1.2 1.2 5 5.19

B-N 1.2 1.2 5 5.16

4. CURRENT IMBALANCE Current (I) – 10%A ,Time Delay- 5 s

Phase Set Current (A) Inj. Current(A) Actual Tripping Trip Time(s)
Time (s)
R-N 0.54 0.54 5 5.01

Y-N 0.54 0.54 5 5.02

B-N 0.54 0.54 5 5.12

5. UNDER VOLTAGE Voltage (I) – 0.7xVnm ,Time Delay- 2 s

Phase Sett Voltage (v) Inj. Voltage(v) Actual Tripping Trip Time(s)
Time (s)

PROTECTION ENGG M/S STEAG ENERGY SERVICES LTD

JAYAMKONDAN V MR.JEYAKUMAR
TEST REPORT FOR
SEL MOTOR PROTECTION SEL 710
RELAY-SEL 710
DATE: 21.06.2018

R-N 45 45 2 2.00

Y-N 45 45 2 2.03

B-N 45 45 2 2.01

6. THERMAL OVER LOAD

Phase Inj. Current(A) Trip Time(s)

R,Y,B 1.33 749

R,Y,B 1.5 630

R,Y,B 1.6 420

Check List:

1. LED Functions has been checked and found ok.


2. Relay operations has been found satisfied and fit for service.

PROTECTION ENGG M/S STEAG ENERGY SERVICES LTD

JAYAMKONDAN V MR.JEYAKUMAR