Professional Documents
Culture Documents
The above arrangement has been used in important 400 kV and 750 kV
substations
Ring Main Arrangement
Mesh Arrangement
Principle of Circulating Current
Linear Coupler
High Impedance Relay
• A high resistance is connected in series with
relay operating coil to make it more sensitive
for internal and external faults.
• Resistance is called stabilizing resitance
High Impedance Relay
Overcurrent Relay
• The operating time of all Overcurrent Relay
Characteristics tends to become asymptotic to
a definite minimum value with increase in the
value of current.
• This is inherent in electromagnetic relays due
to saturation of the magnetic circuit. So by
varying the point of saturation different
Overcurrent Relay Characteristics are obtained.
Definite time.
Inverse definite minimum time (IDMT).
Very inverse.
Extremely inverse.
Overcurrent relays
• The relay has two electromagnets. The upper
electromagnet has two windings, one of these
is primary and is connected to the secondary
of a CT in the line to be protected and is
tapped at intervals.
• The plug bridge is usually arranged to give
seven sections of tappings to give overcurrent
range from 50% to 200% in steps of 25%.
• If the relay is required to response for earth
fault the steps are arranged to give a range
from 10 % to 70 % or 20 to 80% in steps of
10%.
Selection of Pick up value
• Thus pick-up current equals the rated secondary
current of CT multiplied by current setting.
• For example suppose that an overcurrent relay having
a current setting of 150% is connected to a supply
circuit through a CT of 500/5 A.
• The rated secondary current of CT is 5 A and,
therefore, the pick-up value will be 1.5 x 5 i.e., 7.5 A.
• It means that with above current setting, the relay will
actually operate for a relay current equal to or greater
than 7.5 A.
Working
• When the pin is withdrawn for the purpose of
changing the setting value while the relay in
service, the relay automatically adopts higher
setting, thus the CT’s secondary is not open-
circuited.
Working
• The second winding is energized by induction
from the primary, and is connected in series
with the winding on the lower magnet.
• By this arrangement, leakage fluxes of upper
and lower electromagnets are sufficiently
displaced in space and phase to set up a
rotational torque on the aluminum disc
suspended between the two magnets, as in
the shaded pole induction disc motor.
• The torque of these relays as shown earlier is
proportional to Φ1Φ2 sin α where Φ1 and Φ2 are
the two fluxes cutting the disc or cup and α is the
angle between them.
• Where both fluxes are produced by the same
quantity, as in current or voltage operated relays,
then below saturation the torque is proportional
to I2, the coil current, or T = KI2
• If the core is made to saturate at a very early
stage with the result that by increasing I, K
decreases so that the time of operation
remains same over the working range.
Working
where
T = the required time of operation
Tm = the time obtained from the relay
characteristic curve at TMS=1.0, and using the
PSM equivalent to maximum fault current.
Overcurrent relay Settings
• Thus, if the TMS is 0.1 and the time obtained
from the curve, for a particular current is 4.0
seconds the actual operating time will be 4.0 X
0.1=0.4 second.
• In other words, if the time from the curve is
4.0 seconds and the operating time required is
0.4 second the TMS should be 0.4/4.0=0.1.
Increasing the TMS has the effect of moving
the curve higher on the time scale.
Overcurrent relay Settings
Time-Graded Systems
• To ensure selectivity of operation under all
circumstances in a radial feeder, the operating time
of the protection is increased from the far end of
protected circuit towards the generating source.
• This is very conveniently achieved with the help
of definite-timedelay relays, which usually consists
of an instantaneous overcurrent relay followed by a
timing relay the contacts of which trip the breaker
Time-Graded Systems
where
A = relay pickup current in steady state rms
amperes.
B = the steady state rms current which when fully
offset will just pick up the relay.
Current Graded Systems
• The IDMT relay at A must discriminate with the
instantaneous element at B for a fault at B, and
with the IDMT relay at B for a fault at F (the
limit of reach of the instantaneous element at
B). If there were not an instantaneous relay at
B the IDMT relay at A would require the slower
characteristic curve (i).
• .
Current Graded Systems
• Schemes where speed of fault clearance is
proportional to the current are usually
preferred, i.e. the higher the current the faster
the relay operates. The schemes that follow
have this characteristic
Current/Time-Graded Systems
• Current/time grading is possible with inverse-time
Overcurrent Protection of Feeders.
• The most widely used is the IDMT characteristic
where grading is possible over a wide range of
currents and the relay can be set, within the design
limits, to any value of definite minimum time
required.
• Other inverse characteristics, viz. very inverse and
extremely inverse characteristics are also sometimes
employed for the same purpose.
Current/Time-Graded Systems
• If the fault current reduces substantially as the
fault position moves away from the source
some advantage can be gained by using very
inverse relays instead of IDMT relays.
• The long operating time at low values of
overloads of IDMT relays make extremely
inverse relays eminently suitable. Where
grading with fuses is required it is the ideal
choice.
Coordination of Inverse-Time Overcurrent
Relays
• Selection of current setting:
• It is necessary to calculate the maximum fault
current which can occur at each relay position.
A three phase fault under maximum
generation gives the maximum fault current
and phase to phase fault under minimum
generation gives the minimum fault current.
Coordination of Inverse-Time Overcurrent
Relays
• These are the two extreme values of fault
current and the relay has to respond between
these conditions.
• On a radial system the lowest setting must be
at the farthest end; the settings being increased
for the subsequent relays towards the source.
• As per Indian Standards the operating value
should not exceed 130% of the setting, hence
Selection of time setting
• For selective operation when there are a
number of relays connected in series, the relay
farthest from the source should be sot to
operate in the minimum possible time.
• For succeeding relays towards the source a
time delay step is given. For inverse-time
Overcurrent Protection of Feeders the time
setting should be done at the maximum fault
current.
Selection of time setting
• If the relay has proper selectivity at maximum
fault current, it will automatically have a
higher selectivity at the minimum fault
current, as the curve is more inverse on lower
current region.
Directional Relays