CT Knee Point Voltage Calculation Sheet

Primary Secondary Volt Resistance Resistance Length


In MVA In AMP In kV In ohm In ohm/km in Meter In %
1 CT ratio of the trasformer REF Protection - 4000 1 - - - - -
2 Transformer Rating, MVA 50 - - - - - - -
3 % Impedance, %Z - - - - - - - 13.9
4 Voltage of Line Side, KVLV - - - 11 - - - -
5 CT Secondary Resistance, RCT (ohm) - - - - 6 - - -
6 Resistance of control cable of 2.5 Sq. mm. - 8.5 -
7 Loop Length of Control Cable - - - - - - 120

Calculation:
1) Fault Current at Primary Side of CT (kA) = MVA/*100(%Z*1.732*K LV) 18.88
2) Fault Current at Secondary Side of CT, I f (A)= 4.72
3) Cable Lead Resistance, RL (Ohm)= 1.02

4) Knee Point Voltage Vk (Volt) = 2If(RCT+2RL) #NAME?

REMARKS : -
Knee Point Voltage of CT provided by CGL for REF CT = 115V and for Differental CT = 200V are in order.