Professional Documents
Culture Documents
Line/Cable/
XFMR2 XFMR3 Reactor Busway Impedance Tie PD Total
Number of Branches: 5 0 0 3 1 2 11
Adjustments
Apply Individual
Tolerance Adjustments /Global Percent
Apply Individual
Temperature Correction Adjustments /Global Degree C
Load
Bus Initial Voltage Constant kVA Constant Z Constant I Generic
Total Number of Buses: 10 7.512 3.822 4.024 -0.452 0.000 0.000 0.000 0.000
5.000 0.000
Project: load flow analisis ETAP Page: 4
Location: tasikmalaya 19.0.1C Date: 04-14-2021
Contract: SN:
Engineer: adi sunandar Revision: Base
Study Case: LF
Filename: adi sunandar_tugas2 Config.: Normal
Line/Cable/Busway Length
ID Phase MVA Prim. kV Sec. kV % Z1 X1/R1 + 5% - 5% % Tol. Prim. Sec. %Z Type Angle
Branch Connections
* Bus1 34.500 100.000 0.0 6.421 4.732 0.000 0.000 Bus2 6.421 4.732 133.5 80.5
Bus2 13.800 98.844 -0.8 0.000 0.000 0.000 -0.977 Bus3 1.173 4.104 180.6 27.5
Bus3 13.800 98.784 -0.8 5.000 -1.000 0.000 0.000 Bus2 -1.169 -4.102 180.6 27.4
Bus4 13.800 98.349 -0.9 0.000 0.000 4.222 2.617 Bus3 -4.222 -2.617 211.3 85.0
Bus5 4.160 97.991 -2.3 0.000 0.000 0.643 0.271 Bus3 -1.927 -0.417 279.2 97.7
Bus6 4.160 98.109 -2.2 0.000 0.000 2.935 1.187 Bus7 2.300 0.139 325.9 99.8
Bus7 4.160 97.991 -2.3 0.000 0.000 2.881 0.000 Bus6 -2.297 -0.135 325.9 99.8
Bus8 0.480 97.707 -2.6 0.000 0.000 0.304 0.115 Bus5 -0.292 -0.117 387.0 92.8
Bus9 4.160 97.975 -2.3 0.000 0.000 0.000 0.000 Bus7 -0.408 -0.163 62.2 92.9
Bus10 0.480 97.707 -2.6 0.000 0.000 0.395 0.162 Bus9 -0.408 -0.160 539.4 93.1
* Indicates operating load of a bus exceeds the bus critical limit (100.0% of the Continuous Ampere rating).
# Indicates operating load of a bus exceeds the bus marginal limit (95.0% of the Continuous Ampere rating).
Project: load flow analisis ETAP Page: 10
Location: tasikmalaya 19.0.1C Date: 04-14-2021
Contract: SN:
Engineer: adi sunandar Revision: Base
Study Case: LF
Filename: adi sunandar_tugas2 Config.: Normal
Transformer
CKT / Branch Busway / Cable & Reactor
Loading (input) Loading (output)
Ampacity Loading Capability
ID Type (Amp) Amp % (MVA) MVA % MVA %
Vd
From-To Bus Flow To-From Bus Flow Losses % Bus Voltage
% Drop
Branch ID MW Mvar MW Mvar kW kvar From To in Vmag
Cable1 1.173 4.104 -1.169 -4.102 3.6 1.7 98.8 98.8 0.06
Cable2 2.300 0.139 -2.297 -0.135 2.6 3.8 98.1 98.0 0.12
Cable3 0.408 0.163 -0.408 -0.163 0.1 0.0 98.0 98.0 0.02
40.2 358.0
* This Transmission Line includes Series Capacitor.
Project: load flow analisis ETAP Page: 12
Location: tasikmalaya 19.0.1C Date: 04-14-2021
Contract: SN:
Engineer: adi sunandar Revision: Base
Study Case: LF
Filename: adi sunandar_tugas2 Config.: Normal
% Alert Settings
Critical Marginal
Loading
Bus 100.0 95.0
Cable / Busway 100.0 95.0
Reactor 100.0 95.0
Line 100.0 95.0
Transformer 100.0 95.0
Panel 100.0 95.0
Protective Device 100.0 95.0
Generator 100.0 95.0
Inverter/Charger 100.0 95.0
Bus Voltage
OverVoltage 105.0 102.0
UnderVoltage 95.0 98.0
Generator Excitation
OverExcited (Q Max.) 100.0 95.0
UnderExcited (Q Min.) 100.0
Critical Report
Marginal Report
MW Mvar MVA % PF
Number of Iterations: 5