ETAP
Project: SLD TRAFO CANDIREJO Page: 4
12.6.0H
Location: BERBAH, YOGYAKARTA Date: 06-06-2021
Contract: SN:
Engineer: SOFIA MAILAL IKHSANI Revision: Base
Study Case: LF
Filename: SLD CANDIREJO SOFIA Config.: Normal
Line/Cable Length
ID Phase MVA Prim. kV Sec. kV % Z1 X1/R1 + 5% - 5% % Tol. Prim. Sec. %Z Type Angle
BnD S3-4/31 3-Phase 0.050 20.000 0.231 4.00 1.50 0 0 0 0 0 4.0000 Dyn 0.000
TRAFO GJN19 3-Phase 60.000 150.000 20.000 12.50 45.00 0 0 0 0 0 12.5000 Dyn 0.000
ETAP
Project: SLD TRAFO CANDIREJO Page: 6
12.6.0H
Location: BERBAH, YOGYAKARTA Date: 06-06-2021
Contract: SN:
Engineer: SOFIA MAILAL IKHSANI Revision: Base
Study Case: LF
Filename: SLD CANDIREJO SOFIA Config.: Normal
Branch Connections
* Bus1 150.000 100.000 0.0 0.064 0.005 0 0 Bus2 0.064 0.005 0.2 99.7
Bus5 0.231 89.874 -3.0 0 0 0.007 0.000 Bus4 -0.007 0.000 20.8 100.0
Bus8 0.231 88.600 -3.4 0 0 0.004 0.000 Bus7 -0.004 0.000 12.6 100.0
Bus12 0.231 83.496 -3.9 0 0 0.008 0.000 Bus9 -0.008 0.000 23.9 100.0
Bus15 0.231 79.176 -4.4 0 0 0.013 0.000 Bus13 -0.013 0.000 40.5 100.0
Bus16 0.231 83.184 -4.4 0 0 0.002 0.000 Bus46 -0.002 0.000 5.4 100.0
Bus19 0.231 81.953 -4.7 0 0 0.001 0.000 Bus32 -0.001 0.000 3.6 100.0
Bus22 0.231 78.282 -5.0 0 0 0.006 0.000 Bus21 -0.006 0.000 20.1 100.0
Bus28 0.231 75.875 -5.1 0 0 0.010 0.000 Bus18 -0.010 0.000 33.4 100.0
* Indicates operating load of a bus exceeds the bus critical limit ( 100.0% of the Continuous Ampere rating).
# Indicates operating load of a bus exceeds the bus marginal limit ( 95.0% of the Continuous Ampere rating).
ETAP
Project: SLD TRAFO CANDIREJO Page: 10
12.6.0H
Location: BERBAH, YOGYAKARTA Date: 06-06-2021
Contract: SN:
Engineer: SOFIA MAILAL IKHSANI Revision: Base
Study Case: LF
Filename: SLD CANDIREJO SOFIA Config.: Normal
Transformer
CKT / Branch Cable & Reactor
Ampacity Loading Capability Loading (input) Loading (output)
Vd
CKT / Branch From-To Bus Flow To-From Bus Flow Losses % Bus Voltage
% Drop
ID MW Mvar MW Mvar kW kvar From To in Vmag
TRAFO GJN19 0.064 0.005 -0.064 -0.005 0.0 0.0 100.0 100.0 0.00
GJN19 0.064 0.005 -0.064 -0.005 0.0 0.0 100.0 100.0 0.00
S3-4/32 0.062 0.002 -0.060 -0.001 2.3 0.6 96.9 93.3 3.65
BnD S3-4/31 -0.062 -0.002 0.064 0.005 1.8 2.7 96.9 100.0 3.07
S3-4/32A 0.008 0.000 -0.007 0.000 0.3 0.0 93.3 89.9 3.40
S3-4/33 0.052 0.001 -0.050 -0.001 1.6 0.4 93.3 90.3 2.94
S3-4/33A 0.005 0.000 -0.004 0.000 0.1 0.0 90.3 88.6 1.73
S3-4/34 0.046 0.001 -0.044 -0.001 1.5 0.4 90.3 87.4 2.93
S3-4/34A 0.008 0.000 -0.008 0.000 0.4 0.0 87.4 83.5 3.90
S3-4/35 0.036 0.001 -0.035 0.000 0.9 0.2 87.4 85.1 2.25
S3-4/35A 0.014 0.000 -0.013 0.000 1.0 0.0 85.1 79.2 5.97
S3-4/36 0.021 0.000 -0.021 0.000 0.3 0.1 85.1 83.9 1.29
S3-4/36A -0.002 0.000 0.002 0.000 0.0 0.0 83.2 83.9 0.67
S3-4/38 -0.017 0.000 0.018 0.000 0.3 0.1 81.3 82.5 1.21
S3-4/38A 0.011 0.000 -0.010 0.000 0.7 0.0 81.3 75.9 5.46
S3-4/39 0.007 0.000 -0.007 0.000 0.0 0.0 81.3 80.9 0.42
S3-4/37A -0.001 0.000 0.001 0.000 0.0 0.0 82.0 82.5 0.59
S3-4/39A 0.006 0.000 -0.006 0.000 0.2 0.0 80.9 78.3 2.63
S3-4/37 -0.019 0.000 0.019 0.000 0.3 0.1 82.5 83.9 1.32
11.8 4.8
ETAP
Project: SLD TRAFO CANDIREJO Page: 12
12.6.0H
Location: BERBAH, YOGYAKARTA Date: 06-06-2021
Contract: SN:
Engineer: SOFIA MAILAL IKHSANI Revision: Base
Study Case: LF
Filename: SLD CANDIREJO SOFIA Config.: Normal
% Alert Settings
Critical Marginal
Loading
Bus 100.0 95.0
Bus Voltage
OverVoltage 105.0 102.0
Generator Excitation
OverExcited (Q Max.) 100.0 95.0
Critical Report
Critical Report
Marginal Report
MW Mvar MVA % PF
Number of Iterations: 2