System Frequency:
60.00 Hz
Unit System:
English
Project Filename:
RANDI SETIAWAN
Output Filename:
C:\ETAP 1260\RANDI SETIAWAN\Untitled.lfr
ETAP Page: 2
Project: LOAD FLOW ANALISIS
Adjustments
Apply Individual
Tolerance Adjustments /Global Percent
Transformer Impedance:
Yes
Individual
Reactor Impedance:
Yes
Individual
Overload Heater Resistance:
No
Transmission Line Length:
No
Cable Length:
No
Apply Individual
Temperature Correction Adjustments /Global Degree C
Load
Total Number of Buses: 2 0.000 0.000 36.000 17.436 0.000 0.000 0.000 0.000
ID kV Type Sub-sys % PF
% Mag. Angle MW Mvar Max Min
0.000 0.000
ETAP Page: 4
Project: LOAD FLOW ANALISIS
Branch Connections
% Mag.
ID kV Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap
Bus2 20.000 97.053 -3.1 0 0 33.910 16.423 Bus1 -33.910 -16.423 1120.7 90.0
* Indicates a voltage regulated bus (voltage controlled or swing type machine connected to
it)# Indicates a bus with a load mismatch of more than 0.1 MVA
ETAP Page: 7
Project: LOAD FLOW ANALISIS
* Indicates operating load of a bus exceeds the bus critical limit ( 100.0% of the Continuous Ampere rating).
# Indicates operating load of a bus exceeds the bus marginal limit ( 95.0% of the Continuous Ampere rating).
ETAP Page: 8
Project: LOAD FLOW ANALISIS
Transformer
Vd
CKT / Branch From-To Bus Flow To-From Bus Flow Losses % Bus Voltage
% Drop
ID MW Mvar MW Mvar kW kvar From To in Vmag
Trafo 1 33.989 18.758 -33.910 -16.423 79.1 2334.7 100.0 97.1 2.95
79.1 2334.7
ETAP Page: 10
Project: LOAD FLOW ANALISIS
% Alert Settings
Critical Marginal
Loading
Bus 100.0 95.0
Bus Voltage
OverVoltage 105.0 102.0
Generator Excitation
OverExcited (Q Max.) 100.0 95.0
Marginal Report
MW Mvar MVA % PF
ETAP
Project: LOAD FLOW ANALISIS
12.6.0H
Location: VIKTOR UNPAM Date: 12-03-2022
System Frequency:
60.00 Hz
Unit System:
English
Project Filename:
RANDI SETIAWAN
Output Filename:
C:\ETAP 1260\RANDI SETIAWAN\Untitled.lfr
ETAP Page: 2
Project: LOAD FLOW ANALISIS
Adjustments
Apply Individual
Tolerance Adjustments /Global Percent
Transformer Impedance:
Yes
Individual
Reactor Impedance:
Yes
Individual
Overload Heater Resistance:
No
Transmission Line Length:
No
Cable Length:
No
Apply Individual
Temperature Correction Adjustments /Global Degree C
Load
Total Number of Buses: 2 0.000 0.000 9.000 4.359 0.000 0.000 0.000 0.000
ID kV Type Sub-sys % PF
% Mag. Angle MW Mvar Max Min
0.000 0.000
ETAP Page: 4
Project: LOAD FLOW ANALISIS
Branch Connections
% Mag.
ID kV Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap
Bus2 20.000 99.273 -0.8 0 0 8.870 4.296 Bus1 -8.870 -4.296 286.6 90.0
* Indicates a voltage regulated bus (voltage controlled or swing type machine connected to
it)# Indicates a bus with a load mismatch of more than 0.1 MVA
ETAP Page: 7
Project: LOAD FLOW ANALISIS
* Indicates operating load of a bus exceeds the bus critical limit ( 100.0% of the Continuous Ampere rating).
# Indicates operating load of a bus exceeds the bus marginal limit ( 95.0% of the Continuous Ampere rating).
ETAP Page: 8
Project: LOAD FLOW ANALISIS
Transformer
Vd
CKT / Branch From-To Bus Flow To-From Bus Flow Losses % Bus Voltage
% Drop
ID MW Mvar MW Mvar kW kvar From To in Vmag
Trafo 2 8.875 4.448 -8.870 -4.296 5.2 152.7 100.0 99.3 0.73
5.2 152.7
ETAP Page: 10
Project: LOAD FLOW ANALISIS
% Alert Settings
Critical Marginal
Loading
Bus 100.0 95.0
Bus Voltage
OverVoltage 105.0 102.0
Generator Excitation
OverExcited (Q Max.) 100.0 95.0
MW Mvar MVA % PF
System Frequency:
60.00 Hz
Unit System:
English
Project Filename:
RANDI SETIAWAN
Output Filename:
C:\ETAP 1260\RANDI SETIAWAN\Untitled.lfr
ETAP Page: 2
Project: LOAD FLOW ANALISIS
Adjustments
Apply Individual
Tolerance Adjustments /Global Percent
Transformer Impedance:
Yes
Individual
Reactor Impedance:
Yes
Individual
Overload Heater Resistance:
No
Transmission Line Length:
No
Cable Length:
No
Apply Individual
Temperature Correction Adjustments /Global Degree C
Load
Total Number of Buses: 2 0.000 0.000 9.000 4.359 0.000 0.000 0.000 0.000
ID kV Type Sub-sys % PF
% Mag. Angle MW Mvar Max Min
0.000 0.000
ETAP Page: 4
Project: LOAD FLOW ANALISIS
Branch Connections
% Mag.
ID kV Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap
Bus2 20.000 98.170 -1.9 0 0 8.674 4.201 Bus1 -8.674 -4.201 283.4 90.0
* Indicates a voltage regulated bus (voltage controlled or swing type machine connected to
it)# Indicates a bus with a load mismatch of more than 0.1 MVA
ETAP Page: 7
Project: LOAD FLOW ANALISIS
* Indicates operating load of a bus exceeds the bus critical limit ( 100.0% of the Continuous Ampere rating).
# Indicates operating load of a bus exceeds the bus marginal limit ( 95.0% of the Continuous Ampere rating).
ETAP Page: 8
Project: LOAD FLOW ANALISIS
Transformer
Vd
CKT / Branch From-To Bus Flow To-From Bus Flow Losses % Bus Voltage
% Drop
ID MW Mvar MW Mvar kW kvar From To in Vmag
Trafo 3 8.686 4.574 -8.674 -4.201 12.7 373.2 100.0 98.2 1.83
12.7 373.2
ETAP Page: 10
Project: LOAD FLOW ANALISIS
% Alert Settings
Critical Marginal
Loading
Bus 100.0 95.0
Bus Voltage
OverVoltage 105.0 102.0
Generator Excitation
OverExcited (Q Max.) 100.0 95.0
MW Mvar MVA % PF
Number of Iterations: 1