Project: ETAP Page: 1

Location: 19.0.1C Date: 11-18-2021

Contract: SN:

Engineer: Revision: Base


Study Case: LF
Filename: load Config.: Normal

Electrical Transient Analyzer Program

Load Flow Analysis

Loading Category (2): Normal

Generation Category (2): Normal

Load Diversity Factor: None

Swing V-Control Load Total


Number of Buses: 1 1 19 21

Line/Cable/
XFMR2 XFMR3 Reactor Busway Impedance Tie PD Total
Number of Branches: 2 0 0 18 0 1 21

Method of Solution: Newton-Raphson Method

Maximum No. of Iteration: 9999

Precision of Solution: 0.1000000

System Frequency: 60.00 Hz

Unit System: English

Project Filename: load

Output Filename: D:\WYNDELL\FILES\PSA\FINAL DIAGRAM PRAMIS\lab1 diagram.lfr


Project: ETAP Page: 2

Location: 19.0.1C Date: 11-18-2021

Contract: SN:

Engineer: Revision: Base


Study Case: LF
Filename: load Config.: Normal

Adjustments

Apply Individual
Tolerance Adjustments /Global Percent

Transformer Impedance: Yes Individual

Reactor Impedance: Yes Individual

Overload Heater Resistance: No

Transmission Line Length: No

Cable / Busway Length: Yes Individual

Apply Individual
Temperature Correction Adjustments /Global Degree C

Transmission Line Resistance: Yes Individual

Cable / Busway Resistance: Yes Individual


Project: ETAP Page: 3

Location: 19.0.1C Date: 11-18-2021

Contract: SN:

Engineer: Revision: Base


Study Case: LF
Filename: load Config.: Normal

Bus Input Data

Load

Bus Initial Voltage Constant kVA Constant Z Constant I Generic

ID kV Sub-sys % Mag. Ang. MW Mvar MW Mvar MW Mvar MW Mvar

Bus_1 13.200 1 100.0 0.0

Bus2 13.200 1 100.0 0.0

Bus_2 0.240 1 100.0 0.0

Bus3 0.240 1 100.0 0.0 0.003 0.002

Bus_3 0.240 1 100.0 0.0

Bus4 0.240 1 100.0 0.0 0.027 0.011

Bus5 13.200 1 100.0 0.0

Bus6 0.240 1 100.0 0.0 0.027 0.011

Bus7 0.240 1 100.0 0.0

Bus8 0.240 1 100.0 0.0 0.004 0.004 0.001 0.001

Bus9 0.240 1 100.0 0.0 0.004 0.004 0.001 0.001

Bus14 0.240 1 100.0 0.0 0.001 0.001

Bus15 0.240 1 100.0 0.0 0.001 0.001

Bus16 0.240 1 100.0 0.0 0.002 0.001

Bus17 0.240 1 100.0 0.0 0.001 0.001

Bus18 0.240 1 100.0 0.0 0.002 0.001

Bus20 0.240 1 100.0 0.0

Bus21 0.240 1 100.0 0.0 0.001 0.001

Bus22 0.240 1 100.0 0.0

T1 FeederBus 0.240 1 100.0 0.0

T2 FeederBus 0.240 1 100.0 0.0

Total Number of Buses: 21 0.068 0.033 0.011 0.009 0.000 0.000 0.000 0.000

Generation Bus Voltage Generation Mvar Limits

ID kV Type Sub-sys % Mag. Angle MW Mvar % PF Max Min

Bus_1 13.200 Swing 1 100.0 0.0

Bus7 0.240 Voltage Control 1 100.0 0.0 0.001 3.777 0.000

0.001 0.000
Project: ETAP Page: 4

Location: 19.0.1C Date: 11-18-2021

Contract: SN:

Engineer: Revision: Base


Study Case: LF
Filename: load Config.: Normal

Line/Cable/Busway Input Data

ohms or siemens/1000 ft per Conductor (Cable) or per Phase (Line/Busway)

Line/Cable/Busway Length

ID Library Size Adj. (ft) % Tol. #/Phase T (°C) R X Y

Chiller Cable1 0.6MCUN3 4/0 164.0 0.0 1 75 0.064000 0.038100

Chiller Cable2 0.6MCUN3 4/0 164.0 0.0 1 75 0.064000 0.038100

Feeder Cable1 0.6NCUN1 4/0 246.1 0.0 1 75 0.062000 0.040800

Feeder Cable2 0.6NCUN1 4/0 246.1 0.0 1 75 0.062000 0.040800

Feeder Cable3 0.6NCUN1 4/0 246.1 0.0 1 75 0.062000 0.040800

Feeder Cable4 0.6MCUN3 4/0 492.1 0.0 1 75 0.064000 0.038100

Feeder Cable5 0.6NCUN1 4/0 492.1 0.0 1 75 0.062000 0.040800

Feeder Cable6 0.6NCUN1 4/0 82.0 0.0 1 75 0.062000 0.040800

Feeder Cable7 0.6NCUN1 4/0 82.0 0.0 1 75 0.062000 0.040800

Feeder Cable8 0.6NCUN1 4/0 82.0 0.0 1 75 0.062000 0.040800

Feeder Cable9 0.6NCUN1 4/0 82.0 0.0 1 75 0.062000 0.040800

Feeder Cable10 0.6NCUN1 4/0 82.0 0.0 1 75 0.062000 0.040800

Feeder Cable11 0.6NCUN1 4/0 82.0 0.0 1 75 0.062000 0.040800

Feeder Cable12 0.6NCUN1 4/0 82.0 0.0 1 75 0.062000 0.040800

Feeder Cable13 0.6NCUN1 4/0 82.0 0.0 1 75 0.062000 0.040800

Gen. Cable 0.6NCUN3 4/0 65.6 0.0 1 75 0.063300 0.033200

T_1 0.6NCUN3 4/0 65.6 0.0 1 75 0.063300 0.033200

T_2 0.6NCUN3 4/0 65.6 0.0 1 75 0.063300 0.033200

Line / Cable / Busway resistances are listed at the specified temperatures.


Project: ETAP Page: 5

Location: 19.0.1C Date: 11-18-2021

Contract: SN:

Engineer: Revision: Base


Study Case: LF
Filename: load Config.: Normal

2-Winding Transformer Input Data

Transformer Rating Z Variation % Tap Setting Adjusted Phase Shift

ID Phase MVA Prim. kV Sec. kV % Z1 X1/R1 + 5% - 5% % Tol. Prim. Sec. %Z Type Angle

T1 3-Phase 3.000 13.200 0.240 5.75 2.47 0 0 0 0 0 5.7500 Dyn 0.000


T2 3-Phase 3.000 13.200 0.240 5.75 2.47 0 0 0 0 0 5.7500 Dyn 0.000
Project: ETAP Page: 6

Location: 19.0.1C Date: 11-18-2021

Contract: SN:

Engineer: Revision: Base


Study Case: LF
Filename: load Config.: Normal

Branch Connections

CKT/Branch Connected Bus ID % Impedance, Pos. Seq., 100 MVA Base


ID Type From Bus To Bus R X Z Y

T1 2W XFMR Bus2 T1 FeederBus 71.93 177.66 191.67

T2 2W XFMR Bus5 T2 FeederBus 71.93 177.66 191.67

Chiller Cable1 Cable T1 FeederBus Bus4 1822.69 1085.07 2121.22

Chiller Cable2 Cable T1 FeederBus Bus6 1822.69 1085.07 2121.22

Feeder Cable1 Cable T2 FeederBus Bus3 2648.60 1742.95 3170.63

Feeder Cable2 Cable T2 FeederBus Bus8 2648.60 1742.95 3170.63

Feeder Cable3 Cable T2 FeederBus Bus9 2648.60 1742.95 3170.63

Feeder Cable4 Cable T2 FeederBus Bus_2 5468.07 3255.21 6363.66

Feeder Cable5 Cable T2 FeederBus Bus_3 5297.19 3485.89 6341.27

Feeder Cable6 Cable Bus_2 Bus14 882.86 580.98 1056.88

Feeder Cable7 Cable Bus_2 Bus16 882.86 580.98 1056.88

Feeder Cable8 Cable Bus_2 Bus15 882.86 580.98 1056.88

Feeder Cable9 Cable Bus_2 Bus17 882.86 580.98 1056.88

Feeder Cable10 Cable Bus_2 Bus18 882.86 580.98 1056.88

Feeder Cable11 Cable Bus_3 Bus20 882.86 580.98 1056.88

Feeder Cable12 Cable Bus_3 Bus22 882.86 580.98 1056.88

Feeder Cable13 Cable Bus_3 Bus21 882.86 580.98 1056.88

Gen. Cable Cable Bus7 T2 FeederBus 721.10 378.21 814.27

T_1 Cable Bus_1 Bus2 0.24 0.13 0.27

T_2 Cable Bus_1 Bus5 0.24 0.13 0.27

Tie Breaker Tie Breakr T1 FeederBus T2 FeederBus


Project: ETAP Page: 7

Location: 19.0.1C Date: 11-18-2021

Contract: SN:

Engineer: Revision: Base


Study Case: LF
Filename: load Config.: Normal

LOAD FLOW REPORT

Bus Voltage Generation Load Load Flow XFMR


ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap

* Bus_1 13.200 100.000 0.0 0.078 0.030 0.000 0.000 Bus2 0.039 0.015 1.8 93.5

Bus5 0.039 0.015 1.8 93.5

Bus2 13.200 100.000 0.0 0.000 0.000 0.000 0.000 Bus_1 -0.039 -0.015 1.8 93.5

T1 FeederBus 0.039 0.015 1.8 93.5

Bus_2 0.240 99.387 0.0 0.000 0.000 0.000 0.000 T2 FeederBus -0.007 -0.005 21.3 79.5

Bus14 0.001 0.001 4.3 80.0

Bus16 0.002 0.001 5.4 76.0

Bus15 0.001 0.001 3.2 80.0

Bus17 0.001 0.001 3.9 80.0

Bus18 0.002 0.001 4.5 82.0

Bus3 0.240 99.804 0.0 0.000 0.000 0.003 0.003 T2 FeederBus -0.003 -0.003 10.8 75.0

Bus_3 0.240 99.689 0.0 0.000 0.000 0.000 0.000 T2 FeederBus -0.003 -0.002 9.7 85.7

Bus20 0.001 0.000 2.7 89.9

Bus22 0.001 0.000 2.7 89.9

Bus21 0.001 0.001 4.5 80.0

Bus4 0.240 99.323 -0.1 0.000 0.000 0.027 0.011 T1 FeederBus -0.027 -0.011 71.4 92.4

Bus5 13.200 100.000 0.0 0.000 0.000 0.000 0.000 Bus_1 -0.039 -0.015 1.8 93.5

T2 FeederBus 0.039 0.015 1.8 93.5

Bus6 0.240 99.323 -0.1 0.000 0.000 0.027 0.011 T1 FeederBus -0.027 -0.011 71.4 92.4

* Bus7 0.240 100.000 -0.1 0.001 0.013 0.000 0.000 T2 FeederBus 0.001 0.013 30.2 8.0

Bus8 0.240 99.728 0.0 0.000 0.000 0.005 0.004 T2 FeederBus -0.005 -0.004 16.6 76.0

Bus9 0.240 99.728 0.0 0.000 0.000 0.005 0.004 T2 FeederBus -0.005 -0.004 16.6 76.0

Bus14 0.240 99.368 0.0 0.000 0.000 0.001 0.001 Bus_2 -0.001 -0.001 4.3 80.0

Bus15 0.240 99.373 0.0 0.000 0.000 0.001 0.001 Bus_2 -0.001 -0.001 3.2 80.0

Bus16 0.240 99.363 0.0 0.000 0.000 0.002 0.001 Bus_2 -0.002 -0.001 5.4 76.0

Bus17 0.240 99.370 0.0 0.000 0.000 0.001 0.001 Bus_2 -0.001 -0.001 3.9 80.0

Bus18 0.240 99.367 0.0 0.000 0.000 0.002 0.001 Bus_2 -0.002 -0.001 4.5 82.0

Bus20 0.240 99.677 0.0 0.000 0.000 0.001 0.000 Bus_3 -0.001 0.000 2.7 89.9

Bus21 0.240 99.669 0.0 0.000 0.000 0.001 0.001 Bus_3 -0.001 -0.001 4.5 80.0

Bus22 0.240 99.677 0.0 0.000 0.000 0.001 0.000 Bus_3 -0.001 0.000 2.7 89.9

T1 FeederBus 0.240 99.945 0.0 0.000 0.000 0.000 0.000 Bus4 0.027 0.011 71.4 92.4
Project: ETAP Page: 8

Location: 19.0.1C Date: 11-18-2021

Contract: SN:

Engineer: Revision: Base


Study Case: LF
Filename: load Config.: Normal

Bus Voltage Generation Load Load Flow XFMR


ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap

Bus6 0.027 0.011 71.4 92.4

Bus2 -0.039 -0.015 100.6 93.5

T2 FeederBus -0.016 -0.008 42.3 89.3

T2 FeederBus 0.240 99.945 0.0 0.000 0.000 0.000 0.000 Bus3 0.003 0.003 10.8 75.0

Bus8 0.005 0.004 16.6 76.0

Bus9 0.005 0.004 16.6 76.0

Bus_2 0.007 0.005 21.3 79.5

Bus_3 0.003 0.002 9.7 85.7

Bus7 -0.001 -0.013 30.2 7.9

Bus5 -0.039 -0.015 100.6 93.5

T1 FeederBus 0.016 0.008 42.3 89.3


* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA
Project: ETAP Page: 9

Location: 19.0.1C Date: 11-18-2021

Contract: SN:

Engineer: Revision: Base


Study Case: LF
Filename: load Config.: Normal

Bus Loading Summary Report

Directly Connected Load Total Bus Load

Bus Constant kVA Constant Z Constant I Generic


Percent
ID kV Rated Amp MW Mvar MW Mvar MW Mvar MW Mvar MVA % PF Amp Loading

Bus_1 13.200 0.084 93.5 3.7


Bus2 13.200 0.042 93.5 1.8
Bus_2 0.240 0.000 0.000 0.009 79.5 21.3
Bus3 0.240 0.003 0.002 0.001 0.001 0.004 75.0 10.8
Bus_3 0.240 0.004 85.7 9.7
Bus4 0.240 0.027 0.011 0.029 92.4 71.4
Bus5 13.200 0.042 93.5 1.8
Bus6 0.240 0.027 0.011 0.029 92.4 71.4
Bus7 0.240 0.013 8.0 30.2
Bus8 0.240 0.004 0.004 0.001 0.001 0.007 76.0 16.6
Bus9 0.240 0.004 0.004 0.001 0.001 0.007 76.0 16.6
Bus14 0.240 0.000 0.001 0.001 0.002 80.0 4.3
Bus15 0.240 0.000 0.001 0.001 0.001 80.0 3.2
Bus16 0.240 0.000 0.002 0.001 0.002 76.0 5.4
Bus17 0.240 0.000 0.001 0.001 0.002 80.0 3.9
Bus18 0.240 0.000 0.002 0.001 0.002 82.0 4.5
Bus20 0.240 0.001 0.000 0.001 89.9 2.7
Bus21 0.240 0.001 0.001 0.002 80.0 4.5
Bus22 0.240 0.001 0.000 0.001 89.9 2.7
T1 FeederBus 0.240 0.059 92.4 142.7
T2 FeederBus 0.240 0.048 82.6 116.7

* Indicates operating load of a bus exceeds the bus critical limit ( 100.0% of the Continuous Ampere rating).
# Indicates operating load of a bus exceeds the bus marginal limit (95.0% of the Continuous Ampere rating).
Project: ETAP Page: 10

Location: 19.0.1C Date: 11-18-2021

Contract: SN:

Engineer: Revision: Base


Study Case: LF
Filename: load Config.: Normal

Branch Loading Summary Report

Transformer
CKT / Branch Busway / Cable & Reactor
Loading (input) Loading (output)
Ampacity Loading Capability
ID Type (Amp) Amp % (MVA) MVA % MVA %

Feeder Cable7 Cable 191.30 5.38 2.81

Feeder Cable8 Cable 191.30 3.23 1.69

Feeder Cable9 Cable 191.30 3.95 2.06

Feeder Cable10 Cable 191.30 4.45 2.33

Feeder Cable11 Cable 191.30 2.66 1.39

Feeder Cable12 Cable 191.30 2.66 1.39

Feeder Cable13 Cable 191.30 4.46 2.33

T_1 Cable 219.49 1.83 0.83

T_2 Cable 219.49 1.83 0.83

T1 Transformer 4.688 0.042 0.9 0.042 0.9

T2 Transformer 4.688 0.042 0.9 0.042 0.9

* Indicates a branch with operating load exceeding the branch capability.


Project: ETAP Page: 11

Location: 19.0.1C Date: 11-18-2021

Contract: SN:

Engineer: Revision: Base


Study Case: LF
Filename: load Config.: Normal

Branch Losses Summary Report

Vd
From-To Bus Flow To-From Bus Flow Losses % Bus Voltage
% Drop

Branch ID MW Mvar MW Mvar kW kvar From To in Vmag

Chiller Cable1 -0.027 -0.011 0.027 0.011 0.2 0.1 99.3 99.9 0.62

Chiller Cable2 -0.027 -0.011 0.027 0.011 0.2 0.1 99.3 99.9 0.62

Feeder Cable1 -0.003 -0.003 0.003 0.003 0.0 0.0 99.8 99.9 0.14

Feeder Cable10 0.002 0.001 -0.002 -0.001 0.0 0.0 99.4 99.4 0.02

Feeder Cable11 0.001 0.000 -0.001 0.000 0.0 0.0 99.7 99.7 0.01

Feeder Cable12 0.001 0.000 -0.001 0.000 0.0 0.0 99.7 99.7 0.01

Feeder Cable13 0.001 0.001 -0.001 -0.001 0.0 0.0 99.7 99.7 0.02

Feeder Cable2 -0.005 -0.004 0.005 0.004 0.0 0.0 99.7 99.9 0.22

Feeder Cable3 -0.005 -0.004 0.005 0.004 0.0 0.0 99.7 99.9 0.22

Feeder Cable4 -0.007 -0.005 0.007 0.005 0.0 0.0 99.4 99.9 0.56

Feeder Cable5 -0.003 -0.002 0.003 0.002 0.0 0.0 99.7 99.9 0.26

Feeder Cable6 0.001 0.001 -0.001 -0.001 0.0 0.0 99.4 99.4 0.02

Feeder Cable7 0.002 0.001 -0.002 -0.001 0.0 0.0 99.4 99.4 0.02

Feeder Cable8 0.001 0.001 -0.001 -0.001 0.0 0.0 99.4 99.4 0.01

Feeder Cable9 0.001 0.001 -0.001 -0.001 0.0 0.0 99.4 99.4 0.02

Gen. Cable 0.001 0.013 -0.001 -0.013 0.0 0.0 100.0 99.9 0.05

T_1 0.039 0.015 -0.039 -0.015 0.0 0.0 100.0 100.0 0.00

T_2 0.039 0.015 -0.039 -0.015 0.0 0.0 100.0 100.0 0.00

T1 0.039 0.015 -0.039 -0.015 0.0 0.0 100.0 99.9 0.05

T2 0.039 0.015 -0.039 -0.015 0.0 0.0 100.0 99.9 0.05

0.4 0.3

* This Transmission Line includes Series Capacitor.


Project: ETAP Page: 12

Location: 19.0.1C Date: 11-18-2021

Contract: SN:

Engineer: Revision: Base


Study Case: LF
Filename: load Config.: Normal

Alert Summary Report

% Alert Settings
Critical Marginal
Loading
Bus 100.0 95.0

Cable / Busway 100.0 95.0

Reactor 100.0 95.0

Line 100.0 95.0

Transformer 100.0 95.0

Panel 100.0 95.0

Protective Device 100.0 95.0

Generator 100.0 95.0

Inverter/Charger 100.0 95.0

Bus Voltage
OverVoltage 105.0 102.0

UnderVoltage 95.0 98.0

Generator Excitation
OverExcited (Q Max.) 100.0 95.0

UnderExcited (Q Min.) 100.0


Project: ETAP Page: 13

Location: 19.0.1C Date: 11-18-2021

Contract: SN:

Engineer: Revision: Base


Study Case: LF
Filename: load Config.: Normal

SUMMARY OF TOTAL GENERATION , LOADING & DEMAND

MW Mvar MVA % PF

Source (Swing Buses): 0.078 0.030 0.084 93.51 Lagging

Source (Non-Swing Buses): 0.001 0.013 0.013 7.96 Lagging

Total Demand: 0.079 0.042 0.090 88.27 Lagging

Total Motor Load: 0.068 0.033 0.075 89.83 Lagging

Total Static Load: 0.011 0.009 0.014 78.61 Lagging

Total Constant I Load: 0.000 0.000 0.000

Total Generic Load: 0.000 0.000 0.000

Apparent Losses: 0.000 0.000

System Mismatch: 0.000 0.000

Number of Iterations: 1