REHABILITATION OF YANBU SOUTH

TERMINAL PROJECTS
BI # 10-00567

Material Receiving, Handling, Storage and


preservation Inspection of Electrical &
Instrumentation Cables

1
2 Contents

 Types of Cables
 Electrical Cables
 Metallic I&C Cable
 Documents Required for Material Receiving Inspection
 Cable Storage, Handling and Preservation
 General Requirement for LV Power Cable
 General Requirement for MV Power Cable
 General Requirement for HV Power Cable
 General Requirement for Metallic Instrumentation and Control Cable
3 Types of Cables

 Electrical Cables
 Low Voltage Power Cable and Building Wire (up to 1 kV).
 Medium Voltage Cable and Conductors (1.001 kV to 35 kV).
 High Voltage Cable (35.001 kV to 69 kV).
 Very High Voltage Cable (above 69 kV).
 Metallic Instrumentation and Control Cable
 I&C Copper Cable - Unshielded Single Twisted Pair / Triad, Multi pair / triad.
 I&C Copper Cable -Shielded Single Twisted Pair / Triad, Multi pair / triad.
 I &C Copper Cable -Thermocouple Extension Cable.
 Instrument Cable - Coaxial and Twin axial Data Cable.
4 Documents Required for Material
Receiving Inspection
 SATIP (Saudi Aramco Typical Inspection Plan).
 SAIC (Saudi Aramco Inspection Checklist).
 SATR (Saudi Aramco Test Report).
 Purchase Order.
 Delivery Note.
 Vendor Approval Letter.
 Material Test Certificate.
 Material Technical Approval Letter.
 Material Requisition.
 IFC Drawings.
5 References for Material Receiving
Inspection
 SCHEDULE-Q
 SATIP (Saudi Aramco Typical Inspection Plan)
 SATIP-P-104-01 for LV Power Cable and Building Wire (up to 1 kV).
 SATIP-P-104-02 for MV Cable and Conductors (1.001 kV to 35 kV).
 SATIP-P-104-10 for HV Cable (35.001 kV to 69 kV).
 SATIP-P-104-11 for VHV Cable (above 69 kV).
 SATIP-J-902-01 for Metallic I&C Cable
 SAIC (Saudi Aramco Inspection Checklist) and SATR (Saudi Aramco Test Report)
 SAIC-3201, 3202, 3203, 3204, 3205 and SATR-P-3201, 3202 for LV Power Cable.
 SAIC-P-3211, SAIC-P-3212 and SATR-P-3207 for MV Power Cable.
 SAIC-P-3216 and SATR-P-3211 for HV Power Cable.
 SAIC-P-3220 and SATR-P-3215 for VHV Power Cable.
 SAIC-J-6601, SAIC-J-6602, SAIC-J-6603, SAIC-J-6604 and SATR-J-6601 for I&C
Cable.
6 Documents Required for Material
Receiving Inspection
 Purchase Order.
 A commercial document and first official offer issued by a buyer to a seller, indicating types,
quantities, and agreed prices for products or services.
 Delivery Note.
 A document accompanying a shipment of goods that lists the description, and quantity of the
goods delivered.
 Vendor Approval Letter.
 A letter that certifies the supplier is approved by Saudi Aramco.
 Material Test Certificate.
 A document that certifies that the supplied material is according to all applicable standards.
 Material Technical Approval Letter.
 A letter that certifies that supplied material is approved for the specific project.
 Material Requisition:
 A material requisition form lists the items to be picked from inventory and used in the production
process or in the provision of a service to a customer, usually for a specific job.
 IFC Drawings.
Drawings that justifies the quantity and use of received material.
7 Cable Storage, Handling and Preservation

 Handling
 Cable reels shall be checked for damage by store yard personnel prior to
acceptance of shipment, unloading, or handling.
 Manufacturer's special handling instructions shall be followed.
 Cable reels shall be shipped and handled on edges of flanges only (not on flat side of
flanges).
 Storage and Preservation
 Firm dry support shall be provided for storage of cable reels.
 Cable ends shall be sealed (water and dust-proof seals) and firmly secured during
shipping and storage.
 Cable reels shall be stored away from chemicals and petroleum products.
 Cable reels shall be supported off the ground and provided with a weatherproof (i.e.,
rain and dust-tight) cover.
8 General Requirement for LV Power
Cable
 Cable and wire shall be rated 600 V.
 Cable and wire shall have a minimum temperature rating of 90°C dry locations and 75°C for
wet locations.
 Cable and wire for industrial locations shall be stranded (regardless of size).
 Control conductor cross-sectional-area shall be 2.5 mm² (14 AWG), or larger.
 Power conductor cross-sectional-area shall be 4 mm² (12 AWG), or larger.
 Marking - Cable and wire shall be externally marked by the manufacturer to indicate
 Maximum rated voltage
 Type letters for the cable and/or wire.
 Manufacturer’s name, trademark, or other distinctive marking
 M/C Cable - quantity and size
 Cables with a neutral conductor that is smaller than ungrounded
9 General Requirement for MV Power
Cable
 Each phase of multi-conductor cables shall be permanently identified.
 Reels shall be made of steel, or, alternatively, shall be heavy duty wood
reels.
 Substitution of IEC cable with AEIC cable, if IEC cable is specified, and vice
versa, is prohibited.
 The outer sheath (jacket) shall be polyvinyl chloride (PVC), suitable for 90°C
maximum rated conductor temperature.
 Minimum size of MV cable shall be 10mm² (8 AWG).
 Conductor and insulation screening is required for all cables.
 All cables shall have a continuous overall outer nonmetallic sheath (jacket).
10 General Requirement for HV Power
Cable
 Incoming High Voltage Cable shall be visually inspected for damage /
defects occurred during transportation.
 High Voltage Cable shall be in accordance with the Saudi Aramco-
approved project-specific design drawings, diagrams, schedules, lists,
databases, and associated design documents.
 Check that the end cap (seal) of cable are heat-shrinkable.
 Check that the cables are supplied from acceptable manufacturers.
 Wires and cables shall have copper conductors. Aluminum conductors are
permitted to be used in community areas for sizes 25 mm² or larger.
 The sizing of cables rated 69 kV and above shall be per IEC 60287.
11 General Requirement for Metallic
Instrumentation and Control Cable
 Conductor:
 Stranded, circular copper, per ASTM B3, 7 strands minimum; tinned, per ASTM B33, if
primary insulation may corrode unprotected copper.
 Primary Insulation Voltage Rating:
 300 V for Type PLTC and Type ITC Cable
 600 V for Type TC Cable
 Jacket Material:
 Flame retardant PVC, minimum temperature rating 90°C.
 Jacket Color:
 Non-intrinsically safe applications: Manufacturer's standard other than blue.
 Intrinsically safe applications: Blue
 FF Application: Orange