Project: ETAP Page: 1

Location: 20.0.0C Date: 09-03-2024

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: EACP_VATIOTRON_BHP Config.: Normal

Short-Circuit Summary Report

3-Phase Fault Currents

Device Capacity (kA)


Bus Device Making Short-Circuit Current (kA)
ID kV ID Type Peak Ib sym Ib asym Idc I"k ip Ib sym Ib asym Idc Ik
344TGF001 0.400 344TGF001 SwtchBoard 27.580 63.710 8.648

0.400 CB1 CB 220.000 100.000 102.111 27.580 63.710 23.411 28.120 15.578

0.400 CB6 CB 220.000 100.000 102.111 27.580 63.710 23.411 28.120 15.578

0.400 CB2 CB 187.000 85.000 86.794 27.580 63.710 23.411 28.120 15.578

Barra SSAA 0.400 Barra SSAA Bus 26.293 58.970 8.622

0.400 CB350A CB 154.000 35.000 41.337 26.293 58.970 24.318 32.092 20.940

0.400 CB200A CB 187.000 85.000 105.983 26.293 58.970 24.318 32.092 20.940

0.400 CB125A CB 187.000 85.000 105.983 26.293 58.970 24.318 32.092 20.940

0.400 CB100A CB 187.000 85.000 105.983 26.293 58.970 24.318 32.092 20.940

Bus8 0.400 Bus8 Bus 27.853 64.799 8.654

0.400 CBGEN CB 220.000 100.000 102.111 27.853 64.799 23.617 28.991 16.813

Enchufe P&C 7.200 Enchufe P&C Bus 1.284 2.990 0.474

PRIM TR 0.400 PRIM TR Bus 27.311 62.658 8.642

SEC TR 7.200 SEC TR Bus 1.287 3.001 0.474

ip is calculated using method C


Ib does not include decay of non-terminal faulted induction motors
Ik is the maximum steady state fault current
Idc is based on X/R from Method C and Ib as specified above

LV CB duty determined based on ultimate rating.


Total through current is used for device duty.
* Indicates a device with calculated duty exceeding the device capability.
# Indicates a device with calculated duty exceeding the device marginal limit . ( 95 % times device capability)
Project: ETAP Page: 2

Location: 20.0.0C Date: 09-03-2024

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: EACP_VATIOTRON_BHP Config.: Normal

Short-Circuit Summary Report

Device Capacity 3-Phase Short-Circuit Duty Results


Rated Thermal Thermal
Bus ID Device ID Ithr (kA) Tkr (sec.) Energy (MJ) Ith (kA) Tkr (sec.) Energy (MJ)

344TGF001 CB1 100.000 1.00 10000.00 18.464 1.00 340.90

344TGF001 CB6 100.000 1.00 10000.00 18.464 1.00 340.90

344TGF001 CB2 65.000 1.00 4225.00 18.464 1.00 340.90

Bus8 CBGEN 100.000 1.00 10000.00 18.627 1.00 346.96

Ithr = Rated short-time withstand current (Icw for low voltage circuit breaker)
Tkr = Rated short-time
Ith = Thermal equivalent short-time current

* Indicates a device with calculated duty exceeding the device capability.


# Indicates a device with calculated duty exceeding the device marginal limit . ( 95 % times device capability)