T16-6081
Full
Page 2/115
Content
1 Project description.................................................................................................................. 4
1.1 Project general settings................................................................................................................... 4
3 Calculation notes.................................................................................................................. 14
3.1 Source circuits............................................................................................................................... 14
1 Project description
1.1 Project general settings
Installation standard IEC60364
0.2
UPP-FF- 127 108 183 0.85 1 3Ph+N No 0
02
PP-FF- 47.6 40.5 68.7 0.85 1 3Ph+N No 0
0.2
ACP-FF- 120 102 173 0.85 1 3Ph+N No 0
22
NOTICE
RISK OF INACCURATE DATA RESULTS
Make sure that you have provided all the required inputs for the conductor sizing.
It is recommended to refer to the cable manufacturer's catalogue before making
the selection.
Failure to follow these instructions can result in incorrect bill of material and loss
of business.
2.1.5 MV Cable
Name Nbr Designation CSA (mm²) Icc (A) In (A) Un (kV)
MVWD 1 1 NA 1 x 300 Al 26.6 484 24
3 Calculation notes
MV/LV transformer TA 1
Range Trihal
Technology Resin
Rated power 1000 kVA
ukrT 6%
Type of losses AoAk
PkrT 9 kW
System earthing arrangement TN-S
MV Connection D
LV Connection yn
No load secondary voltage Ur0 420V
Ur LV 400V
Rb (neutral grounding) NA
Ra (mass grounding) NA
Sizing information UkrT and PkrT calculated by system
Cable WD 1
Parameters
Length 15 m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Ib 1750 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Project: T16-6081 06/08/2023
Page 13/115
Selected phase
Cross section area 7x300 mm²
Core Copper
Iz under real conditions 3956 A
Iz’ 4347 A
Selected neutral
Cross section area 7x150 mm²
Core Copper
Iz under real conditions 2542 A
Iz’ 2793 A
Selected PE
Cross section area 7x150 mm²
Core Copper
Circuit breaker QA 1
Ib 1443 A
Distance from origin NA
Selectivity Results
UpStream Selectivity Limit
Project: T16-6081 06/08/2023
Page 14/115
Design current
IL1 IL2 IL3 IN
Tr 4s
Short delay settings
Isd current 4530 A
Tsd 0.4 s
Instantaneous tripping
Ii current 6930 A
Ti current 50 s
Selectivity Results
UpStream Selectivity Limit
Selected phase
Cross section area 1x300 mm²
Core Copper
Iz under real conditions 465 A
Iz’ 465 A
Selected neutral
Cross section area 1x300 mm²
Core Copper
Iz under real conditions 465 A
Iz’ 465 A
Selected PE
Cross section area 1x150 mm²
Core Copper
Selectivity Results
UpStream Selectivity Limit
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 405 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.8
Standard table reference B-52-17
User correction factor 1
Overall factor 0.8
Selected phase
Cross section area 2x240 mm²
Core Copper
Iz under real conditions 651 A
Iz’ 814 A
Selected neutral
Cross section area 2x120 mm²
Core Copper
Iz under real conditions 429 A
Iz’ 536 A
Selected PE
Cross section area 1x240 mm²
Core Copper
Tr 4s
Short delay settings
Isd current 4060 A
Tsd 0.4 s
Instantaneous tripping
Ii current 6930 A
Ti current 50 s
Selectivity Results
UpStream Selectivity Limit
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 156 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.8
Standard table reference B-52-17
User correction factor 1
Overall factor 0.8
Selected phase
Cross section area 2x120 mm²
Core Copper
Iz under real conditions 429 A
Iz’ 536 A
Selected neutral
Cross section area 2x120 mm²
Core Copper
Iz under real conditions 429 A
Iz’ 536 A
Selected PE
Cross section area 1x120 mm²
Core Copper
Tr NA
Short delay settings
Isd current 1250 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA
Selectivity Results
UpStream Selectivity Limit
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 530 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 2x240 mm²
Core Copper
Iz under real conditions 1076 A
Iz’ 1076 A
Selected neutral
Cross section area 2x240 mm²
Core Copper
Iz under real conditions 1076 A
Iz’ 1076 A
Selected PE
Cross section area 1x240 mm²
Core Copper
Tr 4s
Short delay settings
Isd current 5310 A
Tsd 0.4 s
Instantaneous tripping
Ii current 6930 A
Ti current 50 s
Selectivity Results
UpStream Selectivity Limit
Design current
IL1 IL2 IL3 IN
3.3.1 Circuit Load 10 (4) (3) (1) (1) (2) (1) (1)
Circuit breaker QA 10 (4) (3) (1) (1) (2) (1) (1)
Ib 23.6 A
Distance from origin NA
Selectivity Results
UpStream Selectivity Limit
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Charge PP-GF-0.1
U 400 V
S 16.3 kVA
P 13.9 kW
I 23.6 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Project: T16-6081 06/08/2023
Page 29/115
3.3.2 Circuit Load 10 (4) (3) (1) (1) (1) (2) (1)
Circuit breaker QA 10 (4) (3) (1) (1) (1) (2) (1)
Ib 54.1 A
Distance from origin NA
Selectivity Results
UpStream Selectivity Limit
Ib 54 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 2x35 mm²
Core Copper
Iz under real conditions 316 A
Iz’ 316 A
Selected neutral
Cross section area 2x16 mm²
Core Copper
Iz under real conditions 200 A
Iz’ 200 A
Selected PE
Cross section area 1x35 mm²
Core Copper
Charge KITCHEN
U 400 V
S 37.5 kVA
P 31.9 kW
I 54.1 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 161 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 2x95 mm²
Core Copper
Iz under real conditions 596 A
Iz’ 596 A
Selected neutral
Cross section area 2x50 mm²
Core Copper
Iz under real conditions 384 A
Iz’ 384 A
Selected PE
Cross section area 1x95 mm²
Core Copper
Charge UPP-GF-0.2
U 400 V
S 112 kVA
P 95 kW
I 161 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator Yes
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 10 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Charge SHOP(4)
U 400 V
S 7 kVA
P 5.95 kW
I 10.1 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 10 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Charge SHOP(6)
U 400 V
S 7 kVA
P 5.95 kW
I 10.1 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 10 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Charge SHOP(5)
U 400 V
S 7 kVA
P 5.95 kW
I 10.1 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 42 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 2x25 mm²
Core Copper
Iz under real conditions 254 A
Iz’ 254 A
Selected neutral
Cross section area 2x16 mm²
Core Copper
Iz under real conditions 200 A
Iz’ 200 A
Selected PE
Cross section area 1x25 mm²
Core Copper
Charge ACP-GF-22
U 400 V
S 28.9 kVA
P 24.5 kW
I 41.7 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 42 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Charge PP-GF-0.2
U 400 V
S 29.4 kVA
P 25 kW
I 42.4 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 9A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Charge LP-GF-0.2
U 400 V
S 6.48 kVA
P 5.51 kW
I 9.4 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
3.3.10 Circuit Load 10 (4) (3) (1) (1) (1) (2) (2) (1)
Circuit breaker QA 10 (4) (3) (1) (1) (1) (2) (2) (1)
Ib 21.7 A
Distance from origin NA
Selectivity Results
UpStream Selectivity Limit
Ib 22 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 2x16 mm²
Core Copper
Iz under real conditions 200 A
Iz’ 200 A
Selected neutral
Cross section area 2x16 mm²
Core Copper
Iz under real conditions 200 A
Iz’ 200 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Charge MCC-R
U 400 V
S 15 kVA
P 12.8 kW
I 21.7 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator Yes
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 69 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 2x70 mm²
Core Copper
Iz under real conditions 492 A
Iz’ 492 A
Selected neutral
Cross section area 2x35 mm²
Core Copper
Iz under real conditions 316 A
Iz’ 316 A
Selected PE
Cross section area 1x50 mm²
Core Copper
Charge ACP-FF-12
U 400 V
S 48 kVA
P 40.8 kW
I 69.3 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator Yes
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 185 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.88
Standard table reference B-52-20
User correction factor 1
Overall factor 0.88
Selected phase
Cross section area 2x95 mm²
Core Copper
Iz under real conditions 524 A
Iz’ 596 A
Selected neutral
Cross section area 2x50 mm²
Core Copper
Iz under real conditions 338 A
Iz’ 384 A
Selected PE
Cross section area 1x95 mm²
Core Copper
Charge UPP-FF-0.1
U 400 V
S 128 kVA
P 109 kW
I 185 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator Yes
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 12 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Charge LP-FF-0.1
U 400 V
S 8.65 kVA
P 7.35 kW
I 12.5 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 63 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 2x16 mm²
Core Copper
Iz under real conditions 200 A
Iz’ 200 A
Selected neutral
Cross section area 2x16 mm²
Core Copper
Iz under real conditions 200 A
Iz’ 200 A
Selected PE
Cross section area 1x16 mm²
Core Copper
Charge PP-FF-0.1
U 400 V
S 43.8 kVA
P 37.3 kW
I 63.3 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 122 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 2x95 mm²
Core Copper
Iz under real conditions 596 A
Iz’ 596 A
Selected neutral
Cross section area 2x50 mm²
Core Copper
Iz under real conditions 384 A
Iz’ 384 A
Selected PE
Cross section area 1x95 mm²
Core Copper
Charge ACP-FF-11
U 400 V
S 84.2 kVA
P 71.6 kW
I 122 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator Yes
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 120 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 2x95 mm²
Core Copper
Iz under real conditions 596 A
Iz’ 596 A
Selected neutral
Cross section area 2x50 mm²
Core Copper
Iz under real conditions 384 A
Iz’ 384 A
Selected PE
Cross section area 1x95 mm²
Core Copper
Charge ACP-GF-21
U 400 V
S 83.1 kVA
P 70.7 kW
I 120 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator Yes
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 7A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Charge UPS-GF-0.1
U 400 V
S 4.54 kVA
P 3.86 kW
I 6.55 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 88 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 2x50 mm²
Core Copper
Iz under real conditions 384 A
Iz’ 384 A
Selected neutral
Cross section area 2x25 mm²
Core Copper
Iz under real conditions 254 A
Iz’ 254 A
Selected PE
Cross section area 1x50 mm²
Core Copper
Charge ACP-GF-11
U 400 V
S 61.2 kVA
P 52.1 kW
I 88.4 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator Yes
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
3.3.19 Circuit Load 10 (4) (3) (1) (4) (2) (1) (1)
Circuit breaker QA 10 (4) (3) (1) (4) (2) (1) (1)
Ib 7.61 A
Distance from origin NA
Selectivity Results
UpStream Selectivity Limit
Ib 8A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Charge LP-GF-0.1
U 400 V
S 5.27 kVA
P 4.48 kW
I 7.61 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 10 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Charge SHOP(3)
U 400 V
S 7 kVA
P 5.95 kW
I 10.1 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 10 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Charge SHOP(1)
U 400 V
S 7 kVA
P 5.95 kW
I 10.1 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 10 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Charge SHOP(2)
U 400 V
S 7 kVA
P 5.95 kW
I 10.1 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
3.3.23 Circuit Load 10 (4) (3) (1) (1) (1) (2) (2) (1) (1)
Circuit breaker QA 10 (4) (3) (1) (1) (1) (2) (2) (1) (1)
Ib 131 A
Distance from origin NA
Selectivity Results
UpStream Selectivity Limit
Cable WD 10 (4) (3) (1) (1) (1) (2) (2) (1) (1)
Parameters
Length 65 m
Max length 277 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 94/115
Ib 131 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 2x95 mm²
Core Copper
Iz under real conditions 596 A
Iz’ 596 A
Selected neutral
Cross section area 2x50 mm²
Core Copper
Iz under real conditions 384 A
Iz’ 384 A
Selected PE
Cross section area 1x95 mm²
Core Copper
Charge MCC-F
U 400 V
S 90.6 kVA
P 77 kW
I 131 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 92 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x70 mm²
Core Copper
Iz under real conditions 246 A
Iz’ 246 A
Selected neutral
Cross section area 1x35 mm²
Core Copper
Iz under real conditions 158 A
Iz’ 158 A
Selected PE
Cross section area 1x70 mm²
Core Copper
Charge ACP-FF-21
U 400 V
S 64 kVA
P 54.4 kW
I 92.4 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 13 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Charge LP-FF-0.2
U 400 V
S 8.72 kVA
P 7.41 kW
I 12.6 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 183 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x95 mm²
Core Copper
Iz under real conditions 298 A
Iz’ 298 A
Selected neutral
Cross section area 1x50 mm²
Core Copper
Iz under real conditions 192 A
Iz’ 192 A
Selected PE
Cross section area 1x95 mm²
Core Copper
Charge UPP-FF-02
U 400 V
S 127 kVA
P 108 kW
I 183 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 69 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x25 mm²
Core Copper
Iz under real conditions 127 A
Iz’ 127 A
Selected neutral
Cross section area 1x16 mm²
Core Copper
Iz under real conditions 100 A
Iz’ 100 A
Selected PE
Cross section area 1x25 mm²
Core Copper
Charge PP-FF-0.2
U 400 V
S 47.6 kVA
P 40.5 kW
I 68.7 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Ib 173 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x185 mm²
Core Copper
Iz under real conditions 456 A
Iz’ 456 A
Selected neutral
Cross section area 1x95 mm²
Core Copper
Iz under real conditions 298 A
Iz’ 298 A
Selected PE
Cross section area 1x185 mm²
Core Copper
Charge ACP-FF-22
U 400 V
S 120 kVA
P 102 kW
I 173 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Load 10 (4) (3) (1) (1) (1) QA 10 (4) (3) (1) (1) (1) NG125H
(2) (2) (1) (2) (2) (1)
Load 10 (4) (3) (1) (1) (1) QA 10 (4) (3) (1) (1) (1) NG125H
(2) (1) (2) (1)
Load 10 (4) (3) (1) (1) (1) QA 10 (4) (3) (1) (1) (1) NSXm160F
(2) (2) (1) (1) (2) (2) (1) (1)
Feeder circuit 5 (1) (1) QA 5 (1) (1) (1) (1) (1) NSX630F
(1) (1) (1)
Load 10 (2) (1) (1) (2) QA 10 (2) (1) (1) (2) iC60L
Load 10 (1) (1) (1) (2) QA 10 (1) (1) (1) (2) iC60L
Load 10 (4) (3) (1) (1) (2) QA 10 (4) (3) (1) (1) (2) NG125N
(1) (1)
Load 10 (4) (3) (1) (2) (1) QA 10 (4) (3) (1) (2) (1) NG125N
Load 10 (4) (3) (1) (5) (2) QA 10 (4) (3) (1) (5) (2) NSX250B
(1) (1)
Load 10 (3) (1) (1) (2) QA 10 (3) (1) (1) (2) iC60L
Load 10 (4) (3) (1) (4) (2) QA 10 (4) (3) (1) (4) (2) iC60L
(1) (1)
Load 10 (3) (1) (1) (1) (1) QA 10 (3) (1) (1) (1) (1) NSX250B
Load 10 (1) (1) (1) (1) (1) QA 10 (1) (1) (1) (1) (1) C120H
Load 10 (4) (1) (1) (1) QA 10 (4) (1) (1) (1) C120H
Load 10 (4) (2) (1) (1) (1) QA 10 (4) (2) (1) (1) (1) iC60H
Load 10 (2) (1) (1) (1) (1) QA 10 (2) (1) (1) (1) (1) C120H
Load 10 (4) (1) (2) (1) (1) QA 10 (4) (1) (2) (1) (1) iC60L
Load 10 (3) (1) (1) (2) (1) QA 10 (3) (1) (1) (2) (1) iC60L
Load 10 (2) (1) (1) (2) (1) QA 10 (2) (1) (1) (2) (1) iC60L
Load 10 (4) (1) (2) (1) QA 10 (4) (1) (2) (1) iC60L
Load 10 (4) (3) (1) (1) (2) QA 10 (4) (3) (1) (1) (2) iC60L
(1) (1) (1) (1)
Load 10 (4) (3) (1) (4) (2) QA 10 (4) (3) (1) (4) (2) iC60L
(1) (1) (1) (1)
Load 10 (4) (3) (1) (2) (1) QA 10 (4) (3) (1) (2) (1) NG125N
(1) (1)
Parameters
Switchboard Name UC 7 (1) (1) (1)
Switchboard Range No preference
Rating (A) NA
IP Undefined
Feeder
Circuit name Protection name Protection type
Load 10 (3) (1) (1) (1) QA 10 (3) (1) (1) (1) NSX250B
Load 10 (1) (1) (1) (1) QA 10 (1) (1) (1) (1) NG125N
Load 10 (4) (2) (1) (1) QA 10 (4) (2) (1) (1) iC60L
Load 10 (2) (1) (1) (1) QA 10 (2) (1) (1) (1) NSX250B
</IF>
NOTICE
RISK OF INACCURATE DATA RESULTS.
Configure the software correctly to get accurate reports and/or data results.
Do not rely solely on software messages and reports to determine if the
system is functioning correctly.
Make sure that you have entered the correct inputs for the required
components.
Review the calculated results and solutions provided by the software before
submitting the report.
Failure to follow these instructions can result in incorrect bill of material and
loss of business.