Installation calculation report

T16-6081
Full
Page 2/115

Project: T16-6081 06/08/2023


Page 3/115

Content

1 Project description.................................................................................................................. 4
1.1 Project general settings................................................................................................................... 4

1.2 Settings for wiring device calculation............................................................................................ 4

1.3 List of loads...................................................................................................................................... 4

2 Installation general design.....................................................................................................6


2.1 List of devices.................................................................................................................................. 6

3 Calculation notes.................................................................................................................. 14
3.1 Source circuits............................................................................................................................... 14

3.2 Generator circuits.......................................................................................................................... 23

3.3 LV Source circuits.......................................................................................................................... 23

3.4 UPS circuits.................................................................................................................................... 23

3.5 Surge Arrester circuits.................................................................................................................. 24

3.6 Capacitor bank circuits.................................................................................................................. 24

3.7 Feeder circuits................................................................................................................................ 24

3.8 LV Transformer circuits................................................................................................................. 26

3.9 Couplers circuits............................................................................................................................ 27

3.10 Generic load circuits................................................................................................................. 28

3.11 Lighting load circuits................................................................................................................ 28

3.12 Power socket load circuits....................................................................................................... 29

3.13 Motor starter combination........................................................................................................ 29

3.14 Busbar circuits.......................................................................................................................... 30

3.15 Busbar trunking system circuits............................................................................................. 30

3.16 Busbar trunking system circuits............................................................................................. 30

3.17 Lighting Busbar trunking system circuits..............................................................................30

Project: T16-6081 06/08/2023


Page 4/115

1 Project description
1.1 Project general settings
Installation standard IEC60364

Calculation standard TR50480


Circuit breaker standard IEC 60947-2
Frequency 50 Hz

1.2 Settings for wiring device calculation


Maximal CSA 300 mm²

1.3 List of loads


1.3.1 Generic loads
Name Sr (kVA) Pr (kW) Ir (A) Cos Nbr Polarity Non linear load THDi 3 (%)
PP-GF- 16.3 13.9 23.6 0.85 1 3Ph+N No 0
0.1
KITCHE 37.5 31.9 54.1 0.85 1 3Ph+N No 0
N
UPP- 112 95 161 0.85 1 3Ph+N Yes 0
GF-0.2
SHOP(4) 7 5.95 10.1 0.85 1 3Ph+N No 0
SHOP(6) 7 5.95 10.1 0.85 1 3Ph+N No 0
SHOP(5) 7 5.95 10.1 0.85 1 3Ph+N No 0
ACP- 28.9 24.5 41.7 0.85 1 3Ph+N No 0
GF-22
PP-GF- 29.4 25 42.4 0.85 1 3Ph+N No 0
0.2
LP-GF- 6.48 5.51 9.4 0.85 1 3Ph+N No 0
0.2
MCC-R 15 12.8 21.7 0.85 1 3Ph+N Yes 0
ACP-FF- 48 40.8 69.3 0.85 1 3Ph+N Yes 0
12
UPP-FF- 128 109 185 0.85 1 3Ph+N Yes 0
0.1
LP-FF- 8.65 7.35 12.5 0.85 1 3Ph+N No 0
0.1
PP-FF- 43.8 37.3 63.3 0.85 1 3Ph+N No 0
0.1
ACP-FF- 84.2 71.6 122 0.85 1 3Ph+N Yes 0
11
ACP- 83.1 70.7 120 0.85 1 3Ph+N Yes 0
GF-21
UPS- 4.54 3.86 6.55 0.85 1 3Ph+N No 0
GF-0.1
ACP- 61.2 52.1 88.4 0.85 1 3Ph+N Yes 0
GF-11
LP-GF- 5.27 4.48 7.61 0.85 1 3Ph+N No 0
0.1
SHOP(3) 7 5.95 10.1 0.85 1 3Ph+N No 0
SHOP(1) 7 5.95 10.1 0.85 1 3Ph+N No 0
SHOP(2) 7 5.95 10.1 0.85 1 3Ph+N No 0
MCC-F 90.6 77 131 0.85 1 3Ph+N No 0
ACP-FF- 64 54.4 92.4 0.85 1 3Ph+N No 0
21
LP-FF- 8.72 7.41 12.6 0.85 1 3Ph+N No 0
Project: T16-6081 06/08/2023
Page 5/115

0.2
UPP-FF- 127 108 183 0.85 1 3Ph+N No 0
02
PP-FF- 47.6 40.5 68.7 0.85 1 3Ph+N No 0
0.2
ACP-FF- 120 102 173 0.85 1 3Ph+N No 0
22

Project: T16-6081 06/08/2023


Page 6/115

2 Installation general design


2.1 List of devices
2.1.1 MV/LV transformer
Name Nbr Range Insulation Sr (kVA) ukrT (%) Connection U2 (V) SEA Rb (m)
TA 1 1 Trihal Resin 1000 6 D 420 TN-S 10000

2.1.2 LV switchboards and busbar


Switchboard name Range Rating (A) IP
UC 3 No preference 0.00 Undefined
UC 7 (1) (1) (1) No preference 0.00 Undefined
UC 28 No preference 0.00 Undefined
UC 7 (1) (1) (1) (1) No preference 0.00 Undefined
UC 28 (1) No preference 0.00 Undefined

Busbar name Switchboard Ks Polarity SEA Equipotential bounding


name
WC 2 UC 3 1 3Ph+N TN-S With
WC 6 (1) (1) (2) UC 28 1 3Ph+N TN-S Without
WC 6 (1) (1) (1) (1) UC 7 (1) (1) (1) 1 3Ph+N TN-S Without
(1)
WC 6 (1) (1) (2) (1) UC 28 (1) 1 3Ph+N TN-S Without
WC 6 (1) (1) (1) UC 7 (1) (1) (1) 1 3Ph+N TN-S Without

2.1.3 Circuit breaker


Name Nbr Range - Rating Poles Trip RCD RCD class PowerTag PowerTag Energy
Designation (A) unit/Curve Energy ConnectionType
Designation
QA 1 1 Masterpact 1600 4P4d Micrologic
MTZ1 - 5.0 X
MTZ1 16H1
QA 10 1 Acti9 iC60 - 25 4P4d C
(4) (3) iC60L
(1) (1)
(2) (1)
(1)
QA 10 1 Acti9 NG125 63 4P4d C
(4) (3) - NG125H
(1) (1)
(1) (2)
(1)
QA 10 1 Compact 250 4P4d Micrologic
(4) (3) NSX - 5.2 E
(1) (5) NSX250B
(2) (1)
QA 10 1 Acti9 iC60 - 13 4P4d C
(1) (1) iC60L
(1) (2)
QA 10 1 Acti9 iC60 - 13 4P4d C
(3) (1) iC60L
(1) (2)
QA 10 1 Acti9 iC60 - 13 4P4d C
(2) (1) iC60L
(1) (2)
QA 10 1 Acti9 NG125 50 4P4d C
(4) (1) - NG125N
(2)

Project: T16-6081 06/08/2023


Page 7/115

QA 10 1 Acti9 NG125 50 4P4d C


(4) (3) - NG125N
(1) (1)
(2) (1)
QA 10 1 Acti9 iC60 - 10 4P4d C
(4) (3) iC60L
(1) (4)
(2) (1)
QA 10 1 Acti9 NG125 25 4P4d C
(4) (3) - NG125H
(1) (1)
(1) (2)
(2) (1)
QA 10 1 Acti9 C120 - 80 4P4d C
(2) (1) C120H
(1) (1)
(1)
QA 10 1 Compact 250 4P4d Micrologic
(3) (1) NSX - 5.2 E
(1) (1) NSX250B
(1)
QA 10 1 Acti9 iC60 - 13 4P4d C
(4) (2) iC60H
(1) (1)
(1)
QA 10 1 Acti9 C120 - 80 4P4d C
(4) (1) C120H
(1) (1)
QA 10 1 Acti9 C120 - 125 4P4d C
(1) (1) C120H
(1) (1)
(1)
QA 5 1 Compact 630 4P4d Micrologic
(1) (1) NSX - 5.3 E
(1) (1) NSX630F
QA 1 Compact 630 4P4d Micrologic
5bis NSX - 5.3 E
(1) (1) NSX630F
(1) (1)
QA 5 1 Compact 630 4P4d Micrologic
(1) (1) NSX - 5.3 E
(2) NSX630F
QA 1 Compact 630 4P4d Micrologic
5bis NSX - 5.3 E
(1) (1) NSX630F
(2)
QA 10 1 Acti9 NG125 125 4P4d C
(4) (3) - NG125N
(1) (2)
(1)
QA 10 1 Acti9 iC60 - 10 4P4d C
(3) (1) iC60L
(1) (2)
(1)
QA 5 1 Compact 160 4P4d TM-D
(1) (1) NSXm -
(2) (1) NSXm160F
QA 1 Compact 160 4P4d TM-D
5bis NSXm -
(1) (1) NSXm160B
(2) (1)
QA 10 1 Acti9 NG125 100 4P4d C

Project: T16-6081 06/08/2023


Page 8/115

(4) (3) - NG125N


(1) (2)
(1) (1)
QA 10 1 Acti9 iC60 - 10 4P4d C
(4) (3) iC60L
(1) (4)
(2) (1)
(1)
QA 10 1 Acti9 iC60 - 13 4P4d C
(2) (1) iC60L
(1) (2)
(1)
QA 10 1 Acti9 iC60 - 13 4P4d C
(4) (1) iC60L
(2) (1)
QA 10 1 Acti9 iC60 - 13 4P4d C
(4) (1) iC60L
(2) (1)
(1)
QA 10 1 Compact 160 4P4d TM-D
(4) (3) NSXm -
(1) (1) NSXm160F
(1) (2)
(2) (1)
(1)
QA 10 1 Acti9 NG125 100 4P4d C
(1) (1) - NG125N
(1) (1)
QA 10 1 Acti9 iC60 - 13 4P4d C
(4) (2) iC60L
(1) (1)
QA 10 1 Compact 250 4P4d Micrologic
(3) (1) NSX - 5.2 E
(1) (1) NSX250B
QA 5 1 Compact 630 4P4d Micrologic
(1) (1) NSX - 5.3 E
(1) (1) NSX630F
(1)
QA 1 Compact 630 4P4d Micrologic
5bis NSX - 5.3 E
(1) (1) NSX630F
(1) (1)
(1)
QA 10 1 Acti9 NG125 80 4P4d C
(4) (1) - NG125N
(1)
QA 10 1 Compact 250 4P4d Micrologic
(2) (1) NSX - 5.2 E
(1) (1) NSX250B

2.1.4 Cable schedule


Name Nbr Incomer Feeder Type Insulation L (m) L1/L2/L3 N PE/PEN
WD 5 1 QA 5 (1) QA 5bis Multi-core XLPE 95 2x240 2x240 1x240 Copper
(1) (1) (1) (1) (1) (1) Copper Copper
(1) (1) (1) (1) (1) (1)
(1) (1)
WD 10 1 QA 10 MCC-R Multi-core XLPE 90 2x16 2x16 1x10 Copper
(4) (3) (4) (3) Copper Copper
(1) (1) (1) (1)
(1) (2) (1) (2)
(2) (1) (2) (1)
WD 5 1 QA 5 (1) QA 5bis Multi-core XLPE 80 2x120 2x120 1x120 Copper
Project: T16-6081 06/08/2023
Page 9/115

(1) (1) (1) (2) (1) (1) Copper Copper


(2) (1) (1) (2) (1)
WD 5 1 QA 5 (1) QA 5bis Multi-core XLPE 80 2x240 2x120 1x240 Copper
(1) (1) (1) (2) (1) (1) Copper Copper
(2) (2)
WD 5 1 QA 5 (1) QA 5bis Multi-core XLPE 80 1x300 1x300 1x150 Copper
(1) (1) (1) (1) (1) (1) Copper Copper
(1) (1) (1) (1) (1)
WD 10 1 QA 10 MCC-F Multi-core XLPE 65 2x95 2x50 1x95 Copper
(4) (3) (4) (3) Copper Copper
(1) (1) (1) (1)
(1) (2) (1) (2)
(2) (1) (2) (1)
(1) (1)
WD 10 1 QA 10 SHOP(6 Multi-core XLPE 65 1x10 1x10 1x10 Copper
(3) (1) (3) (1) ) Copper Copper
(1) (2) (1) (2)
WD 10 1 QA 10 SHOP(1 Multi-core XLPE 60 1x10 1x10 1x10 Copper
(4) (1) (4) (1) ) Copper Copper
(2) (1) (2) (1)
WD 10 1 QA 10 SHOP(5 Multi-core XLPE 50 1x10 1x10 1x10 Copper
(2) (1) (2) (1) ) Copper Copper
(1) (2) (1) (2)
WD 10 1 QA 10 SHOP(2 Multi-core XLPE 45 1x10 1x10 1x10 Copper
(4) (1) (4) (1) ) Copper Copper
(2) (1) (2) (1)
(1) (1)
WD 10 1 QA 10 KITCHE Multi-core XLPE 45 2x35 2x16 1x35 Copper
(4) (3) (4) (3) N Copper Copper
(1) (1) (1) (1)
(1) (2) (1) (2)
(1) (1)
WD 10 1 QA 10 SHOP(4 Multi-core XLPE 35 1x10 1x10 1x10 Copper
(1) (1) (1) (1) ) Copper Copper
(1) (2) (1) (2)
WD 10 1 QA 10 SHOP(3 Multi-core XLPE 30 1x10 1x10 1x10 Copper
(2) (1) (2) (1) ) Copper Copper
(1) (2) (1) (2)
(1) (1)
WD 1 1 TA 1 QA 1 Multi-core XLPE 15 7x300 7x150 7x150 Copper
Copper Copper
WD 10 1 QA 10 UPS- Multi-core XLPE 12 1x10 1x10 1x10 Copper
(3) (1) (3) (1) GF-0.1 Copper Copper
(1) (2) (1) (2)
(1) (1)
WD 10 1 QA 10 UPP-FF- Multi-core XLPE 12 2x95 2x50 1x95 Copper
(3) (1) (3) (1) 0.1 Copper Copper
(1) (1) (1) (1)
(1) (1)
WD 10 1 QA 10 UPP- Multi-core XLPE 12 2x95 2x50 1x95 Copper
(4) (3) (4) (3) GF-0.2 Copper Copper
(1) (5) (1) (5)
(2) (1) (2) (1)
WD 10 1 QA 10 ACP-FF- Multi-core XLPE 10 1x185 1x95 1x185 Copper
(2) (1) (2) (1) 22 Copper Copper
(1) (1) (1) (1)
WD 10 1 QA 10 PP-FF- Multi-core XLPE 10 1x25 1x16 1x25 Copper
(4) (1) (4) (1) 0.2 Copper Copper
(1) (1)
WD 10 1 QA 10 UPP-FF- Multi-core XLPE 10 1x95 1x50 1x95 Copper
(3) (1) (3) (1) 02 Copper Copper
(1) (1) (1) (1)

Project: T16-6081 06/08/2023


Page 10/115

WD 10 1 QA 10 LP-FF- Multi-core XLPE 10 1x10 1x10 1x10 Copper


(4) (2) (4) (2) 0.2 Copper Copper
(1) (1) (1) (1)
WD 10 1 QA 10 ACP-FF- Multi-core XLPE 10 1x70 1x35 1x70 Copper
(1) (1) (1) (1) 21 Copper Copper
(1) (1) (1) (1)
WD 10 1 QA 10 LP-GF- Multi-core XLPE 10 1x10 1x10 1x10 Copper
(4) (3) (4) (3) 0.1 Copper Copper
(1) (4) (1) (4)
(2) (1) (2) (1)
(1) (1)
WD 10 1 QA 10 ACP- Multi-core XLPE 10 2x50 2x25 1x50 Copper
(4) (3) (4) (3) GF-11 Copper Copper
(1) (2) (1) (2)
(1) (1) (1) (1)
WD 10 1 QA 10 ACP- Multi-core XLPE 10 2x95 2x50 1x95 Copper
(4) (3) (4) (3) GF-21 Copper Copper
(1) (2) (1) (2)
(1) (1)
WD 10 1 QA 10 ACP-FF- Multi-core XLPE 10 2x95 2x50 1x95 Copper
(1) (1) (1) (1) 11 Copper Copper
(1) (1) (1) (1)
(1) (1)
WD 10 1 QA 10 PP-FF- Multi-core XLPE 10 2x16 2x16 1x16 Copper
(4) (1) (4) (1) 0.1 Copper Copper
(1) (1) (1) (1)
WD 10 1 QA 10 LP-FF- Multi-core XLPE 10 1x10 1x10 1x10 Copper
(4) (2) (4) (2) 0.1 Copper Copper
(1) (1) (1) (1)
(1) (1)
WD 10 1 QA 10 ACP-FF- Multi-core XLPE 10 2x70 2x35 1x50 Copper
(2) (1) (2) (1) 12 Copper Copper
(1) (1) (1) (1)
(1) (1)
WD 10 1 QA 10 LP-GF- Multi-core XLPE 10 1x10 1x10 1x10 Copper
(4) (3) (4) (3) 0.2 Copper Copper
(1) (4) (1) (4)
(2) (1) (2) (1)
WD 10 1 QA 10 PP-GF- Multi-core XLPE 10 1x10 1x10 1x10 Copper
(4) (3) (4) (3) 0.2 Copper Copper
(1) (1) (1) (1)
(2) (1) (2) (1)
WD 10 1 QA 10 ACP- Multi-core XLPE 10 2x25 2x16 1x25 Copper
(4) (1) (4) (1) GF-22 Copper Copper
(2) (2)
WD 10 1 QA 10 PP-GF- Multi-core XLPE 10 1x10 1x10 1x10 Copper
(4) (3) (4) (3) 0.1 Copper Copper
(1) (1) (1) (1)
(2) (1) (2) (1)
(1) (1)

Project: T16-6081 06/08/2023


Page 11/115

NOTICE
RISK OF INACCURATE DATA RESULTS

 Make sure that you have provided all the required inputs for the conductor sizing.
 It is recommended to refer to the cable manufacturer's catalogue before making
the selection.

Failure to follow these instructions can result in incorrect bill of material and loss
of business.

2.1.5 MV Cable
Name Nbr Designation CSA (mm²) Icc (A) In (A) Un (kV)
MVWD 1 1 NA 1 x 300 Al 26.6 484 24

Project: T16-6081 06/08/2023


Page 12/115

3 Calculation notes

3.1 Source circuits


3.1.1 Circuit Source 1
MV power supply W1
Max. upstream short circuit power 750 MVA
Min. upstream short circuit power 250 MVA
MV Cable MVWD 1
Parameters
Length 10 m
Type of cable Multi core
Ib 26 A
Nb of conductor per phase 1
Cross section area 1 x 300 Al mm²
Core Aluminium
Short circuit withstand 26.6 kA
Assigned voltage 22 kV
Insulation voltage 24 kV

MV/LV transformer TA 1
Range Trihal
Technology Resin
Rated power 1000 kVA
ukrT 6%
Type of losses AoAk
PkrT 9 kW
System earthing arrangement TN-S
MV Connection D
LV Connection yn
No load secondary voltage Ur0 420V
Ur LV 400V
Rb (neutral grounding) NA
Ra (mass grounding) NA
Sizing information UkrT and PkrT calculated by system
Cable WD 1
Parameters
Length 15 m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Ib 1750 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Project: T16-6081 06/08/2023
Page 13/115

Touching conductor factor 0.91


Standard table reference B-52-20
User correction factor 1
Overall factor 0.91

Selected phase
Cross section area 7x300 mm²
Core Copper
Iz under real conditions 3956 A
Iz’ 4347 A
Selected neutral
Cross section area 7x150 mm²
Core Copper
Iz under real conditions 2542 A
Iz’ 2793 A
Selected PE
Cross section area 7x150 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 25.78 22.32 25.29 16.53 18.70 19.09 NA 22.11

Synthesis for all operating mode


(kA) 25.78 22.32 25.29 16.53 18.70 19.09 NA 22.11

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Circuit breaker QA 1
Ib 1443 A
Distance from origin NA

Sizing Information Sized by system


Range Masterpact MTZ1
Designation MTZ1 16H1
Circuit breaker rating 1600 A
Breaking capacity 42 kA
TNS One pole breaking capacity 42 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation Micrologic 5.0 X
Trip unit rating 1600 A
Long delay settings
Ir 1472 (Setting: 0.92) A
Tr 24 s
Short delay settings
Isd current 11776 A
Tsd 0.4 s
Instantaneous tripping
Ii current 24000 (Setting: 15) A
Ti current 0.05 s

Selectivity Results
UpStream Selectivity Limit
Project: T16-6081 06/08/2023
Page 14/115

Operating mode Normal


NA Selectivity can't be determinated : no
upstream Lv Breaker

Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 1750.155 1750.155 1750.155 0

Synthesis for all operating mode


(A) 1750.155 1750.155 1750.155 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.177 0.177
UL1L2 (%) 0.205 0.205
UL2L3 (%) 0.205 0.205
UL3L1 (%) 0.205 0.205
UL1N (%) 0.177 0.177
UL2N (%) 0.177 0.177
UL3N (%) 0.177 0.177

3.2 Feeder circuits


3.2.1 Circuit Feeder circuit 5 (1) (1) (1) (1)
Circuit breaker QA 5 (1) (1) (1) (1)
Ib 452 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX630F
Circuit breaker rating 630 A
Breaking capacity 36 kA
TNS One pole breaking capacity 36 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation Micrologic 5.3 E
Trip unit rating 630 A
Long delay settings
Ir 453 A
Project: T16-6081 06/08/2023
Page 15/115

Tr 4s
Short delay settings
Isd current 4530 A
Tsd 0.4 s
Instantaneous tripping
Ii current 6930 A
Ti current 50 s

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 1 Total Selectivity
MTZ1 16H1
Micrologic 5.0 X
1600 A / 4P4d

Cable WD 5 (1) (1) (1) (1)


Parameters
Length 80 m
Max length NA
Installation method 8
B2
Multi-core cable in cable trunking on a
wooden wall run horizontally
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Ib 452 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-17
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x300 mm²

Project: T16-6081 06/08/2023


Page 16/115

Core Copper
Iz under real conditions 465 A
Iz’ 465 A
Selected neutral
Cross section area 1x300 mm²
Core Copper
Iz under real conditions 465 A
Iz’ 465 A
Selected PE
Cross section area 1x150 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 14.61 12.65 9.96 9.73 7.71 6.89 NA 7.98

Synthesis for all operating mode


(kA) 14.61 12.65 9.96 9.73 7.71 6.89 NA 7.98

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Circuit breaker QA 5bis (1) (1) (1) (1)


Ib 452 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX630F
Circuit breaker rating 630 A
Breaking capacity 36 kA
TNS One pole breaking capacity 36 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation Micrologic 5.3 E
Trip unit rating 630 A
Long delay settings
Ir 453 A
Tr 4s
Short delay settings
Isd current 4530 A
Tsd 0.4 s
Instantaneous tripping
Ii current 6930 A
Ti current 50 s

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5 (1) (1) (1) (1) No Selectivity
NSX630F
Micrologic 5.3 E
630 A / 4P4d

Project: T16-6081 06/08/2023


Page 17/115

Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 452.022 452.022 452.022 0

Synthesis for all operating mode


(A) 452.022 452.022 452.022 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.888 1.711
UL1L2 (%) 2.181 1.976
UL2L3 (%) 2.181 1.976
UL3L1 (%) 2.181 1.976
UL1N (%) 1.888 1.711
UL2N (%) 1.888 1.711
UL3N (%) 1.888 1.711

Project: T16-6081 06/08/2023


Page 18/115

3.2.2 Circuit Feeder circuit 5 (1) (1) (2)


Circuit breaker QA 5 (1) (1) (2)
Ib 405 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX630F
Circuit breaker rating 630 A
Breaking capacity 36 kA
TNS One pole breaking capacity 36 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation Micrologic 5.3 E
Trip unit rating 630 A
Long delay settings
Ir 406 A
Tr 4s
Short delay settings
Isd current 4060 A
Tsd 0.4 s
Instantaneous tripping
Ii current 6930 A
Ti current 50 s

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 1 Total Selectivity
MTZ1 16H1
Micrologic 5.0 X
1600 A / 4P4d

Cable WD 5 (1) (1) (2)


Parameters
Length 80 m
Max length NA
Installation method 8
B2
Multi-core cable in cable trunking on a
wooden wall run horizontally
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 19/115

Ib 405 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.8
Standard table reference B-52-17
User correction factor 1
Overall factor 0.8

Selected phase
Cross section area 2x240 mm²
Core Copper
Iz under real conditions 651 A
Iz’ 814 A
Selected neutral
Cross section area 2x120 mm²
Core Copper
Iz under real conditions 429 A
Iz’ 536 A
Selected PE
Cross section area 1x240 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 18.49 16.01 12.91 12.15 9.65 8.77 NA 10.16

Synthesis for all operating mode


(kA) 18.49 16.01 12.91 12.15 9.65 8.77 NA 10.16

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Circuit breaker QA 5bis (1) (1) (2)


Ib 405 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX630F
Circuit breaker rating 630 A
Breaking capacity 36 kA
TNS One pole breaking capacity 36 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation Micrologic 5.3 E
Trip unit rating 630 A
Long delay settings
Ir 406 A
Project: T16-6081 06/08/2023
Page 20/115

Tr 4s
Short delay settings
Isd current 4060 A
Tsd 0.4 s
Instantaneous tripping
Ii current 6930 A
Ti current 50 s

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5 (1) (1) (2) No Selectivity
NSX630F
Micrologic 5.3 E
630 A / 4P4d

Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 405.026 405.026 405.026 0

Synthesis for all operating mode


(A) 405.026 405.026 405.026 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.062 0.884
UL1L2 (%) 1.226 1.021
UL2L3 (%) 1.226 1.021
UL3L1 (%) 1.226 1.021
UL1N (%) 1.062 0.884
UL2N (%) 1.062 0.884
UL3N (%) 1.062 0.884

Project: T16-6081 06/08/2023


Page 21/115

3.2.3 Circuit Feeder circuit 5 (1) (1) (2) (1)


Circuit breaker QA 5 (1) (1) (2) (1)
Ib 156 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSXm
Designation NSXm160F
Circuit breaker rating 160 A
Breaking capacity 36 kA
TNS One pole breaking capacity 36 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation TM-D
Trip unit rating 160 A
Long delay settings
Ir 160 A
Tr NA
Short delay settings
Isd current 1250 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 1 Total Selectivity
MTZ1 16H1
Micrologic 5.0 X
1600 A / 4P4d

Cable WD 5 (1) (1) (2) (1)


Parameters
Length 80 m
Max length NA
Installation method 8
B2
Multi-core cable in cable trunking on a
wooden wall run horizontally
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 22/115

Ib 156 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.8
Standard table reference B-52-17
User correction factor 1
Overall factor 0.8

Selected phase
Cross section area 2x120 mm²
Core Copper
Iz under real conditions 429 A
Iz’ 536 A
Selected neutral
Cross section area 2x120 mm²
Core Copper
Iz under real conditions 429 A
Iz’ 536 A
Selected PE
Cross section area 1x120 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 16.86 14.60 11.78 10.86 8.65 6.65 NA 7.70

Synthesis for all operating mode


(kA) 16.86 14.60 11.78 10.86 8.65 6.65 NA 7.70

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Circuit breaker QA 5bis (1) (1) (2) (1)


Ib 156 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSXm
Designation NSXm160B
Circuit breaker rating 160 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation TM-D
Trip unit rating 160 A
Long delay settings
Ir 160 A
Project: T16-6081 06/08/2023
Page 23/115

Tr NA
Short delay settings
Isd current 1250 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5 (1) (1) (2) (1) No Selectivity
NSXm160F
TM-D
160 A / 4P4d

Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 156.462 156.462 156.462 0

Synthesis for all operating mode


(A) 156.462 156.462 156.462 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.746 0.569
UL1L2 (%) 0.862 0.657
UL2L3 (%) 0.862 0.657
UL3L1 (%) 0.862 0.657
UL1N (%) 0.746 0.569
UL2N (%) 0.746 0.569
UL3N (%) 0.746 0.569

Project: T16-6081 06/08/2023


Page 24/115

3.2.4 Circuit Feeder circuit 5 (1) (1) (1) (1) (1)


Circuit breaker QA 5 (1) (1) (1) (1) (1)
Ib 530 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX630F
Circuit breaker rating 630 A
Breaking capacity 36 kA
TNS One pole breaking capacity 36 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation Micrologic 5.3 E
Trip unit rating 630 A
Long delay settings
Ir 531 A
Tr 4s
Short delay settings
Isd current 5310 A
Tsd 0.4 s
Instantaneous tripping
Ii current 6930 A
Ti current 50 s

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 1 Total Selectivity
MTZ1 16H1
Micrologic 5.0 X
1600 A / 4P4d

Cable WD 5 (1) (1) (1) (1) (1)


Parameters
Length 95 m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 25/115

Ib 530 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 2x240 mm²
Core Copper
Iz under real conditions 1076 A
Iz’ 1076 A
Selected neutral
Cross section area 2x240 mm²
Core Copper
Iz under real conditions 1076 A
Iz’ 1076 A
Selected PE
Cross section area 1x240 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 17.51 15.17 12.88 11.53 9.83 7.91 NA 9.16

Synthesis for all operating mode


(kA) 17.51 15.17 12.88 11.53 9.83 7.91 NA 9.16

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Circuit breaker QA 5bis (1) (1) (1) (1) (1)


Ib 530 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX630F
Circuit breaker rating 630 A
Breaking capacity 36 kA
TNS One pole breaking capacity 36 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation Micrologic 5.3 E
Trip unit rating 630 A
Long delay settings
Ir 531 A
Project: T16-6081 06/08/2023
Page 26/115

Tr 4s
Short delay settings
Isd current 5310 A
Tsd 0.4 s
Instantaneous tripping
Ii current 6930 A
Ti current 50 s

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5 (1) (1) (1) (1) (1) No Selectivity
NSX630F
Micrologic 5.3 E
630 A / 4P4d

Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 530.098 530.098 530.098 0

Synthesis for all operating mode


(A) 530.098 530.098 530.098 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.552 1.374
UL1L2 (%) 1.792 1.587
UL2L3 (%) 1.792 1.587
UL3L1 (%) 1.792 1.587
UL1N (%) 1.552 1.374
UL2N (%) 1.552 1.374
UL3N (%) 1.552 1.374

Project: T16-6081 06/08/2023


Page 27/115

3.3 Generic load circuits

3.3.1 Circuit Load 10 (4) (3) (1) (1) (2) (1) (1)
Circuit breaker QA 10 (4) (3) (1) (1) (2) (1) (1)
Ib 23.6 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60L
Circuit breaker rating 25 A
Breaking capacity 25 kA
TNS One pole breaking capacity NaN kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 25 A
Long delay settings
Ir 25 A
Tr NA
Short delay settings
Isd current 200 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5bis (1) (1) (2) (1) Total Selectivity
NSXm160B
TM-D
160 A / 4P4d

Cable WD 10 (4) (3) (1) (1) (2) (1) (1)


Parameters
Length 10 m
Max length 95 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Project: T16-6081 06/08/2023
Page 28/115

Type of cable Multi-core


Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Ib 24 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 8.58 7.43 4.69 5.17 3.22 2.88 NA 3.33

Synthesis for all operating mode


(kA) 8.58 7.43 4.69 5.17 3.22 2.88 NA 3.33

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge PP-GF-0.1
U 400 V
S 16.3 kVA
P 13.9 kW
I 23.6 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Project: T16-6081 06/08/2023
Page 29/115

Sensitivity to over voltage NA


Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 23.585 23.585 23.585 0

Synthesis for all operating mode


(A) 23.585 23.585 23.585 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.956 0.210
UL1L2 (%) 1.104 0.242
UL2L3 (%) 1.104 0.242
UL3L1 (%) 1.104 0.242
UL1N (%) 0.956 0.210
UL2N (%) 0.956 0.210
UL3N (%) 0.956 0.210

Synthesis for all operating mode


U3L (%) 0.956
UL1L2 (%) 1.104
UL2L3 (%) 1.104
UL3L1 (%) 1.104
UL1N (%) 0.956
UL2N (%) 0.956
UL3N (%) 0.956

Project: T16-6081 06/08/2023


Page 30/115

3.3.2 Circuit Load 10 (4) (3) (1) (1) (1) (2) (1)
Circuit breaker QA 10 (4) (3) (1) (1) (1) (2) (1)
Ib 54.1 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 NG125
Designation NG125H
Circuit breaker rating 63 A
Breaking capacity 36 kA
TNS One pole breaking capacity 36 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 63 A
Long delay settings
Ir 63 A
Tr NA
Short delay settings
Isd current 504 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 1 Total Selectivity
MTZ1 16H1
Micrologic 5.0 X
1600 A / 4P4d

Cable WD 10 (4) (3) (1) (1) (1) (2) (1)


Parameters
Length 45 m
Max length 276 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 31/115

Ib 54 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 2x35 mm²
Core Copper
Iz under real conditions 316 A
Iz’ 316 A
Selected neutral
Cross section area 2x16 mm²
Core Copper
Iz under real conditions 200 A
Iz’ 200 A
Selected PE
Cross section area 1x35 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 14.33 12.41 6.06 8.82 4.15 4.35 NA 5.04

Synthesis for all operating mode


(kA) 14.33 12.41 6.06 8.82 4.15 4.35 NA 5.04

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge KITCHEN
U 400 V
S 37.5 kVA
P 31.9 kW
I 54.1 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 32/115

(A) 54.127 54.127 54.127 0

Synthesis for all operating mode


(A) 54.127 54.127 54.127 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.503 0.326
UL1L2 (%) 0.581 0.376
UL2L3 (%) 0.581 0.376
UL3L1 (%) 0.581 0.376
UL1N (%) 0.503 0.326
UL2N (%) 0.503 0.326
UL3N (%) 0.503 0.326

Synthesis for all operating mode


U3L (%) 0.503
UL1L2 (%) 0.581
UL2L3 (%) 0.581
UL3L1 (%) 0.581
UL1N (%) 0.503
UL2N (%) 0.503
UL3N (%) 0.503

Project: T16-6081 06/08/2023


Page 33/115

3.3.3 Circuit Load 10 (4) (3) (1) (5) (2) (1)


Circuit breaker QA 10 (4) (3) (1) (5) (2) (1)
Ib 161 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX250B
Circuit breaker rating 250 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation Micrologic 5.2 E
Trip unit rating 250 A
Long delay settings
Ir 162 A
Tr 0.5 s
Short delay settings
Isd current 1620 A
Tsd 0.4 s
Instantaneous tripping
Ii current 3000 A
Ti current 50 s

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5bis (1) (1) (2) Total Selectivity
NSX630F
Micrologic 5.3 E
630 A / 4P4d

Cable WD 10 (4) (3) (1) (5) (2) (1)


Parameters
Length 12 m
Max length 225 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 34/115

Ib 161 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 2x95 mm²
Core Copper
Iz under real conditions 596 A
Iz’ 596 A
Selected neutral
Cross section area 2x50 mm²
Core Copper
Iz under real conditions 384 A
Iz’ 384 A
Selected PE
Cross section area 1x95 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 17.38 15.05 11.29 11.39 8.34 7.61 NA 8.81

Synthesis for all operating mode


(kA) 17.38 15.05 11.29 11.39 8.34 7.61 NA 8.81

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge UPP-GF-0.2
U 400 V
S 112 kVA
P 95 kW
I 161 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator Yes
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 35/115

(A) 161.283 161.283 161.283 0

Synthesis for all operating mode


(A) 161.283 161.283 161.283 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.168 0.106
UL1L2 (%) 1.349 0.123
UL2L3 (%) 1.349 0.123
UL3L1 (%) 1.349 0.123
UL1N (%) 1.168 0.106
UL2N (%) 1.168 0.106
UL3N (%) 1.168 0.106

Synthesis for all operating mode


U3L (%) 1.168
UL1L2 (%) 1.349
UL2L3 (%) 1.349
UL3L1 (%) 1.349
UL1N (%) 1.168
UL2N (%) 1.168
UL3N (%) 1.168

Project: T16-6081 06/08/2023


Page 36/115

3.3.4 Circuit Load 10 (1) (1) (1) (2)


Circuit breaker QA 10 (1) (1) (1) (2)
Ib 10.1 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60L
Circuit breaker rating 13 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 13 A
Long delay settings
Ir 13 A
Tr NA
Short delay settings
Isd current 104 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5bis (1) (1) (2) Total Selectivity
NSX630F
Micrologic 5.3 E
630 A / 4P4d

Cable WD 10 (1) (1) (1) (2)


Parameters
Length 35 m
Max length 222 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 37/115

Ib 10 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 3.57 3.09 1.79 2.10 1.21 1.21 NA 1.40

Synthesis for all operating mode


(kA) 3.57 3.09 1.79 2.10 1.21 1.21 NA 1.40

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge SHOP(4)
U 400 V
S 7 kVA
P 5.95 kW
I 10.1 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 38/115

(A) 10.104 10.104 10.104 0

Synthesis for all operating mode


(A) 10.104 10.104 10.104 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.377 0.315
UL1L2 (%) 1.590 0.364
UL2L3 (%) 1.590 0.364
UL3L1 (%) 1.590 0.364
UL1N (%) 1.377 0.315
UL2N (%) 1.377 0.315
UL3N (%) 1.377 0.315

Synthesis for all operating mode


U3L (%) 1.377
UL1L2 (%) 1.590
UL2L3 (%) 1.590
UL3L1 (%) 1.590
UL1N (%) 1.377
UL2N (%) 1.377
UL3N (%) 1.377

Project: T16-6081 06/08/2023


Page 39/115

3.3.5 Circuit Load 10 (3) (1) (1) (2)


Circuit breaker QA 10 (3) (1) (1) (2)
Ib 10.1 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60L
Circuit breaker rating 13 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 13 A
Long delay settings
Ir 13 A
Tr NA
Short delay settings
Isd current 104 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5bis (1) (1) (2) Total Selectivity
NSX630F
Micrologic 5.3 E
630 A / 4P4d

Cable WD 10 (3) (1) (1) (2)


Parameters
Length 65 m
Max length 222 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 40/115

Ib 10 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 2.01 1.74 1.00 1.18 0.68 0.68 NA 0.79

Synthesis for all operating mode


(kA) 2.01 1.74 1.00 1.18 0.68 0.68 NA 0.79

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge SHOP(6)
U 400 V
S 7 kVA
P 5.95 kW
I 10.1 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 41/115

(A) 10.104 10.104 10.104 0

Synthesis for all operating mode


(A) 10.104 10.104 10.104 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.646 0.585
UL1L2 (%) 1.901 0.675
UL2L3 (%) 1.901 0.675
UL3L1 (%) 1.901 0.675
UL1N (%) 1.646 0.585
UL2N (%) 1.646 0.585
UL3N (%) 1.646 0.585

Synthesis for all operating mode


U3L (%) 1.646
UL1L2 (%) 1.901
UL2L3 (%) 1.901
UL3L1 (%) 1.901
UL1N (%) 1.646
UL2N (%) 1.646
UL3N (%) 1.646

Project: T16-6081 06/08/2023


Page 42/115

3.3.6 Circuit Load 10 (2) (1) (1) (2)


Circuit breaker QA 10 (2) (1) (1) (2)
Ib 10.1 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60L
Circuit breaker rating 13 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 13 A
Long delay settings
Ir 13 A
Tr NA
Short delay settings
Isd current 104 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5bis (1) (1) (2) Total Selectivity
NSX630F
Micrologic 5.3 E
630 A / 4P4d

Cable WD 10 (2) (1) (1) (2)


Parameters
Length 50 m
Max length 222 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 43/115

Ib 10 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 2.57 2.23 1.29 1.51 0.87 0.87 NA 1.01

Synthesis for all operating mode


(kA) 2.57 2.23 1.29 1.51 0.87 0.87 NA 1.01

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge SHOP(5)
U 400 V
S 7 kVA
P 5.95 kW
I 10.1 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 44/115

(A) 10.104 10.104 10.104 0

Synthesis for all operating mode


(A) 10.104 10.104 10.104 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.512 0.450
UL1L2 (%) 1.745 0.519
UL2L3 (%) 1.745 0.519
UL3L1 (%) 1.745 0.519
UL1N (%) 1.512 0.450
UL2N (%) 1.512 0.450
UL3N (%) 1.512 0.450

Synthesis for all operating mode


U3L (%) 1.512
UL1L2 (%) 1.745
UL2L3 (%) 1.745
UL3L1 (%) 1.745
UL1N (%) 1.512
UL2N (%) 1.512
UL3N (%) 1.512

Project: T16-6081 06/08/2023


Page 45/115

3.3.7 Circuit Load 10 (4) (1) (2)


Circuit breaker QA 10 (4) (1) (2)
Ib 41.7 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 NG125
Designation NG125N
Circuit breaker rating 50 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 50 A
Long delay settings
Ir 50 A
Tr NA
Short delay settings
Isd current 400 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5bis (1) (1) (2) Total Selectivity
NSX630F
Micrologic 5.3 E
630 A / 4P4d

Cable WD 10 (4) (1) (2)


Parameters
Length 10 m
Max length 261 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 46/115

Ib 42 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 2x25 mm²
Core Copper
Iz under real conditions 254 A
Iz’ 254 A
Selected neutral
Cross section area 2x16 mm²
Core Copper
Iz under real conditions 200 A
Iz’ 200 A
Selected PE
Cross section area 1x25 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 16.15 13.99 9.51 10.40 6.82 6.16 NA 7.13

Synthesis for all operating mode


(kA) 16.15 13.99 9.51 10.40 6.82 6.16 NA 7.13

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge ACP-GF-22
U 400 V
S 28.9 kVA
P 24.5 kW
I 41.7 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 47/115

(A) 41.670 41.670 41.670 0

Synthesis for all operating mode


(A) 41.670 41.670 41.670 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.138 0.076
UL1L2 (%) 1.314 0.088
UL2L3 (%) 1.314 0.088
UL3L1 (%) 1.314 0.088
UL1N (%) 1.138 0.076
UL2N (%) 1.138 0.076
UL3N (%) 1.138 0.076

Synthesis for all operating mode


U3L (%) 1.138
UL1L2 (%) 1.314
UL2L3 (%) 1.314
UL3L1 (%) 1.314
UL1N (%) 1.138
UL2N (%) 1.138
UL3N (%) 1.138

Project: T16-6081 06/08/2023


Page 48/115

3.3.8 Circuit Load 10 (4) (3) (1) (1) (2) (1)


Circuit breaker QA 10 (4) (3) (1) (1) (2) (1)
Ib 42.4 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 NG125
Designation NG125N
Circuit breaker rating 50 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 50 A
Long delay settings
Ir 50 A
Tr NA
Short delay settings
Isd current 400 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5bis (1) (1) (2) Total Selectivity
NSX630F
Micrologic 5.3 E
630 A / 4P4d

Cable WD 10 (4) (3) (1) (1) (2) (1)


Parameters
Length 10 m
Max length 52 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 49/115

Ib 42 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 9.44 8.17 4.95 5.72 3.41 3.37 NA 3.90

Synthesis for all operating mode


(kA) 9.44 8.17 4.95 5.72 3.41 3.37 NA 3.90

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge PP-GF-0.2
U 400 V
S 29.4 kVA
P 25 kW
I 42.4 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 50/115

(A) 42.435 42.435 42.435 0

Synthesis for all operating mode


(A) 42.435 42.435 42.435 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.440 0.378
UL1L2 (%) 1.662 0.436
UL2L3 (%) 1.662 0.436
UL3L1 (%) 1.662 0.436
UL1N (%) 1.440 0.378
UL2N (%) 1.440 0.378
UL3N (%) 1.440 0.378

Synthesis for all operating mode


U3L (%) 1.440
UL1L2 (%) 1.662
UL2L3 (%) 1.662
UL3L1 (%) 1.662
UL1N (%) 1.440
UL2N (%) 1.440
UL3N (%) 1.440

Project: T16-6081 06/08/2023


Page 51/115

3.3.9 Circuit Load 10 (4) (3) (1) (4) (2) (1)


Circuit breaker QA 10 (4) (3) (1) (4) (2) (1)
Ib 9.4 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60L
Circuit breaker rating 10 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 10 A
Long delay settings
Ir 10 A
Tr NA
Short delay settings
Isd current 80 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5bis (1) (1) (2) Total Selectivity
NSX630F
Micrologic 5.3 E
630 A / 4P4d

Cable WD 10 (4) (3) (1) (4) (2) (1)


Parameters
Length 10 m
Max length 240 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 52/115

Ib 9A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 9.44 8.17 4.95 5.72 3.41 3.37 NA 3.90

Synthesis for all operating mode


(kA) 9.44 8.17 4.95 5.72 3.41 3.37 NA 3.90

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge LP-GF-0.2
U 400 V
S 6.48 kVA
P 5.51 kW
I 9.4 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 53/115

(A) 9.353 9.353 9.353 0

Synthesis for all operating mode


(A) 9.353 9.353 9.353 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.145 0.083
UL1L2 (%) 1.322 0.096
UL2L3 (%) 1.322 0.096
UL3L1 (%) 1.322 0.096
UL1N (%) 1.145 0.083
UL2N (%) 1.145 0.083
UL3N (%) 1.145 0.083

Synthesis for all operating mode


U3L (%) 1.145
UL1L2 (%) 1.322
UL2L3 (%) 1.322
UL3L1 (%) 1.322
UL1N (%) 1.145
UL2N (%) 1.145
UL3N (%) 1.145

Project: T16-6081 06/08/2023


Page 54/115

3.3.10 Circuit Load 10 (4) (3) (1) (1) (1) (2) (2) (1)
Circuit breaker QA 10 (4) (3) (1) (1) (1) (2) (2) (1)
Ib 21.7 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 NG125
Designation NG125H
Circuit breaker rating 25 A
Breaking capacity 36 kA
TNS One pole breaking capacity 36 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 25 A
Long delay settings
Ir 25 A
Tr NA
Short delay settings
Isd current 200 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 1 Total Selectivity
MTZ1 16H1
Micrologic 5.0 X
1600 A / 4P4d

Cable WD 10 (4) (3) (1) (1) (1) (2) (2) (1)


Parameters
Length 90 m
Max length 327 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 55/115

Ib 22 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 2x16 mm²
Core Copper
Iz under real conditions 200 A
Iz’ 200 A
Selected neutral
Cross section area 2x16 mm²
Core Copper
Iz under real conditions 200 A
Iz’ 200 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 4.60 3.98 2.37 2.71 1.60 0.78 NA 0.90

Synthesis for all operating mode


(kA) 4.60 3.98 2.37 2.71 1.60 0.78 NA 0.90

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge MCC-R
U 400 V
S 15 kVA
P 12.8 kW
I 21.7 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator Yes
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 56/115

(A) 21.651 21.651 21.651 0

Synthesis for all operating mode


(A) 21.651 21.651 21.651 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.726 0.549
UL1L2 (%) 0.839 0.634
UL2L3 (%) 0.839 0.634
UL3L1 (%) 0.839 0.634
UL1N (%) 0.726 0.549
UL2N (%) 0.726 0.549
UL3N (%) 0.726 0.549

Synthesis for all operating mode


U3L (%) 0.726
UL1L2 (%) 0.839
UL2L3 (%) 0.839
UL3L1 (%) 0.839
UL1N (%) 0.726
UL2N (%) 0.726
UL3N (%) 0.726

Project: T16-6081 06/08/2023


Page 57/115

3.3.11 Circuit Load 10 (2) (1) (1) (1) (1)


Circuit breaker QA 10 (2) (1) (1) (1) (1)
Ib 69.3 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 C120
Designation C120H
Circuit breaker rating 80 A
Breaking capacity 15 kA
TNS One pole breaking capacity 15 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 80 A
Long delay settings
Ir 80 A
Tr NA
Short delay settings
Isd current 680 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5bis (1) (1) (1) (1) Total Selectivity
NSX630F
Micrologic 5.3 E
630 A / 4P4d

Cable WD 10 (2) (1) (1) (1) (1)


Parameters
Length 10 m
Max length 404 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 58/115

Ib 69 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 2x70 mm²
Core Copper
Iz under real conditions 492 A
Iz’ 492 A
Selected neutral
Cross section area 2x35 mm²
Core Copper
Iz under real conditions 316 A
Iz’ 316 A
Selected PE
Cross section area 1x50 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 13.89 12.03 9.00 9.21 6.85 5.90 NA 6.83

Synthesis for all operating mode


(kA) 13.89 12.03 9.00 9.21 6.85 5.90 NA 6.83

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge ACP-FF-12
U 400 V
S 48 kVA
P 40.8 kW
I 69.3 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator Yes
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 59/115

(A) 69.282 69.282 69.282 0

Synthesis for all operating mode


(A) 69.282 69.282 69.282 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.938 0.049
UL1L2 (%) 2.238 0.057
UL2L3 (%) 2.238 0.057
UL3L1 (%) 2.238 0.057
UL1N (%) 1.938 0.049
UL2N (%) 1.938 0.049
UL3N (%) 1.938 0.049

Synthesis for all operating mode


U3L (%) 1.938
UL1L2 (%) 2.238
UL2L3 (%) 2.238
UL3L1 (%) 2.238
UL1N (%) 1.938
UL2N (%) 1.938
UL3N (%) 1.938

Project: T16-6081 06/08/2023


Page 60/115

3.3.12 Circuit Load 10 (3) (1) (1) (1) (1)


Circuit breaker QA 10 (3) (1) (1) (1) (1)
Ib 185 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX250B
Circuit breaker rating 250 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation Micrologic 5.2 E
Trip unit rating 250 A
Long delay settings
Ir 186 A
Tr 0.5 s
Short delay settings
Isd current 1860 A
Tsd 0.4 s
Instantaneous tripping
Ii current 3000 A
Ti current 50 s

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5bis (1) (1) (1) (1) Total Selectivity
NSX630F
Micrologic 5.3 E
630 A / 4P4d

Cable WD 10 (3) (1) (1) (1) (1)


Parameters
Length 12 m
Max length 196 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 61/115

Ib 185 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.88
Standard table reference B-52-20
User correction factor 1
Overall factor 0.88

Selected phase
Cross section area 2x95 mm²
Core Copper
Iz under real conditions 524 A
Iz’ 596 A
Selected neutral
Cross section area 2x50 mm²
Core Copper
Iz under real conditions 338 A
Iz’ 384 A
Selected PE
Cross section area 1x95 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 13.89 12.03 9.06 9.22 6.92 6.10 NA 7.07

Synthesis for all operating mode


(kA) 13.89 12.03 9.06 9.22 6.92 6.10 NA 7.07

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge UPP-FF-0.1
U 400 V
S 128 kVA
P 109 kW
I 185 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator Yes
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 62/115

(A) 185.358 185.358 185.358 0

Synthesis for all operating mode


(A) 185.358 185.358 185.358 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 2.011 0.122
UL1L2 (%) 2.322 0.141
UL2L3 (%) 2.322 0.141
UL3L1 (%) 2.322 0.141
UL1N (%) 2.011 0.122
UL2N (%) 2.011 0.122
UL3N (%) 2.011 0.122

Synthesis for all operating mode


U3L (%) 2.011
UL1L2 (%) 2.322
UL2L3 (%) 2.322
UL3L1 (%) 2.322
UL1N (%) 2.011
UL2N (%) 2.011
UL3N (%) 2.011

Project: T16-6081 06/08/2023


Page 63/115

3.3.13 Circuit Load 10 (4) (2) (1) (1) (1)


Circuit breaker QA 10 (4) (2) (1) (1) (1)
Ib 12.5 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60H
Circuit breaker rating 13 A
Breaking capacity 15 kA
TNS One pole breaking capacity 15 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 13 A
Long delay settings
Ir 13 A
Tr NA
Short delay settings
Isd current 104 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5bis (1) (1) (1) (1) Total Selectivity
NSX630F
Micrologic 5.3 E
630 A / 4P4d

Cable WD 10 (4) (2) (1) (1) (1)


Parameters
Length 10 m
Max length 179 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 64/115

Ib 12 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 8.41 7.28 4.67 5.16 3.26 3.01 NA 3.49

Synthesis for all operating mode


(kA) 8.41 7.28 4.67 5.16 3.26 3.01 NA 3.49

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge LP-FF-0.1
U 400 V
S 8.65 kVA
P 7.35 kW
I 12.5 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 65/115

(A) 12.485 12.485 12.485 0

Synthesis for all operating mode


(A) 12.485 12.485 12.485 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 2.000 0.111
UL1L2 (%) 2.309 0.128
UL2L3 (%) 2.309 0.128
UL3L1 (%) 2.309 0.128
UL1N (%) 2.000 0.111
UL2N (%) 2.000 0.111
UL3N (%) 2.000 0.111

Synthesis for all operating mode


U3L (%) 2.000
UL1L2 (%) 2.309
UL2L3 (%) 2.309
UL3L1 (%) 2.309
UL1N (%) 2.000
UL2N (%) 2.000
UL3N (%) 2.000

Project: T16-6081 06/08/2023


Page 66/115

3.3.14 Circuit Load 10 (4) (1) (1) (1)


Circuit breaker QA 10 (4) (1) (1) (1)
Ib 63.3 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 C120
Designation C120H
Circuit breaker rating 80 A
Breaking capacity 15 kA
TNS One pole breaking capacity 15 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 80 A
Long delay settings
Ir 80 A
Tr NA
Short delay settings
Isd current 680 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5bis (1) (1) (1) (1) Total Selectivity
NSX630F
Micrologic 5.3 E
630 A / 4P4d

Cable WD 10 (4) (1) (1) (1)


Parameters
Length 10 m
Max length 112 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 67/115

Ib 63 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 2x16 mm²
Core Copper
Iz under real conditions 200 A
Iz’ 200 A
Selected neutral
Cross section area 2x16 mm²
Core Copper
Iz under real conditions 200 A
Iz’ 200 A
Selected PE
Cross section area 1x16 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 12.34 10.68 7.69 7.95 5.65 4.40 NA 5.09

Synthesis for all operating mode


(kA) 12.34 10.68 7.69 7.95 5.65 4.40 NA 5.09

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge PP-FF-0.1
U 400 V
S 43.8 kVA
P 37.3 kW
I 63.3 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 68/115

(A) 63.292 63.292 63.292 0

Synthesis for all operating mode


(A) 63.292 63.292 63.292 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 2.067 0.178
UL1L2 (%) 2.386 0.206
UL2L3 (%) 2.386 0.206
UL3L1 (%) 2.386 0.206
UL1N (%) 2.067 0.178
UL2N (%) 2.067 0.178
UL3N (%) 2.067 0.178

Synthesis for all operating mode


U3L (%) 2.067
UL1L2 (%) 2.386
UL2L3 (%) 2.386
UL3L1 (%) 2.386
UL1N (%) 2.067
UL2N (%) 2.067
UL3N (%) 2.067

Project: T16-6081 06/08/2023


Page 69/115

3.3.15 Circuit Load 10 (1) (1) (1) (1) (1)


Circuit breaker QA 10 (1) (1) (1) (1) (1)
Ib 122 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 C120
Designation C120H
Circuit breaker rating 125 A
Breaking capacity 15 kA
TNS One pole breaking capacity 15 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 125 A
Long delay settings
Ir 125 A
Tr NA
Short delay settings
Isd current 1062 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5bis (1) (1) (1) (1) Total Selectivity
NSX630F
Micrologic 5.3 E
630 A / 4P4d

Cable WD 10 (1) (1) (1) (1) (1)


Parameters
Length 10 m
Max length 298 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 70/115

Ib 122 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 2x95 mm²
Core Copper
Iz under real conditions 596 A
Iz’ 596 A
Selected neutral
Cross section area 2x50 mm²
Core Copper
Iz under real conditions 384 A
Iz’ 384 A
Selected PE
Cross section area 1x95 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 14.00 12.13 9.20 9.30 7.05 6.22 NA 7.20

Synthesis for all operating mode


(kA) 14.00 12.13 9.20 9.30 7.05 6.22 NA 7.20

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge ACP-FF-11
U 400 V
S 84.2 kVA
P 71.6 kW
I 122 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator Yes
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 71/115

(A) 121.604 121.604 121.604 0

Synthesis for all operating mode


(A) 121.604 121.604 121.604 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.955 0.067
UL1L2 (%) 2.258 0.077
UL2L3 (%) 2.258 0.077
UL3L1 (%) 2.258 0.077
UL1N (%) 1.955 0.067
UL2N (%) 1.955 0.067
UL3N (%) 1.955 0.067

Synthesis for all operating mode


U3L (%) 1.955
UL1L2 (%) 2.258
UL2L3 (%) 2.258
UL3L1 (%) 2.258
UL1N (%) 1.955
UL2N (%) 1.955
UL3N (%) 1.955

Project: T16-6081 06/08/2023


Page 72/115

3.3.16 Circuit Load 10 (4) (3) (1) (2) (1)


Circuit breaker QA 10 (4) (3) (1) (2) (1)
Ib 120 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 NG125
Designation NG125N
Circuit breaker rating 125 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 125 A
Long delay settings
Ir 125 A
Tr NA
Short delay settings
Isd current 1000 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5bis (1) (1) (2) Total Selectivity
NSX630F
Micrologic 5.3 E
630 A / 4P4d

Cable WD 10 (4) (3) (1) (2) (1)


Parameters
Length 10 m
Max length 302 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 73/115

Ib 120 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 2x95 mm²
Core Copper
Iz under real conditions 596 A
Iz’ 596 A
Selected neutral
Cross section area 2x50 mm²
Core Copper
Iz under real conditions 384 A
Iz’ 384 A
Selected PE
Cross section area 1x95 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 17.56 15.21 11.54 11.51 8.53 7.79 NA 9.02

Synthesis for all operating mode


(kA) 17.56 15.21 11.54 11.51 8.53 7.79 NA 9.02

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge ACP-GF-21
U 400 V
S 83.1 kVA
P 70.7 kW
I 120 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator Yes
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 74/115

(A) 119.973 119.973 119.973 0

Synthesis for all operating mode


(A) 119.973 119.973 119.973 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.128 0.066
UL1L2 (%) 1.302 0.076
UL2L3 (%) 1.302 0.076
UL3L1 (%) 1.302 0.076
UL1N (%) 1.128 0.066
UL2N (%) 1.128 0.066
UL3N (%) 1.128 0.066

Synthesis for all operating mode


U3L (%) 1.128
UL1L2 (%) 1.302
UL2L3 (%) 1.302
UL3L1 (%) 1.302
UL1N (%) 1.128
UL2N (%) 1.128
UL3N (%) 1.128

Project: T16-6081 06/08/2023


Page 75/115

3.3.17 Circuit Load 10 (3) (1) (1) (2) (1)


Circuit breaker QA 10 (3) (1) (1) (2) (1)
Ib 6.55 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60L
Circuit breaker rating 10 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 10 A
Long delay settings
Ir 10 A
Tr NA
Short delay settings
Isd current 80 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5bis (1) (1) (2) (1) Total Selectivity
NSXm160B
TM-D
160 A / 4P4d

Cable WD 10 (3) (1) (1) (2) (1)


Parameters
Length 12 m
Max length 342 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 76/115

Ib 7A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 7.70 6.67 4.14 4.61 2.83 2.57 NA 2.97

Synthesis for all operating mode


(kA) 7.70 6.67 4.14 4.61 2.83 2.57 NA 2.97

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge UPS-GF-0.1
U 400 V
S 4.54 kVA
P 3.86 kW
I 6.55 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 77/115

(A) 6.553 6.553 6.553 0

Synthesis for all operating mode


(A) 6.553 6.553 6.553 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.816 0.070
UL1L2 (%) 0.943 0.081
UL2L3 (%) 0.943 0.081
UL3L1 (%) 0.943 0.081
UL1N (%) 0.816 0.070
UL2N (%) 0.816 0.070
UL3N (%) 0.816 0.070

Synthesis for all operating mode


U3L (%) 0.816
UL1L2 (%) 0.943
UL2L3 (%) 0.943
UL3L1 (%) 0.943
UL1N (%) 0.816
UL2N (%) 0.816
UL3N (%) 0.816

Project: T16-6081 06/08/2023


Page 78/115

3.3.18 Circuit Load 10 (4) (3) (1) (2) (1) (1)


Circuit breaker QA 10 (4) (3) (1) (2) (1) (1)
Ib 88.4 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 NG125
Designation NG125N
Circuit breaker rating 100 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 100 A
Long delay settings
Ir 100 A
Tr NA
Short delay settings
Isd current 800 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5bis (1) (1) (2) (1) 1250 A
NSXm160B
TM-D
160 A / 4P4d

Cable WD 10 (4) (3) (1) (2) (1) (1)


Parameters
Length 10 m
Max length 234 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 79/115

Ib 88 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 2x50 mm²
Core Copper
Iz under real conditions 384 A
Iz’ 384 A
Selected neutral
Cross section area 2x25 mm²
Core Copper
Iz under real conditions 254 A
Iz’ 254 A
Selected PE
Cross section area 1x50 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 15.47 13.40 9.74 9.89 7.01 5.56 NA 6.44

Synthesis for all operating mode


(kA) 15.47 13.40 9.74 9.89 7.01 5.56 NA 6.44

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge ACP-GF-11
U 400 V
S 61.2 kVA
P 52.1 kW
I 88.4 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator Yes
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 80/115

(A) 88.407 88.407 88.407 0

Synthesis for all operating mode


(A) 88.407 88.407 88.407 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.832 0.085
UL1L2 (%) 0.960 0.098
UL2L3 (%) 0.960 0.098
UL3L1 (%) 0.960 0.098
UL1N (%) 0.832 0.085
UL2N (%) 0.832 0.085
UL3N (%) 0.832 0.085

Synthesis for all operating mode


U3L (%) 0.832
UL1L2 (%) 0.960
UL2L3 (%) 0.960
UL3L1 (%) 0.960
UL1N (%) 0.832
UL2N (%) 0.832
UL3N (%) 0.832

Project: T16-6081 06/08/2023


Page 81/115

3.3.19 Circuit Load 10 (4) (3) (1) (4) (2) (1) (1)
Circuit breaker QA 10 (4) (3) (1) (4) (2) (1) (1)
Ib 7.61 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60L
Circuit breaker rating 10 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 10 A
Long delay settings
Ir 10 A
Tr NA
Short delay settings
Isd current 80 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5bis (1) (1) (2) (1) Total Selectivity
NSXm160B
TM-D
160 A / 4P4d

Cable WD 10 (4) (3) (1) (4) (2) (1) (1)


Parameters
Length 10 m
Max length 295 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 82/115

Ib 8A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 8.58 7.43 4.69 5.17 3.22 2.88 NA 3.33

Synthesis for all operating mode


(kA) 8.58 7.43 4.69 5.17 3.22 2.88 NA 3.33

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge LP-GF-0.1
U 400 V
S 5.27 kVA
P 4.48 kW
I 7.61 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 83/115

(A) 7.607 7.607 7.607 0

Synthesis for all operating mode


(A) 7.607 7.607 7.607 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.814 0.068
UL1L2 (%) 0.940 0.078
UL2L3 (%) 0.940 0.078
UL3L1 (%) 0.940 0.078
UL1N (%) 0.814 0.068
UL2N (%) 0.814 0.068
UL3N (%) 0.814 0.068

Synthesis for all operating mode


U3L (%) 0.814
UL1L2 (%) 0.940
UL2L3 (%) 0.940
UL3L1 (%) 0.940
UL1N (%) 0.814
UL2N (%) 0.814
UL3N (%) 0.814

Project: T16-6081 06/08/2023


Page 84/115

3.3.20 Circuit Load 10 (2) (1) (1) (2) (1)


Circuit breaker QA 10 (2) (1) (1) (2) (1)
Ib 10.1 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60L
Circuit breaker rating 13 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 13 A
Long delay settings
Ir 13 A
Tr NA
Short delay settings
Isd current 104 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5bis (1) (1) (2) (1) Total Selectivity
NSXm160B
TM-D
160 A / 4P4d

Cable WD 10 (2) (1) (1) (2) (1)


Parameters
Length 30 m
Max length 222 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 85/115

Ib 10 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 3.90 3.38 2.00 2.30 1.36 1.29 NA 1.50

Synthesis for all operating mode


(kA) 3.90 3.38 2.00 2.30 1.36 1.29 NA 1.50

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge SHOP(3)
U 400 V
S 7 kVA
P 5.95 kW
I 10.1 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 86/115

(A) 10.104 10.104 10.104 0

Synthesis for all operating mode


(A) 10.104 10.104 10.104 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.016 0.270
UL1L2 (%) 1.174 0.312
UL2L3 (%) 1.174 0.312
UL3L1 (%) 1.174 0.312
UL1N (%) 1.016 0.270
UL2N (%) 1.016 0.270
UL3N (%) 1.016 0.270

Synthesis for all operating mode


U3L (%) 1.016
UL1L2 (%) 1.174
UL2L3 (%) 1.174
UL3L1 (%) 1.174
UL1N (%) 1.016
UL2N (%) 1.016
UL3N (%) 1.016

Project: T16-6081 06/08/2023


Page 87/115

3.3.21 Circuit Load 10 (4) (1) (2) (1)


Circuit breaker QA 10 (4) (1) (2) (1)
Ib 10.1 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60L
Circuit breaker rating 13 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 13 A
Long delay settings
Ir 13 A
Tr NA
Short delay settings
Isd current 104 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5bis (1) (1) (2) (1) Total Selectivity
NSXm160B
TM-D
160 A / 4P4d

Cable WD 10 (4) (1) (2) (1)


Parameters
Length 60 m
Max length 222 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 88/115

Ib 10 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 2.12 1.83 1.07 1.24 0.72 0.70 NA 0.82

Synthesis for all operating mode


(kA) 2.12 1.83 1.07 1.24 0.72 0.70 NA 0.82

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge SHOP(1)
U 400 V
S 7 kVA
P 5.95 kW
I 10.1 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 89/115

(A) 10.104 10.104 10.104 0

Synthesis for all operating mode


(A) 10.104 10.104 10.104 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.286 0.540
UL1L2 (%) 1.485 0.623
UL2L3 (%) 1.485 0.623
UL3L1 (%) 1.485 0.623
UL1N (%) 1.286 0.540
UL2N (%) 1.286 0.540
UL3N (%) 1.286 0.540

Synthesis for all operating mode


U3L (%) 1.286
UL1L2 (%) 1.485
UL2L3 (%) 1.485
UL3L1 (%) 1.485
UL1N (%) 1.286
UL2N (%) 1.286
UL3N (%) 1.286

Project: T16-6081 06/08/2023


Page 90/115

3.3.22 Circuit Load 10 (4) (1) (2) (1) (1)


Circuit breaker QA 10 (4) (1) (2) (1) (1)
Ib 10.1 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60L
Circuit breaker rating 13 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 13 A
Long delay settings
Ir 13 A
Tr NA
Short delay settings
Isd current 104 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5bis (1) (1) (2) (1) Total Selectivity
NSXm160B
TM-D
160 A / 4P4d

Cable WD 10 (4) (1) (2) (1) (1)


Parameters
Length 45 m
Max length 222 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 91/115

Ib 10 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 2.75 2.38 1.39 1.61 0.94 0.91 NA 1.06

Synthesis for all operating mode


(kA) 2.75 2.38 1.39 1.61 0.94 0.91 NA 1.06

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge SHOP(2)
U 400 V
S 7 kVA
P 5.95 kW
I 10.1 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 92/115

(A) 10.104 10.104 10.104 0

Synthesis for all operating mode


(A) 10.104 10.104 10.104 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.151 0.405
UL1L2 (%) 1.329 0.467
UL2L3 (%) 1.329 0.467
UL3L1 (%) 1.329 0.467
UL1N (%) 1.151 0.405
UL2N (%) 1.151 0.405
UL3N (%) 1.151 0.405

Synthesis for all operating mode


U3L (%) 1.151
UL1L2 (%) 1.329
UL2L3 (%) 1.329
UL3L1 (%) 1.329
UL1N (%) 1.151
UL2N (%) 1.151
UL3N (%) 1.151

Project: T16-6081 06/08/2023


Page 93/115

3.3.23 Circuit Load 10 (4) (3) (1) (1) (1) (2) (2) (1) (1)
Circuit breaker QA 10 (4) (3) (1) (1) (1) (2) (2) (1) (1)
Ib 131 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSXm
Designation NSXm160F
Circuit breaker rating 160 A
Breaking capacity 36 kA
TNS One pole breaking capacity 36 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation TM-D
Trip unit rating 160 A
Long delay settings
Ir 144 A
Tr NA
Short delay settings
Isd current 1250 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 1 Total Selectivity
MTZ1 16H1
Micrologic 5.0 X
1600 A / 4P4d

Cable WD 10 (4) (3) (1) (1) (1) (2) (2) (1) (1)
Parameters
Length 65 m
Max length 277 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 94/115

Ib 131 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 2x95 mm²
Core Copper
Iz under real conditions 596 A
Iz’ 596 A
Selected neutral
Cross section area 2x50 mm²
Core Copper
Iz under real conditions 384 A
Iz’ 384 A
Selected PE
Cross section area 1x95 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 17.35 15.03 10.09 11.10 7.16 6.77 NA 7.84

Synthesis for all operating mode


(kA) 17.35 15.03 10.09 11.10 7.16 6.77 NA 7.84

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge MCC-F
U 400 V
S 90.6 kVA
P 77 kW
I 131 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 95/115

(A) 130.770 130.770 130.770 0

Synthesis for all operating mode


(A) 130.770 130.770 130.770 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.645 0.468
UL1L2 (%) 0.745 0.540
UL2L3 (%) 0.745 0.540
UL3L1 (%) 0.745 0.540
UL1N (%) 0.645 0.468
UL2N (%) 0.645 0.468
UL3N (%) 0.645 0.468

Synthesis for all operating mode


U3L (%) 0.645
UL1L2 (%) 0.745
UL2L3 (%) 0.745
UL3L1 (%) 0.745
UL1N (%) 0.645
UL2N (%) 0.645
UL3N (%) 0.645

Project: T16-6081 06/08/2023


Page 96/115

3.3.24 Circuit Load 10 (1) (1) (1) (1)


Circuit breaker QA 10 (1) (1) (1) (1)
Ib 92.4 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 NG125
Designation NG125N
Circuit breaker rating 100 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 100 A
Long delay settings
Ir 100 A
Tr NA
Short delay settings
Isd current 800 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5bis (1) (1) (1) (1) (1) Total Selectivity
NSX630F
Micrologic 5.3 E
630 A / 4P4d

Cable WD 10 (1) (1) (1) (1)


Parameters
Length 10 m
Max length 151 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 97/115

Ib 92 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x70 mm²
Core Copper
Iz under real conditions 246 A
Iz’ 246 A
Selected neutral
Cross section area 1x35 mm²
Core Copper
Iz under real conditions 158 A
Iz’ 158 A
Selected PE
Cross section area 1x70 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 15.54 13.46 9.92 10.13 7.31 6.60 NA 7.64

Synthesis for all operating mode


(kA) 15.54 13.46 9.92 10.13 7.31 6.60 NA 7.64

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge ACP-FF-21
U 400 V
S 64 kVA
P 54.4 kW
I 92.4 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 98/115

(A) 92.376 92.376 92.376 0

Synthesis for all operating mode


(A) 92.376 92.376 92.376 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.684 0.132
UL1L2 (%) 1.944 0.152
UL2L3 (%) 1.944 0.152
UL3L1 (%) 1.944 0.152
UL1N (%) 1.684 0.132
UL2N (%) 1.684 0.132
UL3N (%) 1.684 0.132

Synthesis for all operating mode


U3L (%) 1.684
UL1L2 (%) 1.944
UL2L3 (%) 1.944
UL3L1 (%) 1.944
UL1N (%) 1.684
UL2N (%) 1.684
UL3N (%) 1.684

Project: T16-6081 06/08/2023


Page 99/115

3.3.25 Circuit Load 10 (4) (2) (1) (1)


Circuit breaker QA 10 (4) (2) (1) (1)
Ib 12.6 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60L
Circuit breaker rating 13 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 13 A
Long delay settings
Ir 13 A
Tr NA
Short delay settings
Isd current 104 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5bis (1) (1) (1) (1) (1) Total Selectivity
NSX630F
Micrologic 5.3 E
630 A / 4P4d

Cable WD 10 (4) (2) (1) (1)


Parameters
Length 10 m
Max length 178 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 100/115

Ib 13 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 9.16 7.94 5.09 5.56 3.51 3.24 NA 3.75

Synthesis for all operating mode


(kA) 9.16 7.94 5.09 5.56 3.51 3.24 NA 3.75

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge LP-FF-0.2
U 400 V
S 8.72 kVA
P 7.41 kW
I 12.6 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 101/115

(A) 12.591 12.591 12.591 0

Synthesis for all operating mode


(A) 12.591 12.591 12.591 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.664 0.112
UL1L2 (%) 1.921 0.129
UL2L3 (%) 1.921 0.129
UL3L1 (%) 1.921 0.129
UL1N (%) 1.664 0.112
UL2N (%) 1.664 0.112
UL3N (%) 1.664 0.112

Synthesis for all operating mode


U3L (%) 1.664
UL1L2 (%) 1.921
UL2L3 (%) 1.921
UL3L1 (%) 1.921
UL1N (%) 1.664
UL2N (%) 1.664
UL3N (%) 1.664

Project: T16-6081 06/08/2023


Page 102/115

3.3.26 Circuit Load 10 (3) (1) (1) (1)


Circuit breaker QA 10 (3) (1) (1) (1)
Ib 183 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX250B
Circuit breaker rating 250 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation Micrologic 5.2 E
Trip unit rating 250 A
Long delay settings
Ir 184 A
Tr 0.5 s
Short delay settings
Isd current 1840 A
Tsd 0.4 s
Instantaneous tripping
Ii current 3000 A
Ti current 50 s

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5bis (1) (1) (1) (1) (1) Total Selectivity
NSX630F
Micrologic 5.3 E
630 A / 4P4d

Cable WD 10 (3) (1) (1) (1)


Parameters
Length 10 m
Max length 99 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 103/115

Ib 183 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x95 mm²
Core Copper
Iz under real conditions 298 A
Iz’ 298 A
Selected neutral
Cross section area 1x50 mm²
Core Copper
Iz under real conditions 192 A
Iz’ 192 A
Selected PE
Cross section area 1x95 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 15.85 13.73 10.53 10.38 7.85 6.84 NA 7.92

Synthesis for all operating mode


(kA) 15.85 13.73 10.53 10.38 7.85 6.84 NA 7.92

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge UPP-FF-02
U 400 V
S 127 kVA
P 108 kW
I 183 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 104/115

(A) 183.309 183.309 183.309 0

Synthesis for all operating mode


(A) 183.309 183.309 183.309 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.754 0.202
UL1L2 (%) 2.025 0.233
UL2L3 (%) 2.025 0.233
UL3L1 (%) 2.025 0.233
UL1N (%) 1.754 0.202
UL2N (%) 1.754 0.202
UL3N (%) 1.754 0.202

Synthesis for all operating mode


U3L (%) 1.754
UL1L2 (%) 2.025
UL2L3 (%) 2.025
UL3L1 (%) 2.025
UL1N (%) 1.754
UL2N (%) 1.754
UL3N (%) 1.754

Project: T16-6081 06/08/2023


Page 105/115

3.3.27 Circuit Load 10 (4) (1) (1)


Circuit breaker QA 10 (4) (1) (1)
Ib 68.7 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 NG125
Designation NG125N
Circuit breaker rating 80 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 80 A
Long delay settings
Ir 80 A
Tr NA
Short delay settings
Isd current 640 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5bis (1) (1) (1) (1) (1) Total Selectivity
NSX630F
Micrologic 5.3 E
630 A / 4P4d

Cable WD 10 (4) (1) (1)


Parameters
Length 10 m
Max length 79 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 106/115

Ib 69 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x25 mm²
Core Copper
Iz under real conditions 127 A
Iz’ 127 A
Selected neutral
Cross section area 1x16 mm²
Core Copper
Iz under real conditions 100 A
Iz’ 100 A
Selected PE
Cross section area 1x25 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 13.30 11.52 7.48 8.41 5.30 5.16 NA 5.98

Synthesis for all operating mode


(kA) 13.30 11.52 7.48 8.41 5.30 5.16 NA 5.98

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge PP-FF-0.2
U 400 V
S 47.6 kVA
P 40.5 kW
I 68.7 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 107/115

(A) 68.705 68.705 68.705 0

Synthesis for all operating mode


(A) 68.705 68.705 68.705 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.804 0.252
UL1L2 (%) 2.083 0.291
UL2L3 (%) 2.083 0.291
UL3L1 (%) 2.083 0.291
UL1N (%) 1.804 0.252
UL2N (%) 1.804 0.252
UL3N (%) 1.804 0.252

Synthesis for all operating mode


U3L (%) 1.804
UL1L2 (%) 2.083
UL2L3 (%) 2.083
UL3L1 (%) 2.083
UL1N (%) 1.804
UL2N (%) 1.804
UL3N (%) 1.804

Project: T16-6081 06/08/2023


Page 108/115

3.3.28 Circuit Load 10 (2) (1) (1) (1)


Circuit breaker QA 10 (2) (1) (1) (1)
Ib 173 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX250B
Circuit breaker rating 250 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation Micrologic 5.2 E
Trip unit rating 250 A
Long delay settings
Ir 174 A
Tr 0.5 s
Short delay settings
Isd current 1740 A
Tsd 0.4 s
Instantaneous tripping
Ii current 3000 A
Ti current 50 s

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 5bis (1) (1) (1) (1) (1) Total Selectivity
NSX630F
Micrologic 5.3 E
630 A / 4P4d

Cable WD 10 (2) (1) (1) (1)


Parameters
Length 10 m
Max length 176 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: T16-6081 06/08/2023
Page 109/115

Ib 173 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x185 mm²
Core Copper
Iz under real conditions 456 A
Iz’ 456 A
Selected neutral
Cross section area 1x95 mm²
Core Copper
Iz under real conditions 298 A
Iz’ 298 A
Selected PE
Cross section area 1x185 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 16.26 14.08 11.25 10.71 8.52 7.18 NA 8.32

Synthesis for all operating mode


(kA) 16.26 14.08 11.25 10.71 8.52 7.18 NA 8.32

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge ACP-FF-22
U 400 V
S 120 kVA
P 102 kW
I 173 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: T16-6081 06/08/2023
Page 110/115

(A) 173.118 173.118 173.118 0

Synthesis for all operating mode


(A) 173.118 173.118 173.118 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.665 0.113
UL1L2 (%) 1.923 0.131
UL2L3 (%) 1.923 0.131
UL3L1 (%) 1.923 0.131
UL1N (%) 1.665 0.113
UL2N (%) 1.665 0.113
UL3N (%) 1.665 0.113

Synthesis for all operating mode


U3L (%) 1.665
UL1L2 (%) 1.923
UL2L3 (%) 1.923
UL3L1 (%) 1.923
UL1N (%) 1.665
UL2N (%) 1.665
UL3N (%) 1.665

Project: T16-6081 06/08/2023


Page 111/115

3.4 Busbar circuits


3.4.1 Circuit WC 2
Busbar WC 2
Parameters
Switchboard Name UC 3
Switchboard Range No preference
Rating (A) NA
IP Undefined
Feeder
Circuit name Protection name Protection type

Load 10 (4) (3) (1) (1) (1) QA 10 (4) (3) (1) (1) (1) NG125H
(2) (2) (1) (2) (2) (1)

Feeder circuit 5 (1) (1) QA 5 (1) (1) (1) (1) NSX630F


(1) (1)

Load 10 (4) (3) (1) (1) (1) QA 10 (4) (3) (1) (1) (1) NG125H
(2) (1) (2) (1)

Feeder circuit 5 (1) (1) QA 5 (1) (1) (2) (1) NSXm160F


(2) (1)

Feeder circuit 5 (1) (1) QA 5 (1) (1) (2) NSX630F


(2)

Load 10 (4) (3) (1) (1) (1) QA 10 (4) (3) (1) (1) (1) NSXm160F
(2) (2) (1) (1) (2) (2) (1) (1)

Feeder circuit 5 (1) (1) QA 5 (1) (1) (1) (1) (1) NSX630F
(1) (1) (1)

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 25.78 22.32 25.29 16.54 18.73 19.10 NA 22.12

Synthesis for all operating mode


(kA) 25.78 22.32 25.29 16.54 18.73 19.10 NA 22.12

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

3.4.2 Circuit WC 6 (1) (1) (2)


Busbar WC 6 (1) (1) (2)
Parameters
Switchboard Name UC 28
Switchboard Range No preference
Rating (A) NA
IP Undefined
Feeder
Project: T16-6081 06/08/2023
Page 112/115

Circuit name Protection name Protection type

Load 10 (4) (1) (2) QA 10 (4) (1) (2) NG125N

Load 10 (2) (1) (1) (2) QA 10 (2) (1) (1) (2) iC60L

Load 10 (1) (1) (1) (2) QA 10 (1) (1) (1) (2) iC60L

Load 10 (4) (3) (1) (1) (2) QA 10 (4) (3) (1) (1) (2) NG125N
(1) (1)

Load 10 (4) (3) (1) (2) (1) QA 10 (4) (3) (1) (2) (1) NG125N

Load 10 (4) (3) (1) (5) (2) QA 10 (4) (3) (1) (5) (2) NSX250B
(1) (1)

Load 10 (3) (1) (1) (2) QA 10 (3) (1) (1) (2) iC60L

Load 10 (4) (3) (1) (4) (2) QA 10 (4) (3) (1) (4) (2) iC60L
(1) (1)

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 18.49 16.01 12.91 12.15 9.65 8.77 NA 10.16

Synthesis for all operating mode


(kA) 18.49 16.01 12.91 12.15 9.65 8.77 NA 10.16

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

3.4.3 Circuit WC 6 (1) (1) (1) (1)


Busbar WC 6 (1) (1) (1) (1)
Parameters
Switchboard Name UC 7 (1) (1) (1) (1)
Switchboard Range No preference
Rating (A) NA
IP Undefined
Feeder
Circuit name Protection name Protection type

Load 10 (3) (1) (1) (1) (1) QA 10 (3) (1) (1) (1) (1) NSX250B

Load 10 (1) (1) (1) (1) (1) QA 10 (1) (1) (1) (1) (1) C120H

Load 10 (4) (1) (1) (1) QA 10 (4) (1) (1) (1) C120H

Load 10 (4) (2) (1) (1) (1) QA 10 (4) (2) (1) (1) (1) iC60H

Load 10 (2) (1) (1) (1) (1) QA 10 (2) (1) (1) (1) (1) C120H

Project: T16-6081 06/08/2023


Page 113/115

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 14.61 12.65 9.96 9.73 7.71 6.89 NA 7.98

Synthesis for all operating mode


(kA) 14.61 12.65 9.96 9.73 7.71 6.89 NA 7.98

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

3.4.4 Circuit WC 6 (1) (1) (2) (1)


Busbar WC 6 (1) (1) (2) (1)
Parameters
Switchboard Name UC 28 (1)
Switchboard Range No preference
Rating (A) NA
IP Undefined
Feeder
Circuit name Protection name Protection type

Load 10 (4) (1) (2) (1) (1) QA 10 (4) (1) (2) (1) (1) iC60L

Load 10 (3) (1) (1) (2) (1) QA 10 (3) (1) (1) (2) (1) iC60L

Load 10 (2) (1) (1) (2) (1) QA 10 (2) (1) (1) (2) (1) iC60L

Load 10 (4) (1) (2) (1) QA 10 (4) (1) (2) (1) iC60L

Load 10 (4) (3) (1) (1) (2) QA 10 (4) (3) (1) (1) (2) iC60L
(1) (1) (1) (1)

Load 10 (4) (3) (1) (4) (2) QA 10 (4) (3) (1) (4) (2) iC60L
(1) (1) (1) (1)

Load 10 (4) (3) (1) (2) (1) QA 10 (4) (3) (1) (2) (1) NG125N
(1) (1)

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 16.86 14.60 11.78 10.86 8.65 6.65 NA 7.70

Synthesis for all operating mode


(kA) 16.86 14.60 11.78 10.86 8.65 6.65 NA 7.70

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

3.4.5 Circuit WC 6 (1) (1) (1)


Busbar WC 6 (1) (1) (1)
Project: T16-6081 06/08/2023
Page 114/115

Parameters
Switchboard Name UC 7 (1) (1) (1)
Switchboard Range No preference
Rating (A) NA
IP Undefined
Feeder
Circuit name Protection name Protection type

Load 10 (3) (1) (1) (1) QA 10 (3) (1) (1) (1) NSX250B

Load 10 (1) (1) (1) (1) QA 10 (1) (1) (1) (1) NG125N

Load 10 (4) (1) (1) QA 10 (4) (1) (1) NG125N

Load 10 (4) (2) (1) (1) QA 10 (4) (2) (1) (1) iC60L

Load 10 (2) (1) (1) (1) QA 10 (2) (1) (1) (1) NSX250B

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 17.51 15.17 12.88 11.53 9.83 7.91 NA 9.16

Synthesis for all operating mode


(kA) 17.51 15.17 12.88 11.53 9.83 7.91 NA 9.16

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

</IF>

Project: T16-6081 06/08/2023


Page 115/115

NOTICE
RISK OF INACCURATE DATA RESULTS.

 Configure the software correctly to get accurate reports and/or data results.
 Do not rely solely on software messages and reports to determine if the
system is functioning correctly.
 Make sure that you have entered the correct inputs for the required
components.
 Review the calculated results and solutions provided by the software before
submitting the report.

Failure to follow these instructions can result in incorrect bill of material and
loss of business.

Project: T16-6081 06/08/2023