You are on page 1of 37

Installation calculation report

TR1
Full
Page 2/37

Project: TR1 13/07/2020


Page 3/37

Content

1 Project description.................................................................................................................. 4
1.1 Project general settings................................................................................................................... 4

1.2 Settings for wiring device calculation............................................................................................ 4

1.3 List of loads...................................................................................................................................... 4

2 Installation general design.....................................................................................................6


2.1 List of devices.................................................................................................................................. 6

3 Calculation notes.................................................................................................................. 14
3.1 Source circuits............................................................................................................................... 14

3.2 Generator circuits.......................................................................................................................... 23

3.3 LV Source circuits.......................................................................................................................... 23

3.4 UPS circuits.................................................................................................................................... 23

3.5 Surge Arrester circuits.................................................................................................................. 24

3.6 Capacitor bank circuits.................................................................................................................. 24

3.7 Feeder circuits................................................................................................................................ 24

3.8 LV Transformer circuits................................................................................................................. 26

3.9 Couplers circuits............................................................................................................................ 27

3.10 Generic load circuits................................................................................................................. 28

3.11 Lighting load circuits................................................................................................................ 28

3.12 Power socket load circuits....................................................................................................... 29

3.13 Motor starter combination........................................................................................................ 29

3.14 Busbar circuits.......................................................................................................................... 30

3.15 Busbar trunking system circuits............................................................................................. 30

3.16 Busbar trunking system circuits............................................................................................. 30

3.17 Lighting Busbar trunking system circuits..............................................................................30

Project: TR1 13/07/2020


Page 4/37

1 Project description
1.1 Project general settings
Installation standard IEC60364

Calculation standard TR50480


Circuit breaker standard IEC 60947-2
Frequency 50 Hz

1.2 Settings for wiring device calculation


Maximal CSA 300 mm²

1.3 List of loads


1.3.1 Generic loads
Name Sr (kVA) Pr (kW) Ir (A) Cos Nbr Polarity Non linear load THDi 3 (%)
DP1 154 131 222 0.85 1 3Ph+N No 0
DP2 134 114 193 0.85 1 3Ph+N No 0
DP3 145 123 209 0.85 1 3Ph+N No 0
DP- 90 76.5 130 0.85 1 3Ph+N No 0
BANK
DP- 110 93.5 159 0.85 1 3Ph+N No 0
MALL1
DP- 110 93.5 159 0.85 1 3Ph+N No 0
MALL2
DP- 110 93.5 159 0.85 1 3Ph+N No 0
MALL3
DP- 80 68 115 0.85 1 3Ph+N No 0
LANDSC
APE

Project: TR1 13/07/2020


Page 5/37

2 Installation general design


2.1 List of devices
2.1.1 MV/LV transformer
Name Nbr Range Insulation Sr (kVA) ukrT (%) Connection U2 (V) SEA Rb (m)
TR1 1 Trihal Resin 1000 6 D 420 TN-C 10000

2.1.2 LV switchboards and busbar


Switchboard name Range Rating (A) IP
MDB-TR1 Okken 1680.00 IP54

Busbar name Switchboard Ks Polarity SEA Equipotential bounding


name
WC 1 MDB-TR1 0.7 3Ph+N TN-C With

2.1.3 Circuit breaker


Name Nbr Range - Rating (A) Poles Trip unit/Curve RCD RCD class
Designation
QA 0 1 Masterpact 2000 3P3d Micrologic 5.0 X
MTZ2 -
MTZ2 20H1
MCCB1 1 Compact 400 3P3d Micrologic 2.3
NSX -
NSX400F
QA 6 1 Compact 630 3P3d Micrologic 2.3
NSX -
NSX630N
MCCB8 1 Compact 400 3P3d Micrologic 2.3
NSX -
NSX400F
MCCB7 1 Compact 400 3P3d Micrologic 2.3
NSX -
NSX400F
MCCB6 1 Compact 400 3P3d Micrologic 2.3
NSX -
NSX400F
MCCB5 1 Compact 400 3P3d Micrologic 2.3
NSX -
NSX400F
MCCB4 1 Compact 400 3P3d Micrologic 2.3
NSX -
NSX400F
MCCB3 1 Compact 400 3P3d Micrologic 2.3
NSX -
NSX400N
MCCB2 1 Compact 250 3P3d Micrologic 2.2
NSX -
NSX250N

2.1.4 Transmission busbar trunking system schedule


Name Nbr Incomer Feeder L (m) Range Rating (A)
WD 0 1 TR1 QA 0 20 KTA 2000
WD 6 1 QA 6 CA 6 5 KSA 630

Project: TR1 13/07/2020


Page 6/37

2.1.5 Cable schedule


Name Nbr Incomer Feeder Type Insulation L (m) L1/L2/L3 N PE/PEN
FEED 1 MCCB6 DP- Multi-core XLPE 350 1x300 1x150
ER6 BANK Aluminium Aluminium
FEED 1 MCCB5 DP- Multi-core XLPE 280 1x300 1x150
ER5 MALL1 Aluminium Aluminium
FEED 1 MCCB8 DP2 Multi-core XLPE 240 1x300 1x150
ER8 Aluminium Aluminium
FEED 1 MCCB2 DP- Multi-core XLPE 220 1x150 1x95
ER2 LANDS Aluminium Aluminium
CAPE
FEED 1 MCCB4 DP- Multi-core XLPE 190 1x300 1x150
ER4 MALL2 Aluminium Aluminium
FEED 1 MCCB1 DP1 Multi-core XLPE 160 1x300 1x150
ER1 Aluminium Aluminium
FEED 1 MCCB3 DP- Multi-core XLPE 145 1x300 1x150
ER3 MALL3 Aluminium Aluminium
FEED 1 MCCB7 DP3 Multi-core XLPE 80 1x300 1x150
ER7 Aluminium Aluminium

2.1.6 MV Cable
Name Nbr Designation CSA (mm²) Icc (A) In (A) Un (kV)
MVWD 1 NA 1 x 240 Al 21.3 418 24
0

Project: TR1 13/07/2020


Page 7/37

3 Calculation notes

3.1 Source circuits


3.1.1 Circuit Source 0
MV power supply W0
Max. upstream short circuit power 750 MVA
Min. upstream short circuit power 250 MVA
MV Cable MVWD 0
Parameters
Length 10 m
Type of cable Multi core
Ib 26 A
Nb of conductor per phase 1
Cross section area 1 x 240 Al mm²
Core Aluminium
Short circuit withstand 21.3 kA
Assigned voltage 22 kV
Insulation voltage 24 kV

MV/LV transformer TR1


Range Trihal
Technology Resin
Rated power 1000 kVA
ukrT 6%
Type of losses AoAk
PkrT 9 kW
System earthing arrangement TN-C
MV Connection D
LV Connection yn
No load secondary voltage Ur0 420V
Ur LV 400V
Rb (neutral grounding) NA
Ra (mass grounding) NA
Sizing information UkrT and PkrT calculated by system
Transmission busway WD 0
Parameters
Length 20 m
Max length NA
Installation method Standard
Ambient temperature 35 °C
Level of third harmonic THDI NA %
Ib 1443 A
Sizing Information Sized with Ir
Correction factors
Temperature factor NA
Installation method factor NA
Type of protection factor NA
User defined factor 1
Selected busway
Designation KTA2000
Rating 2000
PE type Standard PE
IP 55
IK 08
Core Aluminium
Icw 4900 kA
Ip 154 kA
Project: TR1 13/07/2020
Page 8/37

Reinforced short circuit NA


withstand

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 22.74 19.69 22.08 16.12 18.01 18.01 NA 20.86

Synthesis for all operating mode


(kA) 22.74 19.69 22.08 16.12 18.01 18.01 NA 20.86

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Circuit breaker QA 0
Ib 1443 A
Distance from origin NA

Sizing Information Sized by system


Range Masterpact MTZ2
Designation MTZ2 20H1
Circuit breaker rating 2000 A
Breaking capacity 66 kA
TNS One pole breaking capacity 66 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation Micrologic 5.0 X
Trip unit rating 2000 A
Long delay settings
Ir 1500 (Setting: 0.75) A
Tr 24 s
Short delay settings
Isd current 12000 A
Tsd 0.4 s
Instantaneous tripping
Ii current 20000 (Setting: 10) A
Ti current 0.05 A

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


NA Selectivity can't be determinated : no
upstream Lv Breaker

<TEMPLATE report="TEMPLATEFILE=HazardWarningMessage.doc" />


<TEMPLATE <TEMPLATE
report="TEMPLATEFILE=Haz report="TEMPLATEFILE=HazardWarni
ardWarningMessage.doc" />M ngMessage.doc" />
odular Contactor
Modular Contactor Rating <TEMPLATE
report="TEMPLATEFILE=HazardWarning
Message.doc" />
Project: TR1 13/07/2020
Page 9/37

Modular Contactor Poles <TEMPLATE


report="TEMPLATEFILE=HazardWarning
Message.doc" />
<TEMPLATE report="TEMPLATEFILE=HazardWarningMessage.doc" />

Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 942.669 942.669 942.669 0

Synthesis for all operating mode


(A) 942.669 942.669 942.669 NA

Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.430 0.430
UL1L2 (%) 0.497 0.497
UL2L3 (%) 0.497 0.497
UL3L1 (%) 0.497 0.497
UL1N (%) 0.430 0.430
UL2N (%) 0.430 0.430
UL3N (%) 0.430 0.430

3.2 Capacitor bank circuits


3.2.1 Circuit Capacitors 6
Circuit breaker QA 6
Ib 253 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX630N
Circuit breaker rating 630 A
Breaking capacity 50 kA
TNS One pole breaking capacity 50 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation Micrologic 2.3
Trip unit rating 630 A
Long delay settings
Ir 346 A
Tr 16 s
Short delay settings
Isd current 3456 A
Tsd 0.02 s
Instantaneous tripping
Ii current 6900 A
Ti current 60 A

Project: TR1 13/07/2020


Page 10/37

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 0 Total Selectivity
MTZ2 20H1
Micrologic 5.0 X
2000 A / 3P3d

<TEMPLATE report="TEMPLATEFILE=HazardWarningMessage.doc" />


<TEMPLATE <TEMPLATE
report="TEMPLATEFILE=Haz report="TEMPLATEFILE=HazardWarni
ardWarningMessage.doc" />M ngMessage.doc" />
odular Contactor
Modular Contactor Rating <TEMPLATE
report="TEMPLATEFILE=HazardWarning
Message.doc" />
Modular Contactor Poles <TEMPLATE
report="TEMPLATEFILE=HazardWarning
Message.doc" />
<TEMPLATE report="TEMPLATEFILE=HazardWarningMessage.doc" />

Transmission busway WD 6
Parameters
Length 5m
Max length 242 m
Installation method Standard
Ambient temperature 35 °C
Level of third harmonic THDI NA %
Ib 253 A
Sizing Information Sized with Ir
Correction factors
Temperature factor NA
Installation method factor NA
Type of protection factor NA
User defined factor 1
Selected busway
Designation KSA630
Rating 630
PE type Standard PE
IP 55
IK 08
Core Aluminium
Icw 1225 kA
Ip 67.5 kA
Reinforced short circuit NA
withstand

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 22.74 19.69 0.00 16.15 0.00 18.07 0.00 20.92

Project: TR1 13/07/2020


Page 11/37

Synthesis for all operating mode


(kA) NA NA NA NA NA NA NA NA

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

LV capacitor bank CA 6
Target P.F. 0.92
Downstream reactive power to 108 kvar
correct
Upstream reactive power to 50 kvar
correct
Range of the capacitor bank VarSet
Designation of the capacitor bank NA
Qr of the capacitor bank 175 kvar
Step 25+3x50
Accord N/A
U 400 V
Frequency 50 Hz
Pollution Gh/Sn NA %
Type of correction No Polluted
P.F. after correction 0.930

Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 252.591 252.591 252.591 0

Synthesis for all operating mode


(A) 252.591 252.591 252.591 NA

Project: TR1 13/07/2020


Page 12/37

Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.430 0.000
UL1L2 (%) 0.497 0.000
UL2L3 (%) 0.497 0.000
UL3L1 (%) 0.497 0.000
UL1N (%) 0.430 0.000
UL2N (%) 0.430 0.000
UL3N (%) 0.430 0.000

3.3 Generic load circuits

3.3.1 Circuit LOAD1


Circuit breaker MCCB1
Ib 222 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX400F
Circuit breaker rating 400 A
Breaking capacity 36 kA
TNS One pole breaking capacity 36 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation Micrologic 2.3
Trip unit rating 400 A
Long delay settings
Ir 223 A
Tr 16 s
Short delay settings
Isd current 1785 A
Tsd 0.02 s
Instantaneous tripping
Ii current 4800 A
Ti current 60 A

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 0 Total Selectivity
MTZ2 20H1
Micrologic 5.0 X
2000 A / 3P3d

<TEMPLATE report="TEMPLATEFILE=HazardWarningMessage.doc" />


<TEMPLATE <TEMPLATE

Project: TR1 13/07/2020


Page 13/37

report="TEMPLATEFILE=Haz report="TEMPLATEFILE=HazardWarni
ardWarningMessage.doc" />M ngMessage.doc" />
odular Contactor
Modular Contactor Rating <TEMPLATE
report="TEMPLATEFILE=HazardWarning
Message.doc" />
Modular Contactor Poles <TEMPLATE
report="TEMPLATEFILE=HazardWarning
Message.doc" />
<TEMPLATE report="TEMPLATEFILE=HazardWarningMessage.doc" />

Cable FEEDER1
Parameters
Length 160 m
Installation method 70
D1
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 222 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-19
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x300 mm²
Core Aluminium
Iz under real conditions 286 A
Iz’ 286 A
Selected PEN
Cross section area 1x150 mm²
Core Aluminium

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 8.52 7.38 4.11 5.69 2.98 2.98 NA 3.45

Synthesis for all operating mode


(kA) 8.52 7.38 4.11 5.69 2.98 2.98 NA 3.45

Project: TR1 13/07/2020


Page 14/37

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge DP1
U 400 V
S 154 kVA
P 131 kW
I 222 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 222.280 222.280 222.280 0

Synthesis for all operating mode


(A) 222.280 222.280 222.280 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 2.722 2.292
UL1L2 (%) 3.143 2.646
UL2L3 (%) 3.143 2.646
UL3L1 (%) 3.143 2.646
UL1N (%) 2.722 2.292
UL2N (%) 2.722 2.292
UL3N (%) 2.722 2.292

Synthesis for all operating mode


U3L (%) 2.722
UL1L2 (%) 3.143
UL2L3 (%) 3.143
UL3L1 (%) 3.143
UL1N (%) 2.722
UL2N (%) 2.722
UL3N (%) 2.722

Project: TR1 13/07/2020


Page 15/37

3.3.2 Circuit LOAD8


Circuit breaker MCCB8
Ib 193 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX400F
Circuit breaker rating 400 A
Breaking capacity 36 kA
TNS One pole breaking capacity 36 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation Micrologic 2.3
Trip unit rating 400 A
Long delay settings
Ir 194 A
Tr 16 s
Short delay settings
Isd current 1358 A
Tsd 0.02 s
Instantaneous tripping
Ii current 4800 A
Ti current 60 A

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 0 Total Selectivity
MTZ2 20H1
Micrologic 5.0 X
2000 A / 3P3d

<TEMPLATE report="TEMPLATEFILE=HazardWarningMessage.doc" />


<TEMPLATE <TEMPLATE
report="TEMPLATEFILE=Haz report="TEMPLATEFILE=HazardWarni
ardWarningMessage.doc" />M ngMessage.doc" />
odular Contactor
Modular Contactor Rating <TEMPLATE
report="TEMPLATEFILE=HazardWarning
Message.doc" />
Modular Contactor Poles <TEMPLATE
report="TEMPLATEFILE=HazardWarning
Message.doc" />
<TEMPLATE report="TEMPLATEFILE=HazardWarningMessage.doc" />

Cable FEEDER8
Parameters
Length 240 m
Installation method 70
D1
Project: TR1 13/07/2020
Page 16/37

Multi-core cable in conduit or in cable


ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 193 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-19
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x300 mm²
Core Aluminium
Iz under real conditions 286 A
Iz’ 286 A
Selected PEN
Cross section area 1x150 mm²
Core Aluminium

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 6.39 5.54 2.87 4.22 2.06 2.06 NA 2.39

Synthesis for all operating mode


(kA) 6.39 5.54 2.87 4.22 2.06 2.06 NA 2.39

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge DP2
U 400 V
S 134 kVA
P 114 kW
I 193 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Project: TR1 13/07/2020
Page 17/37

Operating mode Normal


(A) 193.412 193.412 193.412 0

Synthesis for all operating mode


(A) 193.412 193.412 193.412 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 3.421 2.991
UL1L2 (%) 3.950 3.454
UL2L3 (%) 3.950 3.454
UL3L1 (%) 3.950 3.454
UL1N (%) 3.421 2.991
UL2N (%) 3.421 2.991
UL3N (%) 3.421 2.991

Synthesis for all operating mode


U3L (%) 3.421
UL1L2 (%) 3.950
UL2L3 (%) 3.950
UL3L1 (%) 3.950
UL1N (%) 3.421
UL2N (%) 3.421
UL3N (%) 3.421

Project: TR1 13/07/2020


Page 18/37

3.3.3 Circuit LOAD7


Circuit breaker MCCB7
Ib 209 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX400F
Circuit breaker rating 400 A
Breaking capacity 36 kA
TNS One pole breaking capacity 36 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation Micrologic 2.3
Trip unit rating 400 A
Long delay settings
Ir 212 A
Tr 16 s
Short delay settings
Isd current 2116 A
Tsd 0.02 s
Instantaneous tripping
Ii current 4800 A
Ti current 60 A

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 0 Total Selectivity
MTZ2 20H1
Micrologic 5.0 X
2000 A / 3P3d

<TEMPLATE report="TEMPLATEFILE=HazardWarningMessage.doc" />


<TEMPLATE <TEMPLATE
report="TEMPLATEFILE=Haz report="TEMPLATEFILE=HazardWarni
ardWarningMessage.doc" />M ngMessage.doc" />
odular Contactor
Modular Contactor Rating <TEMPLATE
report="TEMPLATEFILE=HazardWarning
Message.doc" />
Modular Contactor Poles <TEMPLATE
report="TEMPLATEFILE=HazardWarning
Message.doc" />
<TEMPLATE report="TEMPLATEFILE=HazardWarningMessage.doc" />

Cable FEEDER7
Parameters
Length 80 m
Installation method 70
D1
Project: TR1 13/07/2020
Page 19/37

Multi-core cable in conduit or in cable


ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 209 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-19
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x300 mm²
Core Aluminium
Iz under real conditions 286 A
Iz’ 286 A
Selected PEN
Cross section area 1x150 mm²
Core Aluminium

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 12.63 10.94 7.15 8.62 5.29 5.29 NA 6.12

Synthesis for all operating mode


(kA) 12.63 10.94 7.15 8.62 5.29 5.29 NA 6.12

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge DP3
U 400 V
S 145 kVA
P 123 kW
I 209 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Project: TR1 13/07/2020
Page 20/37

Operating mode Normal


(A) 209.289 209.289 209.289 0

Synthesis for all operating mode


(A) 209.289 209.289 209.289 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.509 1.079
UL1L2 (%) 1.742 1.246
UL2L3 (%) 1.742 1.246
UL3L1 (%) 1.742 1.246
UL1N (%) 1.509 1.079
UL2N (%) 1.509 1.079
UL3N (%) 1.509 1.079

Synthesis for all operating mode


U3L (%) 1.509
UL1L2 (%) 1.742
UL2L3 (%) 1.742
UL3L1 (%) 1.742
UL1N (%) 1.509
UL2N (%) 1.509
UL3N (%) 1.509

Project: TR1 13/07/2020


Page 21/37

3.3.4 Circuit LOAD6


Circuit breaker MCCB6
Ib 130 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX400F
Circuit breaker rating 400 A
Breaking capacity 36 kA
TNS One pole breaking capacity 36 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation Micrologic 2.3
Trip unit rating 400 A
Long delay settings
Ir 144 A
Tr 16 s
Short delay settings
Isd current 1008 A
Tsd 0.02 s
Instantaneous tripping
Ii current 4800 A
Ti current 60 A

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 0 Total Selectivity
MTZ2 20H1
Micrologic 5.0 X
2000 A / 3P3d

<TEMPLATE report="TEMPLATEFILE=HazardWarningMessage.doc" />


<TEMPLATE <TEMPLATE
report="TEMPLATEFILE=Haz report="TEMPLATEFILE=HazardWarni
ardWarningMessage.doc" />M ngMessage.doc" />
odular Contactor
Modular Contactor Rating <TEMPLATE
report="TEMPLATEFILE=HazardWarning
Message.doc" />
Modular Contactor Poles <TEMPLATE
report="TEMPLATEFILE=HazardWarning
Message.doc" />
<TEMPLATE report="TEMPLATEFILE=HazardWarningMessage.doc" />

Cable FEEDER6
Parameters
Length 350 m
Installation method 70
D1
Project: TR1 13/07/2020
Page 22/37

Multi-core cable in conduit or in cable


ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 130 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-19
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x300 mm²
Core Aluminium
Iz under real conditions 286 A
Iz’ 286 A
Selected PEN
Cross section area 1x150 mm²
Core Aluminium

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 4.75 4.11 2.03 3.10 1.45 1.45 NA 1.68

Synthesis for all operating mode


(kA) 4.75 4.11 2.03 3.10 1.45 1.45 NA 1.68

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge DP-BANK
U 400 V
S 90 kVA
P 76.5 kW
I 130 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Project: TR1 13/07/2020
Page 23/37

Operating mode Normal


(A) 129.904 129.904 129.904 0

Synthesis for all operating mode


(A) 129.904 129.904 129.904 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 3.360 2.930
UL1L2 (%) 3.879 3.383
UL2L3 (%) 3.879 3.383
UL3L1 (%) 3.879 3.383
UL1N (%) 3.360 2.930
UL2N (%) 3.360 2.930
UL3N (%) 3.360 2.930

Synthesis for all operating mode


U3L (%) 3.360
UL1L2 (%) 3.879
UL2L3 (%) 3.879
UL3L1 (%) 3.879
UL1N (%) 3.360
UL2N (%) 3.360
UL3N (%) 3.360

Project: TR1 13/07/2020


Page 24/37

3.3.5 Circuit LOAD5


Circuit breaker MCCB5
Ib 159 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX400F
Circuit breaker rating 400 A
Breaking capacity 36 kA
TNS One pole breaking capacity 36 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation Micrologic 2.3
Trip unit rating 400 A
Long delay settings
Ir 160 A
Tr 16 s
Short delay settings
Isd current 1280 A
Tsd 0.02 s
Instantaneous tripping
Ii current 4800 A
Ti current 60 A

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 0 Total Selectivity
MTZ2 20H1
Micrologic 5.0 X
2000 A / 3P3d

<TEMPLATE report="TEMPLATEFILE=HazardWarningMessage.doc" />


<TEMPLATE <TEMPLATE
report="TEMPLATEFILE=Haz report="TEMPLATEFILE=HazardWarni
ardWarningMessage.doc" />M ngMessage.doc" />
odular Contactor
Modular Contactor Rating <TEMPLATE
report="TEMPLATEFILE=HazardWarning
Message.doc" />
Modular Contactor Poles <TEMPLATE
report="TEMPLATEFILE=HazardWarning
Message.doc" />
<TEMPLATE report="TEMPLATEFILE=HazardWarningMessage.doc" />

Cable FEEDER5
Parameters
Length 280 m
Installation method 70
D1
Project: TR1 13/07/2020
Page 25/37

Multi-core cable in conduit or in cable


ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 159 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-19
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x300 mm²
Core Aluminium
Iz under real conditions 286 A
Iz’ 286 A
Selected PEN
Cross section area 1x150 mm²
Core Aluminium

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 5.68 4.92 2.50 3.73 1.79 1.79 NA 2.07

Synthesis for all operating mode


(kA) 5.68 4.92 2.50 3.73 1.79 1.79 NA 2.07

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge DP-MALL1
U 400 V
S 110 kVA
P 93.5 kW
I 159 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Project: TR1 13/07/2020
Page 26/37

Operating mode Normal


(A) 158.771 158.771 158.771 0

Synthesis for all operating mode


(A) 158.771 158.771 158.771 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 3.295 2.864
UL1L2 (%) 3.804 3.308
UL2L3 (%) 3.804 3.308
UL3L1 (%) 3.804 3.308
UL1N (%) 3.295 2.864
UL2N (%) 3.295 2.864
UL3N (%) 3.295 2.864

Synthesis for all operating mode


U3L (%) 3.295
UL1L2 (%) 3.804
UL2L3 (%) 3.804
UL3L1 (%) 3.804
UL1N (%) 3.295
UL2N (%) 3.295
UL3N (%) 3.295

Project: TR1 13/07/2020


Page 27/37

3.3.6 Circuit LOAD4


Circuit breaker MCCB4
Ib 159 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX400F
Circuit breaker rating 400 A
Breaking capacity 36 kA
TNS One pole breaking capacity 36 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation Micrologic 2.3
Trip unit rating 400 A
Long delay settings
Ir 160 A
Tr 16 s
Short delay settings
Isd current 1600 A
Tsd 0.02 s
Instantaneous tripping
Ii current 4800 A
Ti current 60 A

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 0 Total Selectivity
MTZ2 20H1
Micrologic 5.0 X
2000 A / 3P3d

<TEMPLATE report="TEMPLATEFILE=HazardWarningMessage.doc" />


<TEMPLATE <TEMPLATE
report="TEMPLATEFILE=Haz report="TEMPLATEFILE=HazardWarni
ardWarningMessage.doc" />M ngMessage.doc" />
odular Contactor
Modular Contactor Rating <TEMPLATE
report="TEMPLATEFILE=HazardWarning
Message.doc" />
Modular Contactor Poles <TEMPLATE
report="TEMPLATEFILE=HazardWarning
Message.doc" />
<TEMPLATE report="TEMPLATEFILE=HazardWarningMessage.doc" />

Cable FEEDER4
Parameters
Length 190 m
Installation method 70
D1
Project: TR1 13/07/2020
Page 28/37

Multi-core cable in conduit or in cable


ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 159 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-19
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x300 mm²
Core Aluminium
Iz under real conditions 286 A
Iz’ 286 A
Selected PEN
Cross section area 1x150 mm²
Core Aluminium

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 7.58 6.56 3.54 5.03 2.55 2.55 NA 2.96

Synthesis for all operating mode


(kA) 7.58 6.56 3.54 5.03 2.55 2.55 NA 2.96

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge DP-MALL2
U 400 V
S 110 kVA
P 93.5 kW
I 159 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Project: TR1 13/07/2020
Page 29/37

Operating mode Normal


(A) 158.771 158.771 158.771 0

Synthesis for all operating mode


(A) 158.771 158.771 158.771 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 2.374 1.944
UL1L2 (%) 2.741 2.244
UL2L3 (%) 2.741 2.244
UL3L1 (%) 2.741 2.244
UL1N (%) 2.374 1.944
UL2N (%) 2.374 1.944
UL3N (%) 2.374 1.944

Synthesis for all operating mode


U3L (%) 2.374
UL1L2 (%) 2.741
UL2L3 (%) 2.741
UL3L1 (%) 2.741
UL1N (%) 2.374
UL2N (%) 2.374
UL3N (%) 2.374

Project: TR1 13/07/2020


Page 30/37

3.3.7 Circuit LOAD3


Circuit breaker MCCB3
Ib 159 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX400N
Circuit breaker rating 400 A
Breaking capacity 50 kA
TNS One pole breaking capacity 50 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation Micrologic 2.3
Trip unit rating 400 A
Long delay settings
Ir 160 A
Tr 16 s
Short delay settings
Isd current 1600 A
Tsd 0.02 s
Instantaneous tripping
Ii current 4800 A
Ti current 60 A

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 0 Total Selectivity
MTZ2 20H1
Micrologic 5.0 X
2000 A / 3P3d

<TEMPLATE report="TEMPLATEFILE=HazardWarningMessage.doc" />


<TEMPLATE <TEMPLATE
report="TEMPLATEFILE=Haz report="TEMPLATEFILE=HazardWarni
ardWarningMessage.doc" />M ngMessage.doc" />
odular Contactor
Modular Contactor Rating <TEMPLATE
report="TEMPLATEFILE=HazardWarning
Message.doc" />
Modular Contactor Poles <TEMPLATE
report="TEMPLATEFILE=HazardWarning
Message.doc" />
<TEMPLATE report="TEMPLATEFILE=HazardWarningMessage.doc" />

Cable FEEDER3
Parameters
Length 145 m
Installation method 70
D1
Project: TR1 13/07/2020
Page 31/37

Multi-core cable in conduit or in cable


ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 159 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-19
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x300 mm²
Core Aluminium
Iz under real conditions 286 A
Iz’ 286 A
Selected PEN
Cross section area 1x150 mm²
Core Aluminium

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 9.08 7.87 4.46 6.08 3.24 3.24 NA 3.76

Synthesis for all operating mode


(kA) 9.08 7.87 4.46 6.08 3.24 3.24 NA 3.76

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge DP-MALL3
U 400 V
S 110 kVA
P 93.5 kW
I 159 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Project: TR1 13/07/2020
Page 32/37

Operating mode Normal


(A) 158.771 158.771 158.771 0

Synthesis for all operating mode


(A) 158.771 158.771 158.771 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.913 1.483
UL1L2 (%) 2.210 1.713
UL2L3 (%) 2.210 1.713
UL3L1 (%) 2.210 1.713
UL1N (%) 1.913 1.483
UL2N (%) 1.913 1.483
UL3N (%) 1.913 1.483

Synthesis for all operating mode


U3L (%) 1.913
UL1L2 (%) 2.210
UL2L3 (%) 2.210
UL3L1 (%) 2.210
UL1N (%) 1.913
UL2N (%) 1.913
UL3N (%) 1.913

Project: TR1 13/07/2020


Page 33/37

3.3.8 Circuit LOAD2


Circuit breaker MCCB2
Ib 115 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX250N
Circuit breaker rating 250 A
Breaking capacity 50 kA
TNS One pole breaking capacity 50 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation Micrologic 2.2
Trip unit rating 250 A
Long delay settings
Ir 116 A
Tr 16 s
Short delay settings
Isd current 930 A
Tsd 0.02 s
Instantaneous tripping
Ii current 3000 A
Ti current 60 A

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 0 Total Selectivity
MTZ2 20H1
Micrologic 5.0 X
2000 A / 3P3d

<TEMPLATE report="TEMPLATEFILE=HazardWarningMessage.doc" />


<TEMPLATE <TEMPLATE
report="TEMPLATEFILE=Haz report="TEMPLATEFILE=HazardWarni
ardWarningMessage.doc" />M ngMessage.doc" />
odular Contactor
Modular Contactor Rating <TEMPLATE
report="TEMPLATEFILE=HazardWarning
Message.doc" />
Modular Contactor Poles <TEMPLATE
report="TEMPLATEFILE=HazardWarning
Message.doc" />
<TEMPLATE report="TEMPLATEFILE=HazardWarningMessage.doc" />

Cable FEEDER2
Parameters
Length 220 m
Installation method 70
D1
Project: TR1 13/07/2020
Page 34/37

Multi-core cable in conduit or in cable


ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 115 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-19
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x150 mm²
Core Aluminium
Iz under real conditions 197 A
Iz’ 197 A
Selected PEN
Cross section area 1x95 mm²
Core Aluminium

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 4.73 4.10 2.07 2.92 1.43 1.43 NA 1.66

Synthesis for all operating mode


(kA) 4.73 4.10 2.07 2.92 1.43 1.43 NA 1.66

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge DP-LANDSCAPE
U 400 V
S 80 kVA
P 68 kW
I 115 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Project: TR1 13/07/2020
Page 35/37

Operating mode Normal


(A) 115.470 115.470 115.470 0

Synthesis for all operating mode


(A) 115.470 115.470 115.470 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 3.240 2.810
UL1L2 (%) 3.741 3.245
UL2L3 (%) 3.741 3.245
UL3L1 (%) 3.741 3.245
UL1N (%) 3.240 2.810
UL2N (%) 3.240 2.810
UL3N (%) 3.240 2.810

Synthesis for all operating mode


U3L (%) 3.240
UL1L2 (%) 3.741
UL2L3 (%) 3.741
UL3L1 (%) 3.741
UL1N (%) 3.240
UL2N (%) 3.240
UL3N (%) 3.240

Project: TR1 13/07/2020


Page 36/37

3.4 Busbar circuits


3.4.1 Circuit WC 1
Busbar WC 1
Parameters
Switchboard Name MDB-TR1
Switchboard Range Okken
Rating (A) 1680
IP IP54
Feeder
Circuit name Protection name Protection type

LOAD1 MCCB1 NSX400F

Capacitors 6 QA 6 NSX630N

LOAD8 MCCB8 NSX400F

LOAD7 MCCB7 NSX400F

LOAD6 MCCB6 NSX400F

LOAD5 MCCB5 NSX400F

LOAD4 MCCB4 NSX400F

LOAD3 MCCB3 NSX400N

LOAD2 MCCB2 NSX250N

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 22.74 19.69 22.08 16.15 18.07 18.07 NA 20.92

Synthesis for all operating mode


(kA) 22.74 19.69 22.08 16.15 18.07 18.07 NA 20.92

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Project: TR1 13/07/2020


Page 37/37

NOTICE
RISK OF INACCURATE DATA RESULTS.

 Configure the software correctly to get accurate reports and/or


data results.
 Do not rely solely on software messages and reports to determine
if the system is functioning correctly.
 Make sure that you have entered the correct inputs for the required
components.
 Review the calculated results and solutions provided by the
software before submitting the report.
Failure to follow these instructions can result in incorrect bill of
material and loss of business.

Project: TR1 13/07/2020

You might also like