bài 1
Full
Page 2/45
Content
1 Project description.................................................................................................................. 4
1.1 Project general settings................................................................................................................... 4
3 Calculation notes.................................................................................................................. 14
3.1 Source circuits............................................................................................................................... 14
1 Project description
1.1 Project general settings
Installation standard IEC60364
NSX100F
QA 14 2 Compact 100 3P3d Micrologic 2.2 M
NSX -
NSX100F
QA 15 3 Acti9 P25M - 23 3P3d M
P25M
QA 16 3 Acti9 iC60 - 10 4P4d C Vigi iC60 A
iC60H
QA 18 1 Acti9 iC60 - 13 4P4d C
iC60L
QA 18bis 1 Acti9 iDPN - 13 4P3d C
iDPN.N
QA 22 10 Acti9 iC60 - 1.6 4P4d C
iC60L
NOTICE
RISK OF INACCURATE DATA RESULTS
Make sure that you have provided all the required inputs for the conductor sizing.
It is recommended to refer to the cable manufacturer's catalogue before making
the selection.
Failure to follow these instructions can result in incorrect bill of material and loss
of business.
2.1.5 MV Cable
Name Nbr Designation CSA (mm²) Icc (A) In (A) Un (kV)
MVWD 1 NA 1 x 240 Al 21.3 418 24
0
3 Calculation notes
MV/LV transformer TA 0
Range Trihal
Technology Resin
Rated power 400 kVA
ukrT 4%
Type of losses AoAk
PkrT 4.5 kW
System earthing arrangement TN-S
MV Connection D
LV Connection yn
No load secondary voltage Ur0 420V
Ur LV 400V
Rb (neutral grounding) NA
Ra (mass grounding) NA
Sizing information UkrT and PkrT calculated by system
Cable WD 0
Parameters
Length 15 m
Installation method 70
D1
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 577 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.85
Project: bài 1 25/09/2021
Page 9/45
Selected phase
Cross section area 2x300 mm²
Core Copper
Iz under real conditions 620 A
Iz’ 730 A
Selected neutral
Cross section area 2x300 mm²
Core Copper
Iz under real conditions 620 A
Iz’ 730 A
Selected PE
Cross section area 2x150 mm²
Core Copper
Circuit breaker QA 0
Ib 577 A
Distance from origin NA
Selectivity Results
UpStream Selectivity Limit
Design current
IL1 IL2 IL3 IN
Ii current 4800 A
Ti current 60 A
Selectivity Results
UpStream Selectivity Limit
Cable WD 3
Parameters
Length 11 m
Installation method 70
D1
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 290 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-19
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x240 mm²
Core Copper
Iz under real conditions 324 A
Iz’ 324 A
Selected neutral
Cross section area 1x240 mm²
Core Copper
Iz under real conditions 324 A
Iz’ 324 A
Selected PE
Cross section area 1x120 mm²
Core Copper
Selectivity Results
UpStream Selectivity Limit
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Cable WD 10
Parameters
Length 10 m
Installation method 70
D1
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 178 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Project: bài 1 25/09/2021
Page 15/45
Selected phase
Cross section area 1x95 mm²
Core Copper
Iz under real conditions 197 A
Iz’ 197 A
Selected neutral
Cross section area 1x95 mm²
Core Copper
Iz under real conditions 197 A
Iz’ 197 A
Selected PE
Cross section area 1x50 mm²
Core Copper
Ii current 3000 A
Ti current 50 A
Selectivity Results
UpStream Selectivity Limit
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Cable WD 18
Parameters
Length 3m
Installation method 70
D1
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 12 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Project: bài 1 25/09/2021
Page 18/45
Selected phase
Cross section area 1x1.5 mm²
Core Copper
Iz under real conditions 21 A
Iz’ 21 A
Selected neutral
Cross section area 1x1.5 mm²
Core Copper
Iz under real conditions 21 A
Iz’ 21 A
Selected PE
Cross section area 1x1.5 mm²
Core Copper
Ii current NA
Ti current NA
Selectivity Results
UpStream Selectivity Limit
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Cable WD 22
Parameters
Length 17 m
Installation method 21
C
Multi-core cables fixed directly under a
wooden ceiling
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: bài 1 25/09/2021
Page 21/45
Ib 1A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.95
Standard table reference B-52-17
User correction factor 1
Overall factor 0.95
Selected phase
Cross section area 1x1.5 mm²
Core Copper
Iz under real conditions 20.9 A
Iz’ 22 A
Selected neutral
Cross section area 1x1.5 mm²
Core Copper
Iz under real conditions 20.9 A
Iz’ 22 A
Selected PE
Cross section area 1x1.5 mm²
Core Copper
Charge EA 22
U 400 V
S 0.825 kVA
P 0.275 kW
I 1.19 A
cos 1
Ku (Normal) 1
Number of circuit 10
Polarity 3Ph+N
Phase connection
Type of luminaries Metal iodine
Nb of luminaries 1
Nb of lights/luminaries 1
Lights power 250 W
Ballast power 25 W
Ia 2.14 A
Harmonic generator No
Project: bài 1 25/09/2021
Page 22/45
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Selectivity Results
UpStream Selectivity Limit
Cable WD 9
Parameters
Length 20 m
Installation method 70
D1
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 10 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-19
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x1.5 mm²
Core Copper
Iz under real conditions 21 A
Iz’ 21 A
Selected neutral
Cross section area 1x1.5 mm²
Core Copper
Iz under real conditions 21 A
Iz’ 21 A
Selected PE
Cross section area 1x1.5 mm²
Core Copper
Charge AA 9
Project: bài 1 25/09/2021
Page 25/45
U 400 V
S 6.6 kVA
P 5.28 kW
I 9.5 A
cos 0.8
Polarity 3Ph+N
Phase connection
Number of circuit 3
Ku (Normal) 0.8
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Selectivity Results
UpStream Selectivity Limit
Cable WD 16
Parameters
Length 20 m
Installation method 70
D1
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 10 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-19
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x1.5 mm²
Core Copper
Iz under real conditions 21 A
Iz’ 21 A
Selected neutral
Cross section area 1x1.5 mm²
Core Copper
Iz under real conditions 21 A
Iz’ 21 A
Selected PE
Cross section area 1x1.5 mm²
Core Copper
Charge AA 16
U 400 V
S 6.6 kVA
P 5.28 kW
Project: bài 1 25/09/2021
Page 28/45
I 9.5 A
cos 0.8
Polarity 3Ph+N
Phase connection
Number of circuit 3
Ku (Normal) 0.8
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Contactor LC1D32
Designation LC1D32
Type of coordination T1
Cable WD 6
Parameters
Length 9m
Installation method 70
D1
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Project: bài 1 25/09/2021
Page 30/45
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 29 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-19
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x4 mm²
Core Copper
Iz under real conditions 36 A
Iz’ 36 A
Selected PE
Cross section area 1x4 mm²
Core Copper
Asynchronous LV Motor MA 6
Startup type Direct
U 400 V
Mechanical power 15 kW
Startup current Id/Ir 7.2
Transient current I’’d/Ir <=19
Ir for sizing 29 A
Sr for sizing 20.1 kVA
Pr for sizing 16.1 kW
cos 0.8
Polarity 3Ph
Number of circuit 3
Ku (mode Normal) 0.8
Harmonic generator No
THDI3 NA %
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Contactor LC1D50A
Project: bài 1 25/09/2021
Page 32/45
Designation LC1D50A
Type of coordination T1
Cable WD 7
Parameters
Length 10 m
Installation method 70
D1
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 40 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-19
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 44 A
Iz’ 44 A
Selected PE
Cross section area 1x6 mm²
Core Copper
Asynchronous LV Motor MA 7
Startup type Direct
U 400 V
Mechanical power 22 kW
Startup current Id/Ir 7.2
Transient current I’’d/Ir <=19
Ir for sizing 40 A
Sr for sizing 27.7 kVA
Pr for sizing 22.2 kW
cos 0.8
Polarity 3Ph
Number of circuit 5
Ku (mode Normal) 0.8
Harmonic generator No
THDI3 NA %
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Ii current 425 A
Ti current 100 A
Selectivity Results
UpStream Selectivity Limit
Contactor LC1D18
Designation LC1D18
Type of coordination T1
Cable WD 8
Parameters
Length 10 m
Installation method 70
D1
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 16 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-19
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x1.5 mm²
Core Copper
Iz under real conditions 21 A
Iz’ 21 A
Selected PE
Cross section area 1x1.5 mm²
Core Copper
Asynchronous LV Motor MA 8
Startup type Direct
U 400 V
Mechanical power 7.5 kW
Startup current Id/Ir 7.2
Transient current I’’d/Ir <=19
Ir for sizing 15.5 A
Sr for sizing 10.7 kVA
Pr for sizing 8.59 kW
cos 0.8
Polarity 3Ph
Number of circuit 3
Ku (mode Normal) 0.8
Harmonic generator No
THDI3 NA %
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Designation NSX100F
Circuit breaker rating 100 A
Breaking capacity 36 kA
TNS One pole breaking capacity 36 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation Micrologic 2.2 M
Trip unit rating 50 A
Long delay settings
Ir 36 A
Tr 5s
Short delay settings
Isd current 468 A
Tsd 0.03 s
Instantaneous tripping
Ii current 750 A
Ti current 60 A
Selectivity Results
UpStream Selectivity Limit
Contactor LC1D40A
Designation LC1D40A
Type of coordination T1
Cable WD 13
Parameters
Length 8m
Installation method 70
D1
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 35 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Project: bài 1 25/09/2021
Page 37/45
Selected phase
Cross section area 1x4 mm²
Core Copper
Iz under real conditions 36 A
Iz’ 36 A
Selected PE
Cross section area 1x4 mm²
Core Copper
Asynchronous LV Motor MA 13
Startup type Direct
U 400 V
Mechanical power 18.5 kW
Startup current Id/Ir 7.2
Transient current I’’d/Ir <=19
Ir for sizing 35 A
Sr for sizing 24.2 kVA
Pr for sizing 19.4 kW
cos 0.8
Polarity 3Ph
Number of circuit 2
Ku (mode Normal) 0.8
Harmonic generator No
THDI3 NA %
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Contactor LC1D32
Designation LC1D32
Type of coordination T1
Cable WD 14
Parameters
Length 9m
Installation method 70
D1
Multi-core cable in conduit or in cable
Project: bài 1 25/09/2021
Page 39/45
Selected phase
Cross section area 1x4 mm²
Core Copper
Iz under real conditions 36 A
Iz’ 36 A
Selected PE
Cross section area 1x4 mm²
Core Copper
Asynchronous LV Motor MA 14
Startup type Direct
U 400 V
Mechanical power 15 kW
Startup current Id/Ir 7.2
Transient current I’’d/Ir <=19
Ir for sizing 29 A
Sr for sizing 20.1 kVA
Pr for sizing 16.1 kW
cos 0.8
Polarity 3Ph
Number of circuit 2
Ku (mode Normal) 0.8
Harmonic generator No
THDI3 NA %
Sensitivity to over voltage NA
Project: bài 1 25/09/2021
Page 40/45
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Contactor LC1D25
Designation LC1D25
Type of coordination T1
Cable WD 15
Parameters
Length 13 m
Installation method 70
D1
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 22 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-19
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x2.5 mm²
Core Copper
Iz under real conditions 28 A
Iz’ 28 A
Selected PE
Cross section area 1x2.5 mm²
Core Copper
Asynchronous LV Motor MA 15
Startup type Direct
U 400 V
Mechanical power 11 kW
Startup current Id/Ir 7.2
Transient current I’’d/Ir <=19
Ir for sizing 22 A
Sr for sizing 15.2 kVA
Pr for sizing 12.2 kW
cos 0.8
Polarity 3Ph
Number of circuit 3
Ku (mode Normal) 0.8
Harmonic generator No
THDI3 NA %
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
3.6.2 Circuit WC 4
Busbar WC 4
Parameters
Switchboard Name UC 5
Switchboard Range No preference
Rating (A) NA
IP Undefined
Feeder
Circuit name Protection name Protection type
Load 9 QA 9 iC60L
3.6.3 Circuit WC 11
Busbar WC 11
Parameters
Switchboard Name UC 12
Switchboard Range No preference
Rating (A) NA
IP Undefined
Feeder
Project: bài 1 25/09/2021
Page 44/45
Load 16 QA 16 iC60H
3.6.4 Circuit WC 19
Busbar WC 19
Parameters
Switchboard Name UC 20
Switchboard Range No preference
Rating (A) NA
IP Undefined
Feeder
Circuit name Protection name Protection type
Load 22 QA 22 iC60L
NOTICE
RISK OF INACCURATE DATA RESULTS.
Configure the software correctly to get accurate reports and/or data results.
Do not rely solely on software messages and reports to determine if the
system is functioning correctly.
Make sure that you have entered the correct inputs for the required
components.
Review the calculated results and solutions provided by the software before
submitting the report.
Failure to follow these instructions can result in incorrect bill of material and
loss of business.