Installation calculation report

bài 1
Full
Page 2/45

Project: bài 1 25/09/2021


Page 3/45

Content

1 Project description.................................................................................................................. 4
1.1 Project general settings................................................................................................................... 4

1.2 Settings for wiring device calculation............................................................................................ 4

1.3 List of loads...................................................................................................................................... 4

2 Installation general design.....................................................................................................6


2.1 List of devices.................................................................................................................................. 6

3 Calculation notes.................................................................................................................. 14
3.1 Source circuits............................................................................................................................... 14

3.2 Generator circuits.......................................................................................................................... 23

3.3 LV Source circuits.......................................................................................................................... 23

3.4 UPS circuits.................................................................................................................................... 23

3.5 Surge Arrester circuits.................................................................................................................. 24

3.6 Capacitor bank circuits.................................................................................................................. 24

3.7 Feeder circuits................................................................................................................................ 24

3.8 LV Transformer circuits................................................................................................................. 26

3.9 Couplers circuits............................................................................................................................ 27

3.10 Generic load circuits................................................................................................................. 28

3.11 Lighting load circuits................................................................................................................ 28

3.12 Power socket load circuits....................................................................................................... 29

3.13 Motor starter combination........................................................................................................ 29

3.14 Busbar circuits.......................................................................................................................... 30

3.15 Busbar trunking system circuits............................................................................................. 30

3.16 Busbar trunking system circuits............................................................................................. 30

3.17 Lighting Busbar trunking system circuits..............................................................................30

Project: bài 1 25/09/2021


Page 4/45

1 Project description
1.1 Project general settings
Installation standard IEC60364

Calculation standard TR50480


Circuit breaker standard IEC 60947-2
Frequency 50 Hz

1.2 Settings for wiring device calculation


Maximal CSA 300 mm²

1.3 List of loads


1.3.1 Power sockets
Name Sr (kVA) Pr (kW) Ir (A) Cos Nbr Polarity Non linear load THDi 3 (%)
AA 9 6.6 5.28 9.5 0.8 3 3Ph+N No 0
AA 16 6.6 5.28 9.5 0.8 3 3Ph+N No 0

1.3.2 Lighting distribution


Name Type of lamp P Lamp (W) P ballast (W) Nb of lamp/light Nb of light
EA 22 Metal iodine 250 25 1 1
1.3.3 Motor loads
Name Sr (kVA) Pr (kW) Ir (A) Cos Nbr Polarity Non linear load THDi 3 (%)
MA 6 20.1 16.1 29 0.8 3 3Ph No 0
MA 7 27.7 22.2 40 0.8 5 3Ph No 0
MA 8 10.7 8.59 15.5 0.8 3 3Ph No 0
MA 13 24.2 19.4 35 0.8 2 3Ph No 0
MA 14 20.1 16.1 29 0.8 2 3Ph No 0
MA 15 15.2 12.2 22 0.8 3 3Ph No 0

Project: bài 1 25/09/2021


Page 5/45

2 Installation general design


2.1 List of devices
2.1.1 MV/LV transformer
Name Nbr Range Insulation Sr (kVA) ukrT (%) Connection U2 (V) SEA Rb (m)
TA 0 1 Trihal Resin 400 4 D 420 TN-S 10000

2.1.2 LV switchboards and busbar

Switchboard name Range Rating (A) IP


UC 2 No preference 0.00 Undefined

UC 5 No preference 0.00 Undefined

UC 12 No preference 0.00 Undefined

UC 20 No preference 0.00 Undefined

Busbar name Switchboard Ks Polarity SEA Equipotential bounding


name
WC 1 UC 2 1 3Ph+N TN-S With
WC 4 UC 5 1 3Ph+N TN-S Without
WC 11 UC 12 1 3Ph+N TN-S Without
WC 19 UC 20 1 3Ph+N TN-S Without

2.1.3 Circuit breaker


Name Nbr Range - Rating (A) Poles Trip unit/Curve RCD RCD class
Designation
QA 0 1 Compact 630 4P4d Micrologic 5.3 A
NSX -
NSX630F
QA 3 1 Compact 400 4P4d Micrologic 2.3
NSX -
NSX400F
QA 3bis 1 Compact 400 4P4d Micrologic 5.3 A
NSX -
NSX400F
QA 6 3 Compact 100 3P3d Micrologic 2.2 M
NSX -
NSX100F
QA 7 5 Compact 100 3P3d Micrologic 2.2 M
NSX -
NSX100F
QA 8 3 TeSys GV4 - 25 3P3d P25
GV4P25B
QA 9 3 Acti9 iC60 - 10 4P4d C Vigi iC60 A
iC60L
QA 10 1 Compact 250 4P4d Micrologic 2.2
NSX -
NSX250B
QA 10bis 1 Compact 250 4P4d Micrologic 5.2 A
NSX -
NSX250B
QA 13 2 Compact 100 3P3d Micrologic 2.2 M
NSX -

Project: bài 1 25/09/2021


Page 6/45

NSX100F
QA 14 2 Compact 100 3P3d Micrologic 2.2 M
NSX -
NSX100F
QA 15 3 Acti9 P25M - 23 3P3d M
P25M
QA 16 3 Acti9 iC60 - 10 4P4d C Vigi iC60 A
iC60H
QA 18 1 Acti9 iC60 - 13 4P4d C
iC60L
QA 18bis 1 Acti9 iDPN - 13 4P3d C
iDPN.N
QA 22 10 Acti9 iC60 - 1.6 4P4d C
iC60L

2.1.4 Cable schedule


Name Nbr Incomer Feeder Type Insulation L (m) L1/L2/L3 N PE/PEN
WD 16 3 QA 16 AA 16 Multi-core XLPE 20 1x1.5 1x1.5 1x1.5
Copper Copper Copper
WD 9 3 QA 9 AA 9 Multi-core XLPE 20 1x1.5 1x1.5 1x1.5
Copper Copper Copper
WD 22 10 QA 22 EA 22 Multi-core XLPE 17 1x1.5 1x1.5 1x1.5
Copper Copper Copper
WD 0 1 TA 0 QA 0 Multi-core XLPE 15 2x300 2x300 1x150
Copper Copper Copper
WD 15 3 QA 15 MA 15 Multi-core XLPE 13 1x2.5 1x2.5
Copper Copper
WD 3 1 QA 3 QA 3bis Multi-core XLPE 11 1x240 1x240 1x120
Copper Copper Copper
WD 10 1 QA 10 QA Multi-core XLPE 10 1x95 1x95 1x50
10bis Copper Copper Copper
WD 8 3 QA 8 MA 8 Multi-core XLPE 10 1x1.5 1x1.5
Copper Copper
WD 7 5 QA 7 MA 7 Multi-core XLPE 10 1x6 Copper 1x6 Copper
WD 14 2 QA 14 MA 14 Multi-core XLPE 9 1x4 Copper 1x4 Copper
WD 6 3 QA 6 MA 6 Multi-core XLPE 9 1x4 Copper 1x4 Copper
WD 13 2 QA 13 MA 13 Multi-core XLPE 8 1x4 Copper 1x4 Copper
WD 18 1 QA 18 QA Multi-core XLPE 3 1x1.5 1x1.5 1x1.5
18bis Copper Copper Copper

Project: bài 1 25/09/2021


Page 7/45

NOTICE
RISK OF INACCURATE DATA RESULTS

 Make sure that you have provided all the required inputs for the conductor sizing.
 It is recommended to refer to the cable manufacturer's catalogue before making
the selection.

Failure to follow these instructions can result in incorrect bill of material and loss
of business.

2.1.5 MV Cable
Name Nbr Designation CSA (mm²) Icc (A) In (A) Un (kV)
MVWD 1 NA 1 x 240 Al 21.3 418 24
0

Project: bài 1 25/09/2021


Page 8/45

3 Calculation notes

3.1 Source circuits


3.1.1 Circuit Source 0
MV power supply W0
Max. upstream short circuit power 500 MVA
Min. upstream short circuit power 250 MVA
MV Cable MVWD 0
Parameters
Length 10 m
Type of cable Single core
Ib 12 A
Nb of conductor per phase 1
Cross section area 1 x 240 Al mm²
Core Aluminium
Short circuit withstand 21.3 kA
Assigned voltage 20 kV
Insulation voltage 24 kV

MV/LV transformer TA 0
Range Trihal
Technology Resin
Rated power 400 kVA
ukrT 4%
Type of losses AoAk
PkrT 4.5 kW
System earthing arrangement TN-S
MV Connection D
LV Connection yn
No load secondary voltage Ur0 420V
Ur LV 400V
Rb (neutral grounding) NA
Ra (mass grounding) NA
Sizing information UkrT and PkrT calculated by system
Cable WD 0
Parameters
Length 15 m
Installation method 70
D1
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 577 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.85
Project: bài 1 25/09/2021
Page 9/45

Standard table reference B-52-19


User correction factor 1
Overall factor 0.85

Selected phase
Cross section area 2x300 mm²
Core Copper
Iz under real conditions 620 A
Iz’ 730 A
Selected neutral
Cross section area 2x300 mm²
Core Copper
Iz under real conditions 620 A
Iz’ 730 A
Selected PE
Cross section area 2x150 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 16.32 14.13 15.72 9.94 11.01 11.47 NA 13.28

Synthesis for all operating mode


(kA) 16.32 14.13 15.72 9.94 11.01 11.47 NA 13.28

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Circuit breaker QA 0
Ib 577 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX630F
Circuit breaker rating 630 A
Breaking capacity 36 kA
TNS One pole breaking capacity 36 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation Micrologic 5.3 A
Trip unit rating 630 A
Long delay settings
Ir 578 A
Tr 16 s
Short delay settings
Isd current 5780 A
Tsd 0.4 s
Instantaneous tripping
Ii current 6930 A
Ti current 50 A

Selectivity Results
UpStream Selectivity Limit

Project: bài 1 25/09/2021


Page 10/45

Operating mode Normal


NA Selectivity can't be determinated : no
upstream Lv Breaker

Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 479.634 467.726 467.726 11.9

Synthesis for all operating mode


(A) 479.634 467.726 467.726 11.9
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.208 0.208
UL1L2 (%) 0.240 0.240
UL2L3 (%) 0.241 0.241
UL3L1 (%) 0.240 0.240
UL1N (%) 0.208 0.208
UL2N (%) 0.208 0.208
UL3N (%) 0.208 0.208

3.2 Feeder circuits


3.2.1 Circuit Feeder circuit 3
Circuit breaker QA 3
Ib 290 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX400F
Circuit breaker rating 400 A
Breaking capacity 36 kA
TNS One pole breaking capacity 36 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation Micrologic 2.3
Trip unit rating 400 A
Long delay settings
Ir 294 A
Tr 16 s
Short delay settings
Isd current 2944 A
Tsd 0.02 s
Instantaneous tripping
Project: bài 1 25/09/2021
Page 11/45

Ii current 4800 A
Ti current 60 A

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 0 6900 A
NSX630F
Micrologic 5.3 A
630 A / 4P4d

Cable WD 3
Parameters
Length 11 m
Installation method 70
D1
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 290 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-19
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x240 mm²
Core Copper
Iz under real conditions 324 A
Iz’ 324 A
Selected neutral
Cross section area 1x240 mm²
Core Copper
Iz under real conditions 324 A
Iz’ 324 A
Selected PE
Cross section area 1x120 mm²

Project: bài 1 25/09/2021


Page 12/45

Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 15.24 13.20 13.82 9.38 9.87 10.03 NA 11.61

Synthesis for all operating mode


(kA) 15.24 13.20 13.82 9.38 9.87 10.03 NA 11.61

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Circuit breaker QA 3bis


Ib 290 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX400F
Circuit breaker rating 400 A
Breaking capacity 36 kA
TNS One pole breaking capacity 36 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation Micrologic 5.3 A
Trip unit rating 400 A
Long delay settings
Ir 290 A
Tr 4s
Short delay settings
Isd current 2900 A
Tsd 0.4 s
Instantaneous tripping
Ii current 4800 A
Ti current 50 A

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 3 No Selectivity
NSX400F
Micrologic 2.3
400 A / 4P4d

Design current
IL1 IL2 IL3 IN

Project: bài 1 25/09/2021


Page 13/45

Operating mode Normal


(A) 289.663 289.663 289.663 0

Synthesis for all operating mode


(A) 289.663 289.663 289.663 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.384 0.175
UL1L2 (%) 0.443 0.202
UL2L3 (%) 0.443 0.202
UL3L1 (%) 0.443 0.202
UL1N (%) 0.383 0.175
UL2N (%) 0.384 0.175
UL3N (%) 0.384 0.175

Project: bài 1 25/09/2021


Page 14/45

3.2.2 Circuit Feeder circuit 10


Circuit breaker QA 10
Ib 178 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX250B
Circuit breaker rating 250 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation Micrologic 2.2
Trip unit rating 250 A
Long delay settings
Ir 180 A
Tr 16 s
Short delay settings
Isd current 1800 A
Tsd 0.02 s
Instantaneous tripping
Ii current 3000 A
Ti current 60 A

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 0 Total Selectivity
NSX630F
Micrologic 5.3 A
630 A / 4P4d

Cable WD 10
Parameters
Length 10 m
Installation method 70
D1
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 178 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Project: bài 1 25/09/2021
Page 15/45

Standard table reference B-52-15


Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-19
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x95 mm²
Core Copper
Iz under real conditions 197 A
Iz’ 197 A
Selected neutral
Cross section area 1x95 mm²
Core Copper
Iz under real conditions 197 A
Iz’ 197 A
Selected PE
Cross section area 1x50 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 14.96 12.96 13.27 9.18 9.42 9.28 NA 10.75

Synthesis for all operating mode


(kA) 14.96 12.96 13.27 9.18 9.42 9.28 NA 10.75

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Circuit breaker QA 10bis


Ib 178 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX250B
Circuit breaker rating 250 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation Micrologic 5.2 A
Trip unit rating 250 A
Long delay settings
Ir 179 A
Tr 4s
Short delay settings
Isd current 1790 A
Tsd 0.4 s
Instantaneous tripping
Project: bài 1 25/09/2021
Page 16/45

Ii current 3000 A
Ti current 50 A

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 10 No Selectivity
NSX250B
Micrologic 2.2
250 A / 4P4d

Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 178.063 178.063 178.063 0

Synthesis for all operating mode


(A) 178.063 178.063 178.063 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.399 0.191
UL1L2 (%) 0.461 0.220
UL2L3 (%) 0.461 0.220
UL3L1 (%) 0.461 0.220
UL1N (%) 0.399 0.191
UL2N (%) 0.399 0.191
UL3N (%) 0.399 0.191

Project: bài 1 25/09/2021


Page 17/45

3.2.3 Circuit Feeder circuit 18


Circuit breaker QA 18
Ib 11.9 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60L
Circuit breaker rating 13 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 13 A
Long delay settings
Ir 13 A
Tr NA
Short delay settings
Isd current 104 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 0 Total Selectivity
NSX630F
Micrologic 5.3 A
630 A / 4P4d

Cable WD 18
Parameters
Length 3m
Installation method 70
D1
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 12 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Project: bài 1 25/09/2021
Page 18/45

Standard table reference B-52-15


Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-19
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x1.5 mm²
Core Copper
Iz under real conditions 21 A
Iz’ 21 A
Selected neutral
Cross section area 1x1.5 mm²
Core Copper
Iz under real conditions 21 A
Iz’ 21 A
Selected PE
Cross section area 1x1.5 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 5.74 4.97 3.15 3.38 2.13 2.15 NA 2.49

Synthesis for all operating mode


(kA) 5.74 4.97 3.15 3.38 2.13 2.15 NA 2.49

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Circuit breaker QA 18bis


Ib 11.9 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iDPN
Designation iDPN.N
Circuit breaker rating 13 A
Breaking capacity 10 kA
TNS One pole breaking capacity NaN kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P3d
Trip unit designation C
Trip unit rating 13 A
Long delay settings
Ir 13 A
Tr NA
Short delay settings
Isd current 110 A
Tsd NA
Instantaneous tripping
Project: bài 1 25/09/2021
Page 19/45

Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 18 No Selectivity
iC60L
C
13 A / 4P4d

Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 11.908 0.000 0.000 11.9

Synthesis for all operating mode


(A) 11.908 NA NA 11.9
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.453 0.244
UL1L2 (%) 0.240 0.000
UL2L3 (%) 0.241 0.000
UL3L1 (%) 0.240 0.000
UL1N (%) 0.697 0.489
UL2N (%) 0.453 0.244
UL3N (%) 0.453 0.244

Project: bài 1 25/09/2021


Page 20/45

3.3 Lighting load circuits

3.3.1 Circuit Load 22


Circuit breaker QA 22
Ib 1.19 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60L
Circuit breaker rating 1.6 A
Breaking capacity 100 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 1.6 A
Long delay settings
Ir 1.6 A
Tr NA
Short delay settings
Isd current 12.8 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 18bis Total Selectivity
iDPN.N
C
13 A / 4P3d

Cable WD 22
Parameters
Length 17 m
Installation method 21
C
Multi-core cables fixed directly under a
wooden ceiling
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: bài 1 25/09/2021
Page 21/45

Ib 1A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.95
Standard table reference B-52-17
User correction factor 1
Overall factor 0.95

Selected phase
Cross section area 1x1.5 mm²
Core Copper
Iz under real conditions 20.9 A
Iz’ 22 A
Selected neutral
Cross section area 1x1.5 mm²
Core Copper
Iz under real conditions 20.9 A
Iz’ 22 A
Selected PE
Cross section area 1x1.5 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 1.01 0.87 0.51 0.59 0.34 0.34 NA 0.40

Synthesis for all operating mode


(kA) 1.01 0.87 0.51 0.59 0.34 0.34 NA 0.40

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge EA 22
U 400 V
S 0.825 kVA
P 0.275 kW
I 1.19 A
cos 1
Ku (Normal) 1
Number of circuit 10
Polarity 3Ph+N
Phase connection
Type of luminaries Metal iodine
Nb of luminaries 1
Nb of lights/luminaries 1
Lights power 250 W
Ballast power 25 W
Ia 2.14 A
Harmonic generator No
Project: bài 1 25/09/2021
Page 22/45

THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 1.191 0.000 0.000 1.19

Synthesis for all operating mode


(A) 1.191 NA NA 1.19
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.591 0.138
UL1L2 (%) 0.240 0.000
UL2L3 (%) 0.241 0.000
UL3L1 (%) 0.240 0.000
UL1N (%) 0.974 0.277
UL2N (%) 0.591 0.138
UL3N (%) 0.591 0.138

Synthesis for all operating mode


U3L (%) 0.591
UL1L2 (%) 0.240
UL2L3 (%) 0.241
UL3L1 (%) 0.240
UL1N (%) 0.974
UL2N (%) 0.591
UL3N (%) 0.591

Project: bài 1 25/09/2021


Page 23/45

3.4 Power socket load circuits


3.4.1 Circuit Load 9
Circuit breaker QA 9
Ib 9.5 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60L
Circuit breaker rating 10 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 10 A
Long delay settings
Ir 10 A
Tr NA
Short delay settings
Isd current 80 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 3bis Total Selectivity
NSX400F
Micrologic 5.3 A
400 A / 4P4d

RCD designation Vigi iC60


Class A
In 30 mA
Break Time 0.03 s
t NA s
Selectivity NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


NA Selectivity not analyzed

Project: bài 1 25/09/2021


Page 24/45

Cable WD 9
Parameters
Length 20 m
Installation method 70
D1
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 10 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-19
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x1.5 mm²
Core Copper
Iz under real conditions 21 A
Iz’ 21 A
Selected neutral
Cross section area 1x1.5 mm²
Core Copper
Iz under real conditions 21 A
Iz’ 21 A
Selected PE
Cross section area 1x1.5 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 1.00 0.87 0.51 0.59 0.34 0.34 NA 0.40

Synthesis for all operating mode


(kA) 1.00 0.87 0.51 0.59 0.34 0.34 NA 0.40

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge AA 9
Project: bài 1 25/09/2021
Page 25/45

U 400 V
S 6.6 kVA
P 5.28 kW
I 9.5 A
cos 0.8
Polarity 3Ph+N
Phase connection
Number of circuit 3
Ku (Normal) 0.8
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 9.526 9.526 9.526 0

Synthesis for all operating mode


(A) 9.526 9.526 9.526 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.430 1.046
UL1L2 (%) 1.651 1.208
UL2L3 (%) 1.651 1.208
UL3L1 (%) 1.651 1.208
UL1N (%) 1.430 1.046
UL2N (%) 1.430 1.046
UL3N (%) 1.430 1.046

Synthesis for all operating mode


U3L (%) 1.430
UL1L2 (%) 1.651
UL2L3 (%) 1.651
UL3L1 (%) 1.651
UL1N (%) 1.430
UL2N (%) 1.430
UL3N (%) 1.430

Project: bài 1 25/09/2021


Page 26/45

3.4.2 Circuit Load 16


Circuit breaker QA 16
Ib 9.5 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60H
Circuit breaker rating 10 A
Breaking capacity 15 kA
TNS One pole breaking capacity 15 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 10 A
Long delay settings
Ir 10 A
Tr NA
Short delay settings
Isd current 80 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 10bis Total Selectivity
NSX250B
Micrologic 5.2 A
250 A / 4P4d

RCD designation Vigi iC60


Class A
In 30 mA
Break Time 0.03 s
t NA s
Selectivity NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


NA Selectivity not analyzed

Project: bài 1 25/09/2021


Page 27/45

Cable WD 16
Parameters
Length 20 m
Installation method 70
D1
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 10 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-19
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x1.5 mm²
Core Copper
Iz under real conditions 21 A
Iz’ 21 A
Selected neutral
Cross section area 1x1.5 mm²
Core Copper
Iz under real conditions 21 A
Iz’ 21 A
Selected PE
Cross section area 1x1.5 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 1.00 0.87 0.51 0.59 0.34 0.34 NA 0.39

Synthesis for all operating mode


(kA) 1.00 0.87 0.51 0.59 0.34 0.34 NA 0.39

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge AA 16
U 400 V
S 6.6 kVA
P 5.28 kW
Project: bài 1 25/09/2021
Page 28/45

I 9.5 A
cos 0.8
Polarity 3Ph+N
Phase connection
Number of circuit 3
Ku (Normal) 0.8
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 9.526 9.526 9.526 0

Synthesis for all operating mode


(A) 9.526 9.526 9.526 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.446 1.046
UL1L2 (%) 1.669 1.208
UL2L3 (%) 1.669 1.208
UL3L1 (%) 1.669 1.208
UL1N (%) 1.445 1.046
UL2N (%) 1.446 1.046
UL3N (%) 1.446 1.046

Synthesis for all operating mode


U3L (%) 1.446
UL1L2 (%) 1.669
UL2L3 (%) 1.669
UL3L1 (%) 1.669
UL1N (%) 1.445
UL2N (%) 1.446
UL3N (%) 1.446

Project: bài 1 25/09/2021


Page 29/45

3.5 Motor starter combination


3.5.1 Circuit Motor Load 6
Circuit breaker QA 6
Ib NA
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX100F
Circuit breaker rating 100 A
Breaking capacity 36 kA
TNS One pole breaking capacity 36 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation Micrologic 2.2 M
Trip unit rating 50 A
Long delay settings
Ir 30 A
Tr 5s
Short delay settings
Isd current 390 A
Tsd 0.03 s
Instantaneous tripping
Ii current 750 A
Ti current 60 A

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 3bis Total Selectivity
NSX400F
Micrologic 5.3 A
400 A / 4P4d

Contactor LC1D32
Designation LC1D32
Type of coordination T1

Cable WD 6
Parameters
Length 9m
Installation method 70
D1
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Project: bài 1 25/09/2021
Page 30/45

Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 29 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-19
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x4 mm²
Core Copper
Iz under real conditions 36 A
Iz’ 36 A
Selected PE
Cross section area 1x4 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 5.10 4.41 NA 3.01 NA 1.87 NA 2.16

Synthesis for all operating mode


(kA) 5.10 4.41 NA 3.01 NA 1.87 NA 2.16

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Asynchronous LV Motor MA 6
Startup type Direct
U 400 V
Mechanical power 15 kW
Startup current Id/Ir 7.2
Transient current I’’d/Ir <=19
Ir for sizing 29 A
Sr for sizing 20.1 kVA
Pr for sizing 16.1 kW
cos 0.8
Polarity 3Ph
Number of circuit 3
Ku (mode Normal) 0.8
Harmonic generator No
THDI3 NA %
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Project: bài 1 25/09/2021


Page 31/45

Operating mode Normal


(A) 29.000 29.000 29.000 0

Synthesis for all operating mode


(A) 29.000 29.000 29.000 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.925 0.541
UL1L2 (%) 1.067 0.625
UL2L3 (%) 1.068 0.625
UL3L1 (%) 1.067 0.625
UL1N (%) 0.383 0.000
UL2N (%) 0.384 0.000
UL3N (%) 0.384 0.000

Startup Voltage drop


UStartUp 1.444
3.5.2 Circuit Motor Load 7
Circuit breaker QA 7
Ib NA
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX100F
Circuit breaker rating 100 A
Breaking capacity 36 kA
TNS One pole breaking capacity 36 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation Micrologic 2.2 M
Trip unit rating 50 A
Long delay settings
Ir 40 A
Tr 5s
Short delay settings
Isd current 520 A
Tsd 0.03 s
Instantaneous tripping
Ii current 750 A
Ti current 60 A

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 3bis Total Selectivity
NSX400F
Micrologic 5.3 A
400 A / 4P4d

Contactor LC1D50A
Project: bài 1 25/09/2021
Page 32/45

Designation LC1D50A
Type of coordination T1

Cable WD 7
Parameters
Length 10 m
Installation method 70
D1
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 40 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-19
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 44 A
Iz’ 44 A
Selected PE
Cross section area 1x6 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 6.37 5.52 NA 3.78 NA 2.42 NA 2.81

Synthesis for all operating mode


(kA) 6.37 5.52 NA 3.78 NA 2.42 NA 2.81

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Asynchronous LV Motor MA 7
Startup type Direct

Project: bài 1 25/09/2021


Page 33/45

U 400 V
Mechanical power 22 kW
Startup current Id/Ir 7.2
Transient current I’’d/Ir <=19
Ir for sizing 40 A
Sr for sizing 27.7 kVA
Pr for sizing 22.2 kW
cos 0.8
Polarity 3Ph
Number of circuit 5
Ku (mode Normal) 0.8
Harmonic generator No
THDI3 NA %
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 40.000 40.000 40.000 0

Synthesis for all operating mode


(A) 40.000 40.000 40.000 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.939 0.555
UL1L2 (%) 1.084 0.641
UL2L3 (%) 1.084 0.641
UL3L1 (%) 1.084 0.641
UL1N (%) 0.383 0.000
UL2N (%) 0.384 0.000
UL3N (%) 0.384 0.000

Startup Voltage drop


UStartUp 1.605
3.5.3 Circuit Motor Load 8
Circuit breaker QA 8
Ib NA
Distance from origin NA

Sizing Information Sized by system


Range TeSys GV4
Designation GV4P25B
Circuit breaker rating 25 A
Breaking capacity 25 kA
TNS One pole breaking capacity NaN kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation P25
Trip unit rating 25 A
Long delay settings
Ir 16 A
Tr 10 s
Short delay settings
Isd current 208 A
Tsd 0.03 s
Instantaneous tripping
Project: bài 1 25/09/2021
Page 34/45

Ii current 425 A
Ti current 100 A

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 3bis Total Selectivity
NSX400F
Micrologic 5.3 A
400 A / 4P4d

Contactor LC1D18
Designation LC1D18
Type of coordination T1

Cable WD 8
Parameters
Length 10 m
Installation method 70
D1
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 16 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-19
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x1.5 mm²
Core Copper
Iz under real conditions 21 A
Iz’ 21 A
Selected PE
Cross section area 1x1.5 mm²
Core Copper

Project: bài 1 25/09/2021


Page 35/45

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 1.96 1.69 NA 1.15 NA 0.67 NA 0.78

Synthesis for all operating mode


(kA) 1.96 1.69 NA 1.15 NA 0.67 NA 0.78

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Asynchronous LV Motor MA 8
Startup type Direct
U 400 V
Mechanical power 7.5 kW
Startup current Id/Ir 7.2
Transient current I’’d/Ir <=19
Ir for sizing 15.5 A
Sr for sizing 10.7 kVA
Pr for sizing 8.59 kW
cos 0.8
Polarity 3Ph
Number of circuit 3
Ku (mode Normal) 0.8
Harmonic generator No
THDI3 NA %
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 15.500 15.500 15.500 0

Synthesis for all operating mode


(A) 15.500 15.500 15.500 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.235 0.851
UL1L2 (%) 1.426 0.983
UL2L3 (%) 1.426 0.983
UL3L1 (%) 1.426 0.983
UL1N (%) 0.383 0.000
UL2N (%) 0.384 0.000
UL3N (%) 0.384 0.000

Startup Voltage drop


UStartUp 1.773
3.5.4 Circuit Motor Load 13
Circuit breaker QA 13
Ib NA
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Project: bài 1 25/09/2021
Page 36/45

Designation NSX100F
Circuit breaker rating 100 A
Breaking capacity 36 kA
TNS One pole breaking capacity 36 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation Micrologic 2.2 M
Trip unit rating 50 A
Long delay settings
Ir 36 A
Tr 5s
Short delay settings
Isd current 468 A
Tsd 0.03 s
Instantaneous tripping
Ii current 750 A
Ti current 60 A

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 10bis Total Selectivity
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Contactor LC1D40A
Designation LC1D40A
Type of coordination T1

Cable WD 13
Parameters
Length 8m
Installation method 70
D1
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 35 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Project: bài 1 25/09/2021
Page 37/45

Touching conductor factor 1


Standard table reference B-52-19
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x4 mm²
Core Copper
Iz under real conditions 36 A
Iz’ 36 A
Selected PE
Cross section area 1x4 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 5.47 4.73 NA 3.23 NA 2.00 NA 2.32

Synthesis for all operating mode


(kA) 5.47 4.73 NA 3.23 NA 2.00 NA 2.32

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Asynchronous LV Motor MA 13
Startup type Direct
U 400 V
Mechanical power 18.5 kW
Startup current Id/Ir 7.2
Transient current I’’d/Ir <=19
Ir for sizing 35 A
Sr for sizing 24.2 kVA
Pr for sizing 19.4 kW
cos 0.8
Polarity 3Ph
Number of circuit 2
Ku (mode Normal) 0.8
Harmonic generator No
THDI3 NA %
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 35.000 35.000 35.000 0

Synthesis for all operating mode


(A) 35.000 35.000 35.000 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.980 0.580
UL1L2 (%) 1.131 0.670
UL2L3 (%) 1.131 0.670
Project: bài 1 25/09/2021
Page 38/45

UL3L1 (%) 1.131 0.670


UL1N (%) 0.399 0.000
UL2N (%) 0.399 0.000
UL3N (%) 0.399 0.000

Startup Voltage drop


UStartUp 1.579
3.5.5 Circuit Motor Load 14
Circuit breaker QA 14
Ib NA
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX100F
Circuit breaker rating 100 A
Breaking capacity 36 kA
TNS One pole breaking capacity 36 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation Micrologic 2.2 M
Trip unit rating 50 A
Long delay settings
Ir 30 A
Tr 5s
Short delay settings
Isd current 390 A
Tsd 0.03 s
Instantaneous tripping
Ii current 750 A
Ti current 60 A

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 10bis Total Selectivity
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Contactor LC1D32
Designation LC1D32
Type of coordination T1

Cable WD 14
Parameters
Length 9m
Installation method 70
D1
Multi-core cable in conduit or in cable
Project: bài 1 25/09/2021
Page 39/45

ducting in the ground


Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 29 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-19
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x4 mm²
Core Copper
Iz under real conditions 36 A
Iz’ 36 A
Selected PE
Cross section area 1x4 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 4.99 4.33 NA 2.94 NA 1.81 NA 2.09

Synthesis for all operating mode


(kA) 4.99 4.33 NA 2.94 NA 1.81 NA 2.09

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Asynchronous LV Motor MA 14
Startup type Direct
U 400 V
Mechanical power 15 kW
Startup current Id/Ir 7.2
Transient current I’’d/Ir <=19
Ir for sizing 29 A
Sr for sizing 20.1 kVA
Pr for sizing 16.1 kW
cos 0.8
Polarity 3Ph
Number of circuit 2
Ku (mode Normal) 0.8
Harmonic generator No
THDI3 NA %
Sensitivity to over voltage NA
Project: bài 1 25/09/2021
Page 40/45

Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 29.000 29.000 29.000 0

Synthesis for all operating mode


(A) 29.000 29.000 29.000 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.940 0.541
UL1L2 (%) 1.085 0.625
UL2L3 (%) 1.086 0.625
UL3L1 (%) 1.085 0.625
UL1N (%) 0.399 0.000
UL2N (%) 0.399 0.000
UL3N (%) 0.399 0.000

Startup Voltage drop


UStartUp 1.462
3.5.6 Circuit Motor Load 15
Circuit breaker QA 15
Ib NA
Distance from origin NA

Sizing Information Sized by system


Range Acti9 P25M
Designation P25M
Circuit breaker rating 23 A
Breaking capacity 15 kA
TNS One pole breaking capacity NaN kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation M
Trip unit rating 23 A
Long delay settings
Ir 22 A
Tr NA
Short delay settings
Isd current 327 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 10bis Total Selectivity
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Project: bài 1 25/09/2021


Page 41/45

Contactor LC1D25
Designation LC1D25
Type of coordination T1

Cable WD 15
Parameters
Length 13 m
Installation method 70
D1
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ground temperature 20 °C
Level of third harmonic THDI NA %
Ib 22 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-15
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-19
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x2.5 mm²
Core Copper
Iz under real conditions 28 A
Iz’ 28 A
Selected PE
Cross section area 1x2.5 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 2.44 2.11 NA 1.43 NA 0.84 NA 0.98

Synthesis for all operating mode


(kA) 2.44 2.11 NA 1.43 NA 0.84 NA 0.98

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Project: bài 1 25/09/2021


Page 42/45

Asynchronous LV Motor MA 15
Startup type Direct
U 400 V
Mechanical power 11 kW
Startup current Id/Ir 7.2
Transient current I’’d/Ir <=19
Ir for sizing 22 A
Sr for sizing 15.2 kVA
Pr for sizing 12.2 kW
cos 0.8
Polarity 3Ph
Number of circuit 3
Ku (mode Normal) 0.8
Harmonic generator No
THDI3 NA %
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 22.000 22.000 22.000 0

Synthesis for all operating mode


(A) 22.000 22.000 22.000 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.344 0.945
UL1L2 (%) 1.552 1.091
UL2L3 (%) 1.552 1.091
UL3L1 (%) 1.552 1.091
UL1N (%) 0.399 0.000
UL2N (%) 0.399 0.000
UL3N (%) 0.399 0.000

Startup Voltage drop


UStartUp 2.036

3.6 Busbar circuits


3.6.1 Circuit WC 1
Busbar WC 1
Parameters
Switchboard Name UC 2
Switchboard Range No preference
Rating (A) NA
IP Undefined
Feeder
Circuit name Protection name Protection type

Feeder circuit 3 QA 3 NSX400F

Feeder circuit 10 QA 10 NSX250B

Feeder circuit 18 QA 18 iC60L

Project: bài 1 25/09/2021


Page 43/45

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 16.32 14.13 15.72 9.96 11.06 11.50 NA 13.32

Synthesis for all operating mode


(kA) 16.32 14.13 15.72 9.96 11.06 11.50 NA 13.32

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

3.6.2 Circuit WC 4
Busbar WC 4
Parameters
Switchboard Name UC 5
Switchboard Range No preference
Rating (A) NA
IP Undefined
Feeder
Circuit name Protection name Protection type

Motor Load 6 QA 6 NSX100F

Motor Load 7 QA 7 NSX100F

Motor Load 8 QA 8 GV4P25B

Load 9 QA 9 iC60L

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 15.24 13.20 13.82 9.38 9.87 10.03 NA 11.61

Synthesis for all operating mode


(kA) 15.24 13.20 13.82 9.38 9.87 10.03 NA 11.61

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

3.6.3 Circuit WC 11
Busbar WC 11
Parameters
Switchboard Name UC 12
Switchboard Range No preference
Rating (A) NA
IP Undefined
Feeder
Project: bài 1 25/09/2021
Page 44/45

Circuit name Protection name Protection type

Motor Load 13 QA 13 NSX100F

Motor Load 14 QA 14 NSX100F

Motor Load 15 QA 15 P25M

Load 16 QA 16 iC60H

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 14.96 12.96 13.27 9.18 9.42 9.28 NA 10.75

Synthesis for all operating mode


(kA) 14.96 12.96 13.27 9.18 9.42 9.28 NA 10.75

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

3.6.4 Circuit WC 19
Busbar WC 19
Parameters
Switchboard Name UC 20
Switchboard Range No preference
Rating (A) NA
IP Undefined
Feeder
Circuit name Protection name Protection type

Load 22 QA 22 iC60L

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 5.74 4.97 3.15 3.38 2.13 2.15 NA 2.49

Synthesis for all operating mode


(kA) 5.74 4.97 3.15 3.38 2.13 2.15 NA 2.49

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Project: bài 1 25/09/2021


Page 45/45

NOTICE
RISK OF INACCURATE DATA RESULTS.

 Configure the software correctly to get accurate reports and/or data results.
 Do not rely solely on software messages and reports to determine if the
system is functioning correctly.
 Make sure that you have entered the correct inputs for the required
components.
 Review the calculated results and solutions provided by the software before
submitting the report.

Failure to follow these instructions can result in incorrect bill of material and
loss of business.