1 Bus Name Protective Bus Bus Bus Prot Dev Prot Dev
2 Device kV Bolted Arcing Bolted Arcing
3 Name Fault Fault Fault Fault
4 (kA) (kA) (kA) (kA)
5 MLTP SWBD MLTP CB 0.415 54.91 29.80 49.85 27.05

6 MV PNL RELAY I/C 11.00 13.62 12.43 13.44 12.26

7 TRI PRI RELAY MAIN 33.00 25.77 25.77 25.71 25.71

8 TRI SEC RELAY MAIN 11.00 13.72 12.51 13.53 12.35

9 TRI-2 PRI RELAY O/G-1 11.00 13.37 12.20 13.19 12.03

10 TRI-2 SEC RELAY O/G-1 0.415 59.17 30.68 54.17 28.09


For additional information
refer to NFPA 70 E,
Standard for Electrical
11 Safety in the Workplace.

12

13

14
H I K L M N O P Q
1 Trip/ Breaker Equip Electrode Box Box Box Gap Arc
2 Delay Opening Type Config Width Height Depth (mm) Flash
3 Time Time/Tol (in) (in) (in) Boundary
4 (sec.) (sec.) (in)
5 0.32 0.0000 PNL VCB 12 14 10 25 116

6 0.3369 0.1000 SWG VCB 30 45 30 152 106

7 0.1 0.1000 SWG VCB 30 45 30 152 336

8 0.6503 0.1000 SWG VCB 30 45 30 152 150

9 0.04 0.1000 SWG VCB 30 45 30 152 51

10 1.9 0.1000 PNL VCB 12 14 10 25 373

11

12

13

14
R S T U V W
1 Working Incident PPE Level / Notes (*N) Label # Cable Length Incident
2 Distance Energy From Trip Device Energy
3 (in) (cal/cm2) (m) at Low
4 Marginal
5 18 23.5 (*N21a) # 0002

6 36 6.47 # 0001

7 36 103.9 (*N_kv) # 0003 110.00

8 36 11.2 # 0004 110.00

9 36 2.05 # 0005 75.00

10 18 151.4 (*N9) # 0006 75.00


#Equip Eval (*N_kv) - Out of IEEE 1584
Failed = 1 Voltage Range, Lee
Equation Used. Consider
11 NESC method to compare.

#Bus Equip (*N9) - Max Arcing Duration


12 Eval Failed = 0 Reached

(*N21a) - Equipment
Evaluation Failed,
OVERDUTIED
PROTECTIVE DEVICE
EQUIPMENT FOUND -
13 Inappropriate to provide
arc-flash hazard results.

IEEE 1584 2018 Bus


Report - Comprehensive
Fault (60% Cleared Fault
Threshold, include Ind.
Motors for 5.0 Cycles, mis-
14 coordination checked
X Y Z AA AB
1 Incident User Notes User Notes2 User Notes3 User Notes4
2 Energy
3 at High
4 Marginal
5
6
7
8
9
10

11

12

13

14