INSPECTION AND TEST PLAN (ITP) For Spacer Dampers

Type Sample

Manufacturer Name:
Plant Location: Contract No. / Project Title:
Equipment/Material Description: Spacer Damper for Twin/Quad Conductors ITP No. : ITP-SD-02
Type of Equipment / Material Elastomer Lined Clamp Review Cycle No :
Bolted Clamp Type Date:
No. of days:

Equipment Technical data (To be filled by the manufacturer):


Rated Voltage (Ur [kVrms]) 110/115/132/230/380kV
Nominal voltage (Um [kV]) To be filled by the manufacturer
Rated Current (A) To be filled by the manufacturer
Rated Frequency (Hz) 60 Hz
Specification: 12-TMSS-01, Rev.02

Applicable Insp. Location Manufacturer’s


Item Tests Description Unit Test Procedure Sample Acceptance Criteria Remarks
Standard Type of Tests Compliance
100 (for 100 to 132kV)
kV 12-TMSS-01 185 (for 230kV)
1 Corona & RIV Clause 7.7.1 of IEC 61854 6 W 300 (for 380kV)
Clause 7.1.3 (a)
dB 40
12-TMSS-01
2 Electrical resistance test MΩ Clause 7.7.2 of IEC 61854 6 W 1 - 20
Clause 7.1.3 (b)
Clamp slip test 12-TMSS-01 Clause 7.5.1 of IEC 61854 >1.5 Nutcracker
3 kN 6
(Longitudinal / axial) Clause 7.1.3 (c) (method A) W >4.5 Cantilever

12-TMSS-01 Clause 7.5.2 of IEC 61854


4 Breakaway bolt test Nm 6 W Design value ± 10 %
Clause 7.1.3 (d)

Clamp bolt tightening 12-TMSS-01 No damage shall occur to


5 Nm Clause 7.5.3 of IEC 61854 6 W
test Clause 7.1.3 (e) clamps and fasteners
No permanent
Simulated short circuit
12-TMSS-01 Clause 7.5.4.1 of IEC deformation due to
6 current test kN 6 W
Clause 7.1.3(f) 61854 compression & tension
forces for 50kA & 63kA
Characterization of the Clause 7.5.5 (method C) of
12-TMSS-01
7 elastic and damping % IEC 61854 6 W ±20%
Clause 7.1.3 (g)
properties (Log
ITP-SD-02 Standards & Specifications Department PAGE 1 OF 3

License=Al Sharif Group & KEC Co. Ltd/SA-881-t Not For Resale ,1/23/2023 8:23:56 PM Saudi Time
INSPECTION AND TEST PLAN (ITP) For Spacer Dampers

Applicable Insp. Location Manufacturer’s


Item Tests Description Unit Test Procedure Sample Acceptance Criteria Remarks
Standard Type of Tests Compliance
decrement method)

Flexibility tests
Longitudinal displacement 12-TMSS-01 Clause 7.5.6 of IEC 61854 ±25mm
8 Vertical displacement mm 6 W
Clause 7.1.3 (h) ±50mm
Transverse displacement ±25mm
Conical displacement 20°
Sub span oscillation Clause 7.5.7.2 of IEC
12-TMSS-01 61854
9 fatigue test (20 million 6 W
Clause 7.1.3(i) Force ≥70% initial value.
cycles at 2 Hz)

Aeolian vibration fatigue Clause 7.5.7.3 of IEC


12-TMSS-01 61854
10 test (100 million cycles at 6 W Force ≥70% initial value.
Clause 7.1.3(i)
20 Hz)
Heat Soak test (for Heat
Resistant Conductors)
Afterwards, the following
tests shall be carried out:

 Simulated short circuit


test
11  Characteristics of °C
12-TMSS-01 Clause 7.1.3 (j) of
3 W As above
Elastic and Damping Clause 7.1.3 (j) 12-TMSS-01
Properties (Log
Decrement Method)
 Clamp slip test
 Fatigue Aeolian
vibration Test
 Fatigue sub-span
oscillation Test

Legend:
W = Witness [by SEC/National Grid SA Engineers. and/or SEC approved 3rd Party Independent Inspection Agency (IIA) Inspector]
RC = Review of Certificates [by SEC/National Grid SA Engineers. and/or SEC approved 3rd Party Independent Inspection Agency (IIA) Inspector]

ITP-SD-02 Standards & Specifications Department PAGE 2 OF 3

License=Al Sharif Group & KEC Co. Ltd/SA-881-t Not For Resale ,1/23/2023 8:23:56 PM Saudi Time
INSPECTION AND TEST PLAN (ITP) For Spacer Dampers

General instructions:
1- Manufacturer’s compliance shall be indicated in front of each test.
2- Approved Data Schedule & final drawings for the equipment / Material shall be attached.
3- Test Procedure & Day-to-day activity schedule shall be attached for approval.
4- The ITP must be duly signed and stamped by manufacturer's authorized personnel.
5- This document is valid for testing after S&SD approval.

Prepared by (Mfr's authorized QC test inspector) Approved by: (Mfr's authorized QA/QC personnel)

Date:

Date:
Manufacturer Stamp

S&SD Approval

ITP-SD-02 Standards & Specifications Department PAGE 3 OF 3

License=Al Sharif Group & KEC Co. Ltd/SA-881-t Not For Resale ,1/23/2023 8:23:56 PM Saudi Time