Mock-up Villa A
15 DECEMBER 2019
REV - 00
Installation calculation report
VILLA A - new
Full
Page 2/77
Content
1 Project description................................................................................................................. 3
1.1 Project general settings ................................................................................................................... 3
3.11 Power socket load circuits ............................................................. Error! Bookmark not defined.
3.14 Busbar trunking system circuits .................................................... Error! Bookmark not defined.
3.15 Busbar trunking system circuits .................................................... Error! Bookmark not defined.
3.16 Lighting Busbar trunking system circuits .................................... Error! Bookmark not defined.
1 Project description
1.1 Project general settings
Installation standard IEC60364
iC60L
DB-GRD 1 Acti9 iC60 - 32 2P1d C Vigi xC60 A
iC60N
DB-A-EL 1 Acti9 iC60 - 32 3P3d C Vigi xC60 A
iC60L
MCC-A-R 1 Multi 9 125 3P3d C Vigi NG125 A
NG125 -
NG125N
DBP-A-M 1 Acti9 iC60 - 32 2P1d C Vigi xC60 A
iC60N
FOR DUMB 1 Acti9 iC60 - 16 2P1d C Vigi iC60 A
WAITER iC60N
2.1.3 Switch
Name Nbr Range Rating (A) Poles RCD RCD class
MCC-A-R 1 Acti 9 100 3P
iSW
3 Calculation notes
Selected phase
Cross section area 1x300 mm²
Core Copper
Project: VILLA A - new 15/12/2019
Page 8/77
Design current
IL1 IL2 IL3 IN
Cable MCC-A-R
Parameters
Length 20 m
Max length NA
Installation method 60
B2
Multi-core cables in conduit in masonry
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 98 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Selected phase
Cross section area 1x50 mm²
Core Copper
Iz under real conditions 126 A
Selected neutral
Cross section area 1x50 mm²
Core Copper
Iz under real conditions 126 A
Selected PE
Cross section area 1x25 mm²
Core Copper
Design current
IL1 IL2 IL3 IN
Cable DBL-A-B
Parameters
Length 45 m
Max length 148 m
Installation method 2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 7A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Project: VILLA A - new 15/12/2019
Page 14/77
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Cable DBP-A-B
Parameters
Length 45 m
Max length 93.1 m
Installation method 2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 24 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 17/77
Selected phase
Cross section area 1x10 mm²
Core Aluminium
Iz under real conditions 33.6 A
Selected neutral
Cross section area 1x10 mm²
Core Aluminium
Iz under real conditions 33.6 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Cable DBL-A-G
Parameters
Length 10 m
Max length 148 m
Installation method 2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 16 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 20/77
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Cable DBP-A-G
Parameters
Length 10 m
Max length 302 m
Installation method 2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 41 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 23/77
Selected phase
Cross section area 1x25 mm²
Core Copper
Iz under real conditions 73 A
Selected neutral
Cross section area 1x25 mm²
Core Copper
Iz under real conditions 73 A
Selected PE
Cross section area 1x16 mm²
Core Copper
Cable DBL-A-F
Parameters
Length 15 m
Max length 148 m
Installation method 2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 20 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 26/77
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Cable DBP-A-F
Parameters
Length 15 m
Max length 148 m
Installation method 2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 14 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 29/77
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Cable LIFT
Parameters
Length 40 m
Max length 118 m
Installation method 2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 8A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 32/77
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Cable DB-A-R
Parameters
Length 25 m
Max length 148 m
Installation method 2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 6A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 35/77
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Cable PAC
Parameters
Length 40 m
Max length 114 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 5
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 26 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 38/77
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 46.7 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 46.7 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Cable ODU-1
Parameters
Length 40 m
Max length 86.3 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 6
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 19 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 41/77
Selected phase
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected neutral
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected PE
Cross section area 1x6 mm²
Core Copper
Cable ODU-1
Parameters
Length 40 m
Max length 86.3 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 6
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 10 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 44/77
Selected phase
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected neutral
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected PE
Cross section area 1x6 mm²
Core Copper
Cable ODU-2
Parameters
Length 40 m
Max length 86.3 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 6
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 19 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 47/77
Selected phase
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected neutral
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected PE
Cross section area 1x6 mm²
Core Copper
Cable ODU-2
Parameters
Length 40 m
Max length 86.3 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 6
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 19 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 50/77
Selected phase
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected neutral
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected PE
Cross section area 1x6 mm²
Core Copper
Cable ODU-3
Parameters
Length 45 m
Max length 86.3 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 6
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 10 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 53/77
Selected phase
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected neutral
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected PE
Cross section area 1x6 mm²
Core Copper
Cable ODU-3
Parameters
Length 45 m
Max length 86.3 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 6
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 19 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 56/77
Selected phase
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected neutral
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected PE
Cross section area 1x6 mm²
Core Copper
Cable ODU-3
Parameters
Length 45 m
Max length 86.3 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 6
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 19 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 59/77
Selected phase
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected neutral
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected PE
Cross section area 1x6 mm²
Core Copper
Cable MCC-PL
Parameters
Length 25 m
Max length 148 m
Installation method 2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 18 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 62/77
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Cable DB-GRD
Parameters
Length 40 m
Max length 50.2 m
Installation method 72
D
Sheathed multi-core cables direct in the
ground without added mechanical
protection
Type of cable Multi-core
Nb of additional touching circuits 1
Insulation XLPE
Ground temperature 25 °C
Level of third harmonic THDI 0%
Ib 11 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.96
Standard table reference A-52-15
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Project: VILLA A - new 15/12/2019
Page 65/77
Selected phase
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 43 A
Selected neutral
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 43 A
Selected PE
Cross section area 1x6 mm²
Core Copper
Cable DB-A-EL
Parameters
Length 40 m
Max length 148 m
Installation method 73
D
Sheathed multi-core cables direct in the
ground with added mechanical protection
Type of cable Multi-core
Nb of additional touching circuits 2
Insulation XLPE
Ground temperature 25 °C
Level of third harmonic THDI 0%
Ib 19 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.96
Standard table reference A-52-15
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 68/77
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Cable DBP-A-M
Parameters
Length 20 m
Max length 50.2 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 15 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 71/77
Selected phase
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 51.7 A
Selected neutral
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 51.7 A
Selected PE
Cross section area 1x6 mm²
Core Copper
Selected phase
Cross section area 1x4 mm²
Core Copper
Iz under real conditions 27.1 A
Selected neutral
Cross section area 1x4 mm²
Core Copper
Iz under real conditions 27.1 A
Selected PE
Cross section area 1x4 mm²
Core Copper