Voltage Drop And Short Circuit Report

Mock-up Villa A
15 DECEMBER 2019
REV - 00
Installation calculation report

VILLA A - new
Full
Page 2/77

Content

1 Project description................................................................................................................. 3
1.1 Project general settings ................................................................................................................... 3

1.2 Settings for wiring device calculation............................................................................................. 3

1.3 List of loads ....................................................................................................................................... 3

2 Installation general design .................................................................................................... 4


2.1 List of devices ................................................................................................................................... 4

3 Calculation notes ................................................................................................................... 7


3.1 Source circuits ...................................................................................... Error! Bookmark not defined.

3.2 Generator circuits ................................................................................. Error! Bookmark not defined.

3.3 LV Source circuits ............................................................................................................................. 7

3.4 UPS circuits ........................................................................................... Error! Bookmark not defined.

3.5 Capacitor bank circuits ........................................................................ Error! Bookmark not defined.

3.6 Feeder circuits ................................................................................................................................. 10

3.7 LV Transformer circuits ........................................................................ Error! Bookmark not defined.

3.8 Couplers circuits ................................................................................... Error! Bookmark not defined.

3.9 Generic load circuits ....................................................................................................................... 13

3.10 Lighting load circuits ...................................................................... Error! Bookmark not defined.

3.11 Power socket load circuits ............................................................. Error! Bookmark not defined.

3.12 Motor starter combination .............................................................. Error! Bookmark not defined.

3.13 Busbar circuits ........................................................................................................................... 76

3.14 Busbar trunking system circuits .................................................... Error! Bookmark not defined.

3.15 Busbar trunking system circuits .................................................... Error! Bookmark not defined.

3.16 Lighting Busbar trunking system circuits .................................... Error! Bookmark not defined.

Project: VILLA A - new 15/12/2019


Page 3/77

1 Project description
1.1 Project general settings
Installation standard IEC60364

Calculation standard TR50480


Circuit breaker standard IEC 60947-2
Frequency 60 Hz

1.2 Settings for wiring device calculation


Maximal CSA 630 mm²

1.3 List of loads


1.3.1 Generic loads
Name Sr (kVA) Pr (kW) Ir (A) Cos Nbr Polarity Non linear load THDi 3 (%)
DBL-A-B 4.71 4 6.79 0.85 1 3Ph+N No 0
DBP-A-B 16.4 13.9 23.6 0.85 1 3Ph+N No 0
DBL-A-G 11 9.3 15.8 0.85 1 3Ph+N No 0
DBP-A- 28.3 24.1 40.9 0.85 1 3Ph+N No 0
G
DBL-A-F 13.7 11.7 19.8 0.85 1 3Ph+N No 0
DBP-A-F 9.8 8.29 14.1 0.85 1 3Ph+N No 0
LIFT 5.88 5 8.49 0.85 1 3Ph+N No 0
DB-A-R 4.09 3.48 5.91 0.85 1 3Ph+N No 0
PAC 18.2 15.5 26.3 0.85 1 3Ph+N No 0
ODU-1 12.8 10.9 18.5 0.85 1 3Ph+N No 0
ODU-1 6.82 5.8 9.8 0.85 1 3Ph+N No 0
ODU-2 13.2 11.2 19 0.85 1 3Ph+N No 0
ODU-2 12.8 10.9 18.5 0.85 1 3Ph+N No 0
ODU-3 6.82 5.8 9.8 0.85 1 3Ph+N No 0
ODU-3 13.2 11.2 19 0.85 1 3Ph+N No 0
ODU-3 12.8 10.9 18.5 0.85 1 3Ph+N No 0
MCC-PL 12.4 10.6 17.9 0.85 1 3Ph+N No 0
DB-GRD 2.47 2.1 10.7 0.85 1 1Ph+N No 0
DB-A-EL 13.2 11.2 19 0.85 1 3Ph+N No 0
DBP-A- 3.51 2.98 15.2 0.85 1 1Ph+N No 0
M
FOR 3.51 2.98 15.2 0.85 1 1Ph+N No 0
DUMB
WAITER

Project: VILLA A - new 15/12/2019


Page 4/77

2 Installation general design


2.1 List of devices

2.1.1 LV switchboards and busbar


Switchboard name Range Rating (A) IP
MDB-A No preference 0.00 Undefined
MCC-A-R No preference 0.00 Undefined

Busbar name Switchboard Ks Polarity SEA Equipotential bounding


name
WC 1 MDB-A 1 3Ph+N TN-S With
MCC-A-R MCC-A-R 1 3Ph+N TN-S Without

2.1.2 Circuit breaker


Name Nbr Range - Rating (A) Poles Trip unit/Curve RCD RCD class
Designation
QA 4 1 Compact 400 4P4d Micrologic 5.3 A
NSX -
NSX400F
DBL-A-B 1 Acti9 iC60 - 32 3P3d C Vigi xC60 A
iC60L
DBP-A-B 1 Acti9 iC60 - 32 3P3d C Vigi xC60 A
iC60L
DBL-A-G 1 Acti9 iC60 - 32 3P3d C Vigi xC60 A
iC60L
DBP-A-G 1 Multi 9 63 3P3d C Vigi NG125 A
NG125 -
NG125N
DBL-A-F 1 Acti9 iC60 - 32 3P3d C Vigi xC60 A
iC60L
DBP-A-F 1 Multi 9 32 3P3d C Vigi NG125 A
NG125 -
NG125N
LIFT 1 Acti9 iC60 - 40 3P3d C Vigi xC60 A
iC60L
DB-A-R 1 Acti9 iC60 - 32 3P3d C Vigi xC60 A
iC60L
PAC 1 Acti9 iC60 - 40 3P3d C Vigi xC60 A
iC60H
ODU-1 1 Acti9 iC60 - 32 4P4d C Vigi xC60 A
iC60H
ODU-1 1 Acti9 iC60 - 32 3P3d C Vigi xC60 A
iC60H
ODU-2 1 Acti9 iC60 - 32 3P3d C Vigi xC60 A
iC60H
ODU-2 1 Acti9 iC60 - 32 3P3d C Vigi xC60 A
iC60H
ODU-3 1 Acti9 iC60 - 32 3P3d C Vigi xC60 A
iC60H
ODU-3 1 Acti9 iC60 - 32 3P3d C Vigi xC60 A
iC60H
ODU-3 1 Acti9 iC60 - 32 3P3d C Vigi xC60 A
iC60H
MCC-PL 1 Acti9 iC60 - 32 3P3d C Vigi xC60 A

Project: VILLA A - new 15/12/2019


Page 5/77

iC60L
DB-GRD 1 Acti9 iC60 - 32 2P1d C Vigi xC60 A
iC60N
DB-A-EL 1 Acti9 iC60 - 32 3P3d C Vigi xC60 A
iC60L
MCC-A-R 1 Multi 9 125 3P3d C Vigi NG125 A
NG125 -
NG125N
DBP-A-M 1 Acti9 iC60 - 32 2P1d C Vigi xC60 A
iC60N
FOR DUMB 1 Acti9 iC60 - 16 2P1d C Vigi iC60 A
WAITER iC60N

2.1.3 Switch
Name Nbr Range Rating (A) Poles RCD RCD class
MCC-A-R 1 Acti 9 100 3P
iSW

2.1.4 Cable schedule

Name Nbr Incomer Feeder Type Insulation L (m) L1/L2/L3 N PE/PEN


ODU-3 1 ODU-3 ODU-3 Multi-core XLPE 45 1x6 Copper 1x6 Copper 1x6 Copper
ODU-3 1 ODU-3 ODU-3 Multi-core XLPE 45 1x6 Copper 1x6 Copper 1x6 Copper
ODU-3 1 ODU-3 ODU-3 Multi-core XLPE 45 1x6 Copper 1x6 Copper 1x6 Copper
DBP- 1 DBP-A- DBP-A- Multi-core XLPE 45 1x10 1x10 1x10
A-B B B Aluminium Aluminium Copper
DBL- 1 DBL-A-B DBL-A-B Multi-core XLPE 45 1x10 1x10 1x10
A-B Copper Copper Copper
DB-A- 1 DB-A-EL DB-A-EL Multi-core XLPE 40 1x10 1x10 1x10
EL Copper Copper Copper
DB- 1 DB-GRD DB-GRD Multi-core XLPE 40 1x6 Copper 1x6 Copper 1x6 Copper
GRD
ODU-2 1 ODU-2 ODU-2 Multi-core XLPE 40 1x6 Copper 1x6 Copper 1x6 Copper
ODU-2 1 ODU-2 ODU-2 Multi-core XLPE 40 1x6 Copper 1x6 Copper 1x6 Copper
ODU-1 1 ODU-1 ODU-1 Multi-core XLPE 40 1x6 Copper 1x6 Copper 1x6 Copper
ODU-1 1 ODU-1 ODU-1 Multi-core XLPE 40 1x6 Copper 1x6 Copper 1x6 Copper
PAC 1 PAC PAC Multi-core XLPE 40 1x10 1x10 1x10
Copper Copper Copper
LIFT 1 LIFT LIFT Multi-core XLPE 40 1x10 1x10 1x10
Copper Copper Copper
FOR 1 FOR FOR Multi-core XLPE 35 1x4 Copper 1x4 Copper 1x4 Copper
DUMB DUMB DUMB
WAITE WAITER WAITER
R
WD 4 1 W4 QA 4 Multi-core Halogen 26 1x300 1x300 1x150
free, 70°C Copper Copper Copper
MCC- 1 MCC-PL MCC-PL Multi-core XLPE 25 1x10 1x10 1x10
PL Copper Copper Copper
DB-A- 1 DB-A-R DB-A-R Multi-core XLPE 25 1x10 1x10 1x10
R Copper Copper Copper
DBP- 1 DBP-A- DBP-A- Multi-core XLPE 20 1x6 Copper 1x6 Copper 1x6 Copper
A-M M M
MCC- 1 MCC-A- MCC-A- Multi-core XLPE 20 1x50 1x50 1x25
A-R R R Copper Copper Copper
DBP- 1 DBP-A- DBP-A- Multi-core XLPE 15 1x10 1x10 1x10
A-F F F Copper Copper Copper
DBL- 1 DBL-A-F DBL-A-F Multi-core XLPE 15 1x10 1x10 1x10
A-F Copper Copper Copper
DBP- 1 DBP-A- DBP-A- Multi-core XLPE 10 1x25 1x25 1x16
Project: VILLA A - new 15/12/2019
Page 6/77

A-G G G Copper Copper Copper


DBL- 1 DBL-A- DBL-A- Multi-core XLPE 10 1x10 1x10 1x10
A-G G G Copper Copper Copper

Project: VILLA A - new 15/12/2019


Page 7/77

3 Calculation notes

3.1 LV Source circuits

3.1.1 Circuit Source 4


LV power supply W4
Connection description
Type of connection Private substation
Ur 400 V
Connection capacity - Ir 300 A
Polarity 3Ph+N
System earthing arrangement TN-S
Equipotential bounding No
Rb (neutral grounding) NA
Ra (mass grounding) NA
Short circuit characteristics
Ik3max 20 kA
Ik1min 8 kA
Ief 10 kA
Ief2min 5 kA
Cos cc 0.3
Cable WD 4
Parameters
Length 26 m
Max length NA
Installation method 72
D
Sheathed multi-core cables direct in the
ground without added mechanical
protection
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation Halogen free, 70°C
Ground temperature 25 °C
Level of third harmonic THDI 0%
Ib 300 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 0.95
Standard table reference A-52-15
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference NA
User correction factor 1
Overall factor 0.95

Selected phase
Cross section area 1x300 mm²
Core Copper
Project: VILLA A - new 15/12/2019
Page 8/77

Iz under real conditions 319 A


Selected neutral
Cross section area 1x300 mm²
Core Copper
Iz under real conditions 319 A
Selected PE
Cross section area 1x150 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 20.00 17.32 9.26 12.02 6.52 0.00 0.00

Synthesis for all operating mode


(kA) 20.00 17.32 9.26 12.02 6.52 0.00 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Circuit breaker QA 4
Ib 300 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX400F
Circuit breaker rating 400 A
Breaking capacity 36 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation Micrologic 5.3 A
Trip unit rating 400 A
Long delay settings
Ir 300 A
Tr 16 s
Short delay settings
Isd current 3000 A
Tsd 0s
Instantaneous tripping
Ii current 4800 A

Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 224.637 228.223 228.223 3.59

Synthesis for all operating mode


(A) 224.637 228.223 228.223 3.59
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.383 0.383

Project: VILLA A - new 15/12/2019


Page 9/77

UL1L2 (%) 1.443 0.443


UL2L3 (%) 1.443 0.443
UL3L1 (%) 1.443 0.443
UL1N (%) 1.383 0.383
UL2N (%) 1.383 0.383
UL3N (%) 1.383 0.383

Project: VILLA A - new 15/12/2019


Page 10/77

3.2 Feeder circuits


3.2.1 Circuit Feeder circuit 7
Circuit breaker MCC-A-R
Ib 97.7 A
Distance from origin NA

Sizing Information Sized by system


Range Multi 9 NG125
Designation NG125N
Circuit breaker rating 125 A
Breaking capacity 25 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation C
Trip unit rating 125 A
Long delay settings
Ir 125 A
Tr NA
Short delay settings
Isd current 1000 A
Tsd NA
Instantaneous tripping
Ii current NA

RCD designation Vigi NG125


Class A
In 3000 mA
Break Time 0.3 s
t 0s
Discrimination NA
Normative required break time [0.00 ; 5.00] s
Normative required sensitivity [0.03 ; 2824.94] mA

Cable MCC-A-R
Parameters
Length 20 m
Max length NA
Installation method 60
B2
Multi-core cables in conduit in masonry
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 98 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1

Project: VILLA A - new 15/12/2019


Page 11/77

Standard table reference A-52-16


Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-17
User correction factor 1
Overall factor 0.82

Selected phase
Cross section area 1x50 mm²
Core Copper
Iz under real conditions 126 A
Selected neutral
Cross section area 1x50 mm²
Core Copper
Iz under real conditions 126 A
Selected PE
Cross section area 1x25 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 16.30 14.12 7.65 8.46 4.69 5.65 0.00

Synthesis for all operating mode


(kA) 16.30 14.12 7.65 8.46 4.69 5.65 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Switch MCC-A-R
Range Acti 9 iSW
Designation iSW
Rating 100 A
Icm (making capacity) 75 kA
Icw 2.5 kA - 1 s.
Cascading with upstream No
circuit breaker
Reinforced short circuit NA
withstand
Pole 3

Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 97.708 97.708 97.708 0

Synthesis for all operating mode


(A) 97.708 97.708 97.708 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.767 0.384
UL1L2 (%) 1.886 0.443
UL2L3 (%) 1.886 0.443
UL3L1 (%) 1.886 0.443

Project: VILLA A - new 15/12/2019


Page 12/77

UL1N (%) 1.767 0.384


UL2N (%) 1.767 0.384
UL3N (%) 1.767 0.384

Project: VILLA A - new 15/12/2019


Page 13/77

3.3 Generic load circuits

3.3.1 Circuit DBL-A-B


Circuit breaker DBL-A-B
Ib 6.79 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60L
Circuit breaker rating 32 A
Breaking capacity 20 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation C
Trip unit rating 32 A
Long delay settings
Ir 32 A
Tr NA
Short delay settings
Isd current 256 A
Tsd NA
Instantaneous tripping
Ii current NA

RCD designation Vigi xC60


Class A
In 500 mA
Break Time 0.03 s
t 0s
Discrimination NA
Normative required break time [0.00 ; 0.20] s
Normative required sensitivity [0.00 ; 498.16] mA

Cable DBL-A-B
Parameters
Length 45 m
Max length 148 m
Installation method 2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 7A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Project: VILLA A - new 15/12/2019
Page 14/77

Temperature factor 0.82


Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-17
User correction factor 1
Overall factor 0.82

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 16.30 14.12 7.65 1.67 0.96 1.00 0.00

Synthesis for all operating mode


(kA) 16.30 14.12 7.65 1.67 0.96 1.00 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge DBL-A-B
U 400 V
S 4.71 kVA
P 4 kW
I 6.79 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 6.792 6.792 6.792 0

Synthesis for all operating mode


(A) 6.792 6.792 6.792 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.657 0.273

Project: VILLA A - new 15/12/2019


Page 15/77

UL1L2 (%) 1.758 0.316


UL2L3 (%) 1.758 0.316
UL3L1 (%) 1.758 0.316
UL1N (%) 1.657 0.273
UL2N (%) 1.657 0.273
UL3N (%) 1.657 0.273

Synthesis for all operating mode


U3L (%) 1.657
UL1L2 (%) 1.758
UL2L3 (%) 1.758
UL3L1 (%) 1.758
UL1N (%) 1.657
UL2N (%) 1.657
UL3N (%) 1.657

Project: VILLA A - new 15/12/2019


Page 16/77

3.3.2 Circuit DBP-A-B


Circuit breaker DBP-A-B
Ib 23.6 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60L
Circuit breaker rating 32 A
Breaking capacity 20 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation C
Trip unit rating 32 A
Long delay settings
Ir 32 A
Tr NA
Short delay settings
Isd current 256 A
Tsd NA
Instantaneous tripping
Ii current NA

RCD designation Vigi xC60


Class A
In 500 mA
Break Time 0.03 s
t 0s
Discrimination NA
Normative required break time [0.00 ; 0.20] s
Normative required sensitivity [0.00 ; 388.01] mA

Cable DBP-A-B
Parameters
Length 45 m
Max length 93.1 m
Installation method 2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 24 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 17/77

Touching conductor factor 1


Standard table reference A-52-17
User correction factor 1
Overall factor 0.82

Selected phase
Cross section area 1x10 mm²
Core Aluminium
Iz under real conditions 33.6 A
Selected neutral
Cross section area 1x10 mm²
Core Aluminium
Iz under real conditions 33.6 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 16.30 14.12 7.65 1.08 0.62 0.78 0.00

Synthesis for all operating mode


(kA) 16.30 14.12 7.65 1.08 0.62 0.78 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge DBP-A-B
U 400 V
S 16.4 kVA
P 13.9 kW
I 23.6 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 23.637 23.637 23.637 0

Synthesis for all operating mode


(A) 23.637 23.637 23.637 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 2.880 1.497
UL1L2 (%) 3.171 1.729
UL2L3 (%) 3.171 1.729
UL3L1 (%) 3.171 1.729
UL1N (%) 2.880 1.497
UL2N (%) 2.880 1.497
UL3N (%) 2.880 1.497
Project: VILLA A - new 15/12/2019
Page 18/77

Synthesis for all operating mode


U3L (%) 2.880
UL1L2 (%) 3.171
UL2L3 (%) 3.171
UL3L1 (%) 3.171
UL1N (%) 2.880
UL2N (%) 2.880
UL3N (%) 2.880

Project: VILLA A - new 15/12/2019


Page 19/77

3.3.3 Circuit DBL-A-G


Circuit breaker DBL-A-G
Ib 15.8 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60L
Circuit breaker rating 32 A
Breaking capacity 20 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation C
Trip unit rating 32 A
Long delay settings
Ir 32 A
Tr NA
Short delay settings
Isd current 256 A
Tsd NA
Instantaneous tripping
Ii current NA

RCD designation Vigi xC60


Class A
In 500 mA
Break Time 0.03 s
t 0s
Discrimination NA
Normative required break time [0.00 ; 0.20] s
Normative required sensitivity [0.00 ; 1971.74] mA

Cable DBL-A-G
Parameters
Length 10 m
Max length 148 m
Installation method 2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 16 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 20/77

Touching conductor factor 1


Standard table reference A-52-17
User correction factor 1
Overall factor 0.82

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 16.30 14.12 7.65 5.71 3.22 3.94 0.00

Synthesis for all operating mode


(kA) 16.30 14.12 7.65 5.71 3.22 3.94 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge DBL-A-G
U 400 V
S 11 kVA
P 9.3 kW
I 15.8 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 15.843 15.843 15.843 0

Synthesis for all operating mode


(A) 15.843 15.843 15.843 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.525 0.142
UL1L2 (%) 1.606 0.164
UL2L3 (%) 1.606 0.164
UL3L1 (%) 1.606 0.164
UL1N (%) 1.525 0.142
UL2N (%) 1.525 0.142
UL3N (%) 1.525 0.142
Project: VILLA A - new 15/12/2019
Page 21/77

Synthesis for all operating mode


U3L (%) 1.525
UL1L2 (%) 1.606
UL2L3 (%) 1.606
UL3L1 (%) 1.606
UL1N (%) 1.525
UL2N (%) 1.525
UL3N (%) 1.525

Project: VILLA A - new 15/12/2019


Page 22/77

3.3.4 Circuit DBP-A-G


Circuit breaker DBP-A-G
Ib 40.9 A
Distance from origin NA

Sizing Information Sized by system


Range Multi 9 NG125
Designation NG125N
Circuit breaker rating 63 A
Breaking capacity 25 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation C
Trip unit rating 63 A
Long delay settings
Ir 63 A
Tr NA
Short delay settings
Isd current 504 A
Tsd NA
Instantaneous tripping
Ii current NA

RCD designation Vigi NG125


Class A
In 300 mA
Break Time 0.03 s
t 0s
Discrimination NA
Normative required break time [0.00 ; 5.00] s
Normative required sensitivity [0.00 ; 3200.76] mA

Cable DBP-A-G
Parameters
Length 10 m
Max length 302 m
Installation method 2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 41 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 23/77

Touching conductor factor 1


Standard table reference A-52-17
User correction factor 1
Overall factor 0.82

Selected phase
Cross section area 1x25 mm²
Core Copper
Iz under real conditions 73 A
Selected neutral
Cross section area 1x25 mm²
Core Copper
Iz under real conditions 73 A
Selected PE
Cross section area 1x16 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 16.30 14.12 7.65 8.73 4.84 6.40 0.00

Synthesis for all operating mode


(kA) 16.30 14.12 7.65 8.73 4.84 6.40 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge DBP-A-G
U 400 V
S 28.3 kVA
P 24.1 kW
I 40.9 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 40.907 40.907 40.907 0

Synthesis for all operating mode


(A) 40.907 40.907 40.907 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.535 0.152
UL1L2 (%) 1.618 0.175
UL2L3 (%) 1.618 0.175
UL3L1 (%) 1.618 0.175
UL1N (%) 1.535 0.152
UL2N (%) 1.535 0.152
UL3N (%) 1.535 0.152
Project: VILLA A - new 15/12/2019
Page 24/77

Synthesis for all operating mode


U3L (%) 1.535
UL1L2 (%) 1.618
UL2L3 (%) 1.618
UL3L1 (%) 1.618
UL1N (%) 1.535
UL2N (%) 1.535
UL3N (%) 1.535

Project: VILLA A - new 15/12/2019


Page 25/77

3.3.5 Circuit DBL-A-F


Circuit breaker DBL-A-F
Ib 19.8 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60L
Circuit breaker rating 32 A
Breaking capacity 20 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation C
Trip unit rating 32 A
Long delay settings
Ir 32 A
Tr NA
Short delay settings
Isd current 256 A
Tsd NA
Instantaneous tripping
Ii current NA

RCD designation Vigi xC60


Class A
In 500 mA
Break Time 0.03 s
t 0s
Discrimination NA
Normative required break time [0.00 ; 0.20] s
Normative required sensitivity [0.00 ; 1392.43] mA

Cable DBL-A-F
Parameters
Length 15 m
Max length 148 m
Installation method 2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 20 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 26/77

Touching conductor factor 1


Standard table reference A-52-17
User correction factor 1
Overall factor 0.82

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 16.30 14.12 7.65 4.29 2.44 2.78 0.00

Synthesis for all operating mode


(kA) 16.30 14.12 7.65 4.29 2.44 2.78 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge DBL-A-F
U 400 V
S 13.7 kVA
P 11.7 kW
I 19.8 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 19.834 19.834 19.834 0

Synthesis for all operating mode


(A) 19.834 19.834 19.834 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.649 0.266
UL1L2 (%) 1.750 0.307
UL2L3 (%) 1.750 0.307
UL3L1 (%) 1.750 0.307
UL1N (%) 1.649 0.266
UL2N (%) 1.649 0.266
UL3N (%) 1.649 0.266
Project: VILLA A - new 15/12/2019
Page 27/77

Synthesis for all operating mode


U3L (%) 1.649
UL1L2 (%) 1.750
UL2L3 (%) 1.750
UL3L1 (%) 1.750
UL1N (%) 1.649
UL2N (%) 1.649
UL3N (%) 1.649

Project: VILLA A - new 15/12/2019


Page 28/77

3.3.6 Circuit DBP-A-F


Circuit breaker DBP-A-F
Ib 14.1 A
Distance from origin NA

Sizing Information Sized by system


Range Multi 9 NG125
Designation NG125N
Circuit breaker rating 32 A
Breaking capacity 25 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation C
Trip unit rating 32 A
Long delay settings
Ir 32 A
Tr NA
Short delay settings
Isd current 256 A
Tsd NA
Instantaneous tripping
Ii current NA

RCD designation Vigi NG125


Class A
In 300 mA
Break Time 0.03 s
t 0s
Discrimination NA
Normative required break time [0.00 ; 0.20] s
Normative required sensitivity [0.00 ; 1392.43] mA

Cable DBP-A-F
Parameters
Length 15 m
Max length 148 m
Installation method 2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 14 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 29/77

Touching conductor factor 1


Standard table reference A-52-17
User correction factor 1
Overall factor 0.82

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 16.30 14.12 7.65 4.29 2.44 2.78 0.00

Synthesis for all operating mode


(kA) 16.30 14.12 7.65 4.29 2.44 2.78 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge DBP-A-F
U 400 V
S 9.8 kVA
P 8.29 kW
I 14.1 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 14.077 14.077 14.077 0

Synthesis for all operating mode


(A) 14.077 14.077 14.077 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.572 0.189
UL1L2 (%) 1.661 0.218
UL2L3 (%) 1.661 0.218
UL3L1 (%) 1.661 0.218
UL1N (%) 1.572 0.189
UL2N (%) 1.572 0.189
UL3N (%) 1.572 0.189
Project: VILLA A - new 15/12/2019
Page 30/77

Synthesis for all operating mode


U3L (%) 1.572
UL1L2 (%) 1.661
UL2L3 (%) 1.661
UL3L1 (%) 1.661
UL1N (%) 1.572
UL2N (%) 1.572
UL3N (%) 1.572

Project: VILLA A - new 15/12/2019


Page 31/77

3.3.7 Circuit LIFT


Circuit breaker LIFT
Ib 8.49 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60L
Circuit breaker rating 40 A
Breaking capacity 20 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation C
Trip unit rating 40 A
Long delay settings
Ir 40 A
Tr NA
Short delay settings
Isd current 320 A
Tsd NA
Instantaneous tripping
Ii current NA

RCD designation Vigi xC60


Class A
In 500 mA
Break Time 0.03 s
t 0s
Discrimination NA
Normative required break time [0.00 ; 0.20] s
Normative required sensitivity [0.00 ; 558.12] mA

Cable LIFT
Parameters
Length 40 m
Max length 118 m
Installation method 2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 8A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 32/77

Touching conductor factor 1


Standard table reference A-52-17
User correction factor 1
Overall factor 0.82

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 16.30 14.12 7.65 1.86 1.07 1.12 0.00

Synthesis for all operating mode


(kA) 16.30 14.12 7.65 1.86 1.07 1.12 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge LIFT
U 400 V
S 5.88 kVA
P 5 kW
I 8.49 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 8.490 8.490 8.490 0

Synthesis for all operating mode


(A) 8.490 8.490 8.490 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.687 0.304
UL1L2 (%) 1.793 0.351
UL2L3 (%) 1.793 0.351
UL3L1 (%) 1.793 0.351
UL1N (%) 1.687 0.304
UL2N (%) 1.687 0.304
UL3N (%) 1.687 0.304
Project: VILLA A - new 15/12/2019
Page 33/77

Synthesis for all operating mode


U3L (%) 1.687
UL1L2 (%) 1.793
UL2L3 (%) 1.793
UL3L1 (%) 1.793
UL1N (%) 1.687
UL2N (%) 1.687
UL3N (%) 1.687

Project: VILLA A - new 15/12/2019


Page 34/77

3.3.8 Circuit DB-A-S


Circuit breaker DB-A-R
Ib 5.91 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60L
Circuit breaker rating 32 A
Breaking capacity 20 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation C
Trip unit rating 32 A
Long delay settings
Ir 32 A
Tr NA
Short delay settings
Isd current 256 A
Tsd NA
Instantaneous tripping
Ii current NA

RCD designation Vigi xC60


Class A
In 500 mA
Break Time 0.03 s
t 0s
Discrimination NA
Normative required break time [0.00 ; 0.20] s
Normative required sensitivity [0.00 ; 872.63] mA

Cable DB-A-R
Parameters
Length 25 m
Max length 148 m
Installation method 2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 6A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 35/77

Touching conductor factor 1


Standard table reference A-52-17
User correction factor 1
Overall factor 0.82

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 16.30 14.12 7.65 2.83 1.62 1.75 0.00

Synthesis for all operating mode


(kA) 16.30 14.12 7.65 2.83 1.62 1.75 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge DB-A-R
U 400 V
S 4.09 kVA
P 3.48 kW
I 5.91 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 5.909 5.909 5.909 0

Synthesis for all operating mode


(A) 5.909 5.909 5.909 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.515 0.132
UL1L2 (%) 1.595 0.152
UL2L3 (%) 1.595 0.152
UL3L1 (%) 1.595 0.152
UL1N (%) 1.515 0.132
UL2N (%) 1.515 0.132
UL3N (%) 1.515 0.132
Project: VILLA A - new 15/12/2019
Page 36/77

Synthesis for all operating mode


U3L (%) 1.515
UL1L2 (%) 1.595
UL2L3 (%) 1.595
UL3L1 (%) 1.595
UL1N (%) 1.515
UL2N (%) 1.515
UL3N (%) 1.515

Project: VILLA A - new 15/12/2019


Page 37/77

3.3.9 Circuit PAC


Circuit breaker PAC
Ib 26.3 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60H
Circuit breaker rating 40 A
Breaking capacity 15 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation C
Trip unit rating 40 A
Long delay settings
Ir 40 A
Tr NA
Short delay settings
Isd current 320 A
Tsd NA
Instantaneous tripping
Ii current NA

RCD designation Vigi xC60


Class A
In 500 mA
Break Time 0.03 s
t 0s
Discrimination NA
Normative required break time [0.00 ; 0.20] s
Normative required sensitivity [0.00 ; 487.04] mA

Cable PAC
Parameters
Length 40 m
Max length 114 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 5
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 26 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 38/77

Touching conductor factor 0.76


Standard table reference A-52-20
User correction factor 1
Overall factor 0.623

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 46.7 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 46.7 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 12.14 10.52 5.81 1.70 0.98 0.97 0.00

Synthesis for all operating mode


(kA) 12.14 10.52 5.81 1.70 0.98 0.97 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge PAC
U 400 V
S 18.2 kVA
P 15.5 kW
I 26.3 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 26.320 26.320 26.320 0

Synthesis for all operating mode


(A) 26.320 26.320 26.320 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 2.708 0.941
UL1L2 (%) 2.972 1.087
UL2L3 (%) 2.972 1.087
UL3L1 (%) 2.972 1.087
UL1N (%) 2.708 0.941
UL2N (%) 2.708 0.941
UL3N (%) 2.708 0.941
Project: VILLA A - new 15/12/2019
Page 39/77

Synthesis for all operating mode


U3L (%) 2.708
UL1L2 (%) 2.972
UL2L3 (%) 2.972
UL3L1 (%) 2.972
UL1N (%) 2.708
UL2N (%) 2.708
UL3N (%) 2.708

Project: VILLA A - new 15/12/2019


Page 40/77

3.3.10 Circuit ODU-1


Circuit breaker ODU-1
Ib 18.5 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60H
Circuit breaker rating 32 A
Breaking capacity 15 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 32 A
Long delay settings
Ir 32 A
Tr NA
Short delay settings
Isd current 256 A
Tsd NA
Instantaneous tripping
Ii current NA

RCD designation Vigi xC60


Class A
In 500 mA
Break Time 0.03 s
t 0s
Discrimination NA
Normative required break time [0.00 ; 0.20] s
Normative required sensitivity [0.00 ; 312.49] mA

Cable ODU-1
Parameters
Length 40 m
Max length 86.3 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 6
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 19 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 41/77

Touching conductor factor 0.73


Standard table reference A-52-20
User correction factor 1
Overall factor 0.599

Selected phase
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected neutral
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected PE
Cross section area 1x6 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 12.14 10.52 5.81 1.09 0.63 0.62 0.00

Synthesis for all operating mode


(kA) 12.14 10.52 5.81 1.09 0.63 0.62 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge ODU-1
U 400 V
S 12.8 kVA
P 10.9 kW
I 18.5 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 18.509 18.509 18.509 0

Synthesis for all operating mode


(A) 18.509 18.509 18.509 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 2.859 1.092
UL1L2 (%) 3.147 1.261
UL2L3 (%) 3.147 1.261
UL3L1 (%) 3.147 1.261
UL1N (%) 2.859 1.092
UL2N (%) 2.859 1.092
UL3N (%) 2.859 1.092
Project: VILLA A - new 15/12/2019
Page 42/77

Synthesis for all operating mode


U3L (%) 2.859
UL1L2 (%) 3.147
UL2L3 (%) 3.147
UL3L1 (%) 3.147
UL1N (%) 2.859
UL2N (%) 2.859
UL3N (%) 2.859

Project: VILLA A - new 15/12/2019


Page 43/77

3.3.11 Circuit ODU-1


Circuit breaker ODU-1
Ib 9.8 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60H
Circuit breaker rating 32 A
Breaking capacity 15 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation C
Trip unit rating 32 A
Long delay settings
Ir 32 A
Tr NA
Short delay settings
Isd current 256 A
Tsd NA
Instantaneous tripping
Ii current NA

RCD designation Vigi xC60


Class A
In 500 mA
Break Time 0.03 s
t 0s
Discrimination NA
Normative required break time [0.00 ; 0.20] s
Normative required sensitivity [0.00 ; 312.49] mA

Cable ODU-1
Parameters
Length 40 m
Max length 86.3 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 6
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 10 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 44/77

Touching conductor factor 0.73


Standard table reference A-52-20
User correction factor 1
Overall factor 0.599

Selected phase
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected neutral
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected PE
Cross section area 1x6 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 12.14 10.52 5.81 1.09 0.63 0.62 0.00

Synthesis for all operating mode


(kA) 12.14 10.52 5.81 1.09 0.63 0.62 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge ODU-1
U 400 V
S 6.82 kVA
P 5.8 kW
I 9.8 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 9.849 9.849 9.849 0

Synthesis for all operating mode


(A) 9.849 9.849 9.849 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 2.348 0.581
UL1L2 (%) 2.557 0.671
UL2L3 (%) 2.557 0.671
UL3L1 (%) 2.557 0.671
UL1N (%) 2.348 0.581
UL2N (%) 2.348 0.581
UL3N (%) 2.348 0.581
Project: VILLA A - new 15/12/2019
Page 45/77

Synthesis for all operating mode


U3L (%) 2.348
UL1L2 (%) 2.557
UL2L3 (%) 2.557
UL3L1 (%) 2.557
UL1N (%) 2.348
UL2N (%) 2.348
UL3N (%) 2.348

Project: VILLA A - new 15/12/2019


Page 46/77

3.3.12 Circuit ODU-2


Circuit breaker ODU-2
Ib 19 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60H
Circuit breaker rating 32 A
Breaking capacity 15 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation C
Trip unit rating 32 A
Long delay settings
Ir 32 A
Tr NA
Short delay settings
Isd current 256 A
Tsd NA
Instantaneous tripping
Ii current NA

RCD designation Vigi xC60


Class A
In 500 mA
Break Time 0.03 s
t 0s
Discrimination NA
Normative required break time [0.00 ; 0.20] s
Normative required sensitivity [0.00 ; 312.49] mA

Cable ODU-2
Parameters
Length 40 m
Max length 86.3 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 6
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 19 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 47/77

Touching conductor factor 0.73


Standard table reference A-52-20
User correction factor 1
Overall factor 0.599

Selected phase
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected neutral
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected PE
Cross section area 1x6 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 12.14 10.52 5.81 1.09 0.63 0.62 0.00

Synthesis for all operating mode


(kA) 12.14 10.52 5.81 1.09 0.63 0.62 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge ODU-2
U 400 V
S 13.2 kVA
P 11.2 kW
I 19 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 19.019 19.019 19.019 0

Synthesis for all operating mode


(A) 19.019 19.019 19.019 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 2.889 1.122
UL1L2 (%) 3.182 1.296
UL2L3 (%) 3.182 1.296
UL3L1 (%) 3.182 1.296
UL1N (%) 2.889 1.122
UL2N (%) 2.889 1.122
UL3N (%) 2.889 1.122
Project: VILLA A - new 15/12/2019
Page 48/77

Synthesis for all operating mode


U3L (%) 2.889
UL1L2 (%) 3.182
UL2L3 (%) 3.182
UL3L1 (%) 3.182
UL1N (%) 2.889
UL2N (%) 2.889
UL3N (%) 2.889

Project: VILLA A - new 15/12/2019


Page 49/77

3.3.13 Circuit ODU-2


Circuit breaker ODU-2
Ib 18.5 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60H
Circuit breaker rating 32 A
Breaking capacity 15 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation C
Trip unit rating 32 A
Long delay settings
Ir 32 A
Tr NA
Short delay settings
Isd current 256 A
Tsd NA
Instantaneous tripping
Ii current NA

RCD designation Vigi xC60


Class A
In 500 mA
Break Time 0.03 s
t 0s
Discrimination NA
Normative required break time [0.00 ; 0.20] s
Normative required sensitivity [0.00 ; 312.49] mA

Cable ODU-2
Parameters
Length 40 m
Max length 86.3 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 6
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 19 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 50/77

Touching conductor factor 0.73


Standard table reference A-52-20
User correction factor 1
Overall factor 0.599

Selected phase
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected neutral
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected PE
Cross section area 1x6 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 12.14 10.52 5.81 1.09 0.63 0.62 0.00

Synthesis for all operating mode


(kA) 12.14 10.52 5.81 1.09 0.63 0.62 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge ODU-2
U 400 V
S 12.8 kVA
P 10.9 kW
I 18.5 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 18.509 18.509 18.509 0

Synthesis for all operating mode


(A) 18.509 18.509 18.509 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 2.859 1.092
UL1L2 (%) 3.147 1.261
UL2L3 (%) 3.147 1.261
UL3L1 (%) 3.147 1.261
UL1N (%) 2.859 1.092
UL2N (%) 2.859 1.092
UL3N (%) 2.859 1.092
Project: VILLA A - new 15/12/2019
Page 51/77

Synthesis for all operating mode


U3L (%) 2.859
UL1L2 (%) 3.147
UL2L3 (%) 3.147
UL3L1 (%) 3.147
UL1N (%) 2.859
UL2N (%) 2.859
UL3N (%) 2.859

Project: VILLA A - new 15/12/2019


Page 52/77

3.3.14 Circuit ODU-3


Circuit breaker ODU-3
Ib 9.8 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60H
Circuit breaker rating 32 A
Breaking capacity 15 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation C
Trip unit rating 32 A
Long delay settings
Ir 32 A
Tr NA
Short delay settings
Isd current 256 A
Tsd NA
Instantaneous tripping
Ii current NA

RCD designation Vigi xC60


Class A
In 500 mA
Break Time 0.03 s
t 0s
Discrimination NA
Normative required break time [0.00 ; 0.20] s
Normative required sensitivity [0.00 ; 280.91] mA

Cable ODU-3
Parameters
Length 45 m
Max length 86.3 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 6
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 10 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 53/77

Touching conductor factor 0.73


Standard table reference A-52-20
User correction factor 1
Overall factor 0.599

Selected phase
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected neutral
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected PE
Cross section area 1x6 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 12.14 10.52 5.81 0.98 0.56 0.56 0.00

Synthesis for all operating mode


(kA) 12.14 10.52 5.81 0.98 0.56 0.56 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge ODU-3
U 400 V
S 6.82 kVA
P 5.8 kW
I 9.8 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 9.849 9.849 9.849 0

Synthesis for all operating mode


(A) 9.849 9.849 9.849 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 2.421 0.654
UL1L2 (%) 2.641 0.755
UL2L3 (%) 2.641 0.755
UL3L1 (%) 2.641 0.755
UL1N (%) 2.421 0.654
UL2N (%) 2.421 0.654
UL3N (%) 2.421 0.654
Project: VILLA A - new 15/12/2019
Page 54/77

Synthesis for all operating mode


U3L (%) 2.421
UL1L2 (%) 2.641
UL2L3 (%) 2.641
UL3L1 (%) 2.641
UL1N (%) 2.421
UL2N (%) 2.421
UL3N (%) 2.421

Project: VILLA A - new 15/12/2019


Page 55/77

3.3.15 Circuit ODU-3


Circuit breaker ODU-3
Ib 19 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60H
Circuit breaker rating 32 A
Breaking capacity 15 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation C
Trip unit rating 32 A
Long delay settings
Ir 32 A
Tr NA
Short delay settings
Isd current 256 A
Tsd NA
Instantaneous tripping
Ii current NA

RCD designation Vigi xC60


Class A
In 500 mA
Break Time 0.03 s
t 0s
Discrimination NA
Normative required break time [0.00 ; 0.20] s
Normative required sensitivity [0.00 ; 280.91] mA

Cable ODU-3
Parameters
Length 45 m
Max length 86.3 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 6
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 19 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 56/77

Touching conductor factor 0.73


Standard table reference A-52-20
User correction factor 1
Overall factor 0.599

Selected phase
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected neutral
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected PE
Cross section area 1x6 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 12.14 10.52 5.81 0.98 0.56 0.56 0.00

Synthesis for all operating mode


(kA) 12.14 10.52 5.81 0.98 0.56 0.56 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge ODU-3
U 400 V
S 13.2 kVA
P 11.2 kW
I 19 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 19.019 19.019 19.019 0

Synthesis for all operating mode


(A) 19.019 19.019 19.019 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 3.030 1.263
UL1L2 (%) 3.344 1.458
UL2L3 (%) 3.344 1.458
UL3L1 (%) 3.344 1.458
UL1N (%) 3.030 1.263
UL2N (%) 3.030 1.263
UL3N (%) 3.030 1.263
Project: VILLA A - new 15/12/2019
Page 57/77

Synthesis for all operating mode


U3L (%) 3.030
UL1L2 (%) 3.344
UL2L3 (%) 3.344
UL3L1 (%) 3.344
UL1N (%) 3.030
UL2N (%) 3.030
UL3N (%) 3.030

Project: VILLA A - new 15/12/2019


Page 58/77

3.3.16 Circuit ODU-3


Circuit breaker ODU-3
Ib 18.5 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60H
Circuit breaker rating 32 A
Breaking capacity 15 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation C
Trip unit rating 32 A
Long delay settings
Ir 32 A
Tr NA
Short delay settings
Isd current 256 A
Tsd NA
Instantaneous tripping
Ii current NA

RCD designation Vigi xC60


Class A
In 500 mA
Break Time 0.03 s
t 0s
Discrimination NA
Normative required break time [0.00 ; 0.20] s
Normative required sensitivity [0.00 ; 280.91] mA

Cable ODU-3
Parameters
Length 45 m
Max length 86.3 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 6
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 19 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 59/77

Touching conductor factor 0.73


Standard table reference A-52-20
User correction factor 1
Overall factor 0.599

Selected phase
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected neutral
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 32.3 A
Selected PE
Cross section area 1x6 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 12.14 10.52 5.81 0.98 0.56 0.56 0.00

Synthesis for all operating mode


(kA) 12.14 10.52 5.81 0.98 0.56 0.56 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge ODU-3
U 400 V
S 12.8 kVA
P 10.9 kW
I 18.5 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 18.509 18.509 18.509 0

Synthesis for all operating mode


(A) 18.509 18.509 18.509 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 2.996 1.229
UL1L2 (%) 3.305 1.419
UL2L3 (%) 3.305 1.419
UL3L1 (%) 3.305 1.419
UL1N (%) 2.996 1.229
UL2N (%) 2.996 1.229
UL3N (%) 2.996 1.229
Project: VILLA A - new 15/12/2019
Page 60/77

Synthesis for all operating mode


U3L (%) 2.996
UL1L2 (%) 3.305
UL2L3 (%) 3.305
UL3L1 (%) 3.305
UL1N (%) 2.996
UL2N (%) 2.996
UL3N (%) 2.996

Project: VILLA A - new 15/12/2019


Page 61/77

3.3.17 Circuit MCC-PL


Circuit breaker MCC-PL
Ib 17.9 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60L
Circuit breaker rating 32 A
Breaking capacity 20 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation C
Trip unit rating 32 A
Long delay settings
Ir 32 A
Tr NA
Short delay settings
Isd current 256 A
Tsd NA
Instantaneous tripping
Ii current NA

RCD designation Vigi xC60


Class A
In 500 mA
Break Time 0.03 s
t 0s
Discrimination NA
Normative required break time [0.00 ; 0.20] s
Normative required sensitivity [0.00 ; 872.63] mA

Cable MCC-PL
Parameters
Length 25 m
Max length 148 m
Installation method 2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 18 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 62/77

Touching conductor factor 1


Standard table reference A-52-17
User correction factor 1
Overall factor 0.82

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41.8 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 16.30 14.12 7.65 2.83 1.62 1.75 0.00

Synthesis for all operating mode


(kA) 16.30 14.12 7.65 2.83 1.62 1.75 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge MCC-PL
U 400 V
S 12.4 kVA
P 10.6 kW
I 17.9 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 17.915 17.915 17.915 0

Synthesis for all operating mode


(A) 17.915 17.915 17.915 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.784 0.400
UL1L2 (%) 1.905 0.462
UL2L3 (%) 1.905 0.462
UL3L1 (%) 1.905 0.462
UL1N (%) 1.784 0.400
UL2N (%) 1.784 0.400
UL3N (%) 1.784 0.400
Project: VILLA A - new 15/12/2019
Page 63/77

Synthesis for all operating mode


U3L (%) 1.784
UL1L2 (%) 1.905
UL2L3 (%) 1.905
UL3L1 (%) 1.905
UL1N (%) 1.784
UL2N (%) 1.784
UL3N (%) 1.784

Project: VILLA A - new 15/12/2019


Page 64/77

3.3.18 Circuit DB-GRD


Circuit breaker DB-GRD
Ib 10.7 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60N
Circuit breaker rating 32 A
Breaking capacity 10 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 2P1d
Trip unit designation C
Trip unit rating 32 A
Long delay settings
Ir 32 A
Tr NA
Short delay settings
Isd current 256 A
Tsd NA
Instantaneous tripping
Ii current NA

RCD designation Vigi xC60


Class A
In 500 mA
Break Time 0.03 s
t 0s
Discrimination NA
Normative required break time [0.00 ; 0.40] s
Normative required sensitivity [0.00 ; 340.24] mA

Cable DB-GRD
Parameters
Length 40 m
Max length 50.2 m
Installation method 72
D
Sheathed multi-core cables direct in the
ground without added mechanical
protection
Type of cable Multi-core
Nb of additional touching circuits 1
Insulation XLPE
Ground temperature 25 °C
Level of third harmonic THDI 0%
Ib 11 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.96
Standard table reference A-52-15
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Project: VILLA A - new 15/12/2019
Page 65/77

Standard table reference D-52-1


Touching conductor factor 0.8
Standard table reference A-52-18
User correction factor 1
Overall factor 0.768

Selected phase
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 43 A
Selected neutral
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 43 A
Selected PE
Cross section area 1x6 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 16.30 14.12 7.65 1.15 0.66 0.68 0.00

Synthesis for all operating mode


(kA) 16.30 14.12 7.65 1.15 0.66 0.68 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge DB-GRD
U 400 V
S 2.47 kVA
P 2.1 kW
I 10.7 A
cos 0.85
Polarity 1Ph+N
Phase connection L1-N
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 10.698 0.000 0.000 10.7

Synthesis for all operating mode


(A) 10.698 0.000 0.000 10.7
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 2.015 0.631
UL1L2 (%) 1.443 0.000
UL2L3 (%) 1.443 0.000
UL3L1 (%) 1.443 0.000
UL1N (%) 2.646 1.263
UL2N (%) 1.383 0.000
Project: VILLA A - new 15/12/2019
Page 66/77

UL3N (%) 1.383 0.000

Synthesis for all operating mode


U3L (%) 2.015
UL1L2 (%) 1.443
UL2L3 (%) 1.443
UL3L1 (%) 1.443
UL1N (%) 2.646
UL2N (%) 1.383
UL3N (%) 1.383

Project: VILLA A - new 15/12/2019


Page 67/77

3.3.19 Circuit DB-A-EL


Circuit breaker DB-A-EL
Ib 19 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60L
Circuit breaker rating 32 A
Breaking capacity 20 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation C
Trip unit rating 32 A
Long delay settings
Ir 32 A
Tr NA
Short delay settings
Isd current 256 A
Tsd NA
Instantaneous tripping
Ii current NA

RCD designation Vigi xC60


Class A
In 500 mA
Break Time 0.03 s
t 0s
Discrimination NA
Normative required break time [0.00 ; 0.20] s
Normative required sensitivity [0.00 ; 558.12] mA

Cable DB-A-EL
Parameters
Length 40 m
Max length 148 m
Installation method 73
D
Sheathed multi-core cables direct in the
ground with added mechanical protection
Type of cable Multi-core
Nb of additional touching circuits 2
Insulation XLPE
Ground temperature 25 °C
Level of third harmonic THDI 0%
Ib 19 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.96
Standard table reference A-52-15
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 68/77

Touching conductor factor 0.7


Standard table reference A-52-18
User correction factor 1
Overall factor 0.672

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 41 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 16.30 14.12 7.65 1.86 1.07 1.12 0.00

Synthesis for all operating mode


(kA) 16.30 14.12 7.65 1.86 1.07 1.12 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge DB-A-EL
U 400 V
S 13.2 kVA
P 11.2 kW
I 19 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 18.985 18.985 18.985 0

Synthesis for all operating mode


(A) 18.985 18.985 18.985 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 2.062 0.679
UL1L2 (%) 2.227 0.784
UL2L3 (%) 2.227 0.784
UL3L1 (%) 2.227 0.784
UL1N (%) 2.062 0.679
UL2N (%) 2.062 0.679
UL3N (%) 2.062 0.679
Project: VILLA A - new 15/12/2019
Page 69/77

Synthesis for all operating mode


U3L (%) 2.062
UL1L2 (%) 2.227
UL2L3 (%) 2.227
UL3L1 (%) 2.227
UL1N (%) 2.062
UL2N (%) 2.062
UL3N (%) 2.062

Project: VILLA A - new 15/12/2019


Page 70/77

3.3.20 Circuit DB-GRD (1)


Circuit breaker DBP-A-M
Ib 15.2 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60N
Circuit breaker rating 32 A
Breaking capacity 10 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 2P1d
Trip unit designation C
Trip unit rating 32 A
Long delay settings
Ir 32 A
Tr NA
Short delay settings
Isd current 256 A
Tsd NA
Instantaneous tripping
Ii current NA

RCD designation Vigi xC60


Class A
In 500 mA
Break Time 0.03 s
t 0s
Discrimination NA
Normative required break time [0.00 ; 0.40] s
Normative required sensitivity [0.00 ; 665.94] mA

Cable DBP-A-M
Parameters
Length 20 m
Max length 50.2 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 15 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 71/77

Touching conductor factor 1


Standard table reference A-52-20
User correction factor 1
Overall factor 0.82

Selected phase
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 51.7 A
Selected neutral
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 51.7 A
Selected PE
Cross section area 1x6 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 16.30 14.12 7.65 2.20 1.26 1.33 0.00

Synthesis for all operating mode


(kA) 16.30 14.12 7.65 2.20 1.26 1.33 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge DBP-A-M
U 400 V
S 3.51 kVA
P 2.98 kW
I 15.2 A
cos 0.85
Polarity 1Ph+N
Phase connection L2-N
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 0.000 15.181 0.000 15.2

Synthesis for all operating mode


(A) 0.000 15.181 0.000 15.2
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.831 0.448
UL1L2 (%) 1.443 0.000
UL2L3 (%) 1.443 0.000
UL3L1 (%) 1.443 0.000
UL1N (%) 1.383 0.000
UL2N (%) 2.279 0.896
UL3N (%) 1.383 0.000
Project: VILLA A - new 15/12/2019
Page 72/77

Synthesis for all operating mode


U3L (%) 1.831
UL1L2 (%) 1.443
UL2L3 (%) 1.443
UL3L1 (%) 1.443
UL1N (%) 1.383
UL2N (%) 2.279
UL3N (%) 1.383

Project: VILLA A - new 15/12/2019


Page 73/77

3.3.21 Circuit DUMB WAITER


Circuit breaker FOR DUMB WAITER
Ib 15.2 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60N
Circuit breaker rating 16 A
Breaking capacity 10 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 2P1d
Trip unit designation C
Trip unit rating 16 A
Long delay settings
Ir 16 A
Tr NA
Short delay settings
Isd current 128 A
Tsd NA
Instantaneous tripping
Ii current NA

RCD designation Vigi iC60


Class A
In 500 mA
Break Time 0.03 s
t 0s
Discrimination NA
Normative required break time [0.00 ; 0.40] s
Normative required sensitivity [0.00 ; 260.62] mA

Cable FOR DUMB WAITER


Parameters
Length 35 m
Max length 68.5 m
Installation method 2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 50 °C
Level of third harmonic THDI 0%
Ib 15 A
Sizing constraint Iz
Sizing Information Sized with In
Correction factors
Temperature factor 0.82
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Project: VILLA A - new 15/12/2019
Page 74/77

Touching conductor factor 1


Standard table reference A-52-17
User correction factor 1
Overall factor 0.82

Selected phase
Cross section area 1x4 mm²
Core Copper
Iz under real conditions 27.1 A
Selected neutral
Cross section area 1x4 mm²
Core Copper
Iz under real conditions 27.1 A
Selected PE
Cross section area 1x4 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 16.30 14.12 7.65 0.89 0.51 0.52 0.00

Synthesis for all operating mode


(kA) 16.30 14.12 7.65 0.89 0.51 0.52 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge FOR DUMB WAITER
U 400 V
S 3.51 kVA
P 2.98 kW
I 15.2 A
cos 0.85
Polarity 1Ph+N
Phase connection L3-N
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 0%
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 0.000 0.000 15.181 15.2

Synthesis for all operating mode


(A) 0.000 0.000 15.181 15.2
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 2.553 1.170
UL1L2 (%) 1.443 0.000
UL2L3 (%) 1.443 0.000
UL3L1 (%) 1.443 0.000
UL1N (%) 1.383 0.000
UL2N (%) 1.383 0.000
UL3N (%) 3.723 2.340
Project: VILLA A - new 15/12/2019
Page 75/77

Synthesis for all operating mode


U3L (%) 2.553
UL1L2 (%) 1.443
UL2L3 (%) 1.443
UL3L1 (%) 1.443
UL1N (%) 1.383
UL2N (%) 1.383
UL3N (%) 3.723

Project: VILLA A - new 15/12/2019


Page 76/77

3.4 Busbar circuits


3.4.1 Circuit WC 1
Busbar WC 1
Parameters
Switchboard Name MDB-A
Switchboard Range No preference
Rating (A) 0
IP Undefined
Feeder
Circuit name Protection name Protection type

DBL-A-B DBL-A-B iC60L


DBP-A-B DBP-A-B iC60L
DBP-A-G DBP-A-G NG125N
DBL-A-G DBL-A-G iC60L
DBL-A-F DBL-A-F iC60L
DBP-A-F DBP-A-F NG125N
LIFT LIFT iC60L
DB-A-S DB-A-R iC60L
DB-A-EL DB-A-EL iC60L
DB-GRD DB-GRD iC60N
MCC-PL MCC-PL iC60L
DUMB WAITER FOR DUMB WAITER iC60N
DB-GRD (1) DBP-A-M iC60N
Feeder circuit 7 MCC-A-R NG125N

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 16.30 14.12 7.65 12.10 6.57 13.9 0.00
8

Synthesis for all operating mode


(kA) 16.30 14.12 7.65 12.10 6.57 13.9 0.00
8

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

3.4.2 Circuit MCC-A-R


Busbar MCC-A-R
Parameters
Switchboard Name MCC-A-R
Switchboard Range No preference
Rating (A) 0
IP Undefined
Feeder
Circuit name Protection name Protection type

ODU-3 ODU-3 iC60H


ODU-3 ODU-3 iC60H
ODU-3 ODU-3 iC60H
Project: VILLA A - new 15/12/2019
Page 77/77

ODU-2 ODU-2 iC60H


ODU-2 ODU-2 iC60H
ODU-1 ODU-1 iC60H
ODU-1 ODU-1 iC60H
PAC PAC iC60H

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Normal


(kA) 12.14 10.52 5.81 8.46 4.69 5.65 0.00

Synthesis for all operating mode


(kA) 12.14 10.52 5.81 8.46 4.69 5.65 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Project: VILLA A - new 15/12/2019