You are on page 1of 1

ARAB CONSULTING ENGINEERS PANEL BOARD SHEET

PROJECT : first floor , smart villa Eng.Mahmoud Khairy PANEL BOARD DB1
VOLTAGE : 380/220 V , 3 Ph , 50 Hz

CCT C. BREAK. WIRE DESCRIPTION VA V.A. PER PHASE D.F. DEMANDCCT C. BREAK. WIRE DESCRIPTION VA V.A. PER PHASE D.F. Demand
P H

P H
No. POLE A mm2 R Y B LOAD No. Pole A mm2 R Y B LOAD
1 R1 1 16 3*2.5 lighting 495 495 0.80 396 2 R4 1 16 3*4 Sockets 1000 1000 0.20 200
3 Y1 1 16 3*2.5 lighting 810 810 0.80 648 4 Y4 1 16 3*4 Sockets 500 500 0.20 100
5 B1 1 16 3*2.5 lighting 405 405 0.80 324 6 B4 1 16 3*4 Sockets 1250 1250 0.20 250
7 R2 1 16 3*2.5 lighting 405 405 0.80 324 8 R5 1 16 3*4 Sockets 500 500 0.20 100
9 Y2 1 16 3*2.5 lighting 450 450 0.80 360 10 Y5 1 16 3*4 Sockets 500 500 0.20 100
11 B2 1 16 3*2.5 lighting 600 600 0.80 480 12 B5 1 16 3*4 Sockets 500 500 0.20 100
13 R3 1 16 3*2.5 lighting 600 600 0.80 480 14 R6 1 16 3*4 Sockets 500 500 0.20 100
15 Y3 1 16 3*2.5 lighting 650 650 0.80 520 16 Y6 1 16 3*4 Sockets 750 750 0.20 150
17 B3 1 16 3*2.5 lighting 650 650 0.80 520 18 B6 1 16 3*4 Sockets 1500 1500 0.20 300
19 B7 1 16 3*4 spare 1500 1500 0.80 1200 20 R7 1 16 3*4 spare 1500 1500 0.20 300
21 22 Y7 1 16 3*4 spare 1500 1500 0.20 300
23 24
25 26
27 28
29 30
31 32
33 34
35 36
37 38
39 40
41 42
TOTAL 6565 5252 TOTAL 10000 2000
TOTAL CONNECTED LOAD [VA] 16565
TOTAL DEMAND LOAD [VA] 7252