Our Design is based on the following Unless other wise mentioned hereinafter :-
* This set of drawing is submitted for your kind approval unless other wise mentioned in Page 3
* All External Incoming & Outgoing are via cables with C.S.A. as per table 1
* All internal conductors for all MCCB/MCB up to 250 Amp. as per table 2
* All Cables and Wires Are Black Except Earthing Green And Yelow
* Main and Distribution bus bars are bare and with C.S.A. as per table 3
* All Wires for all control circuits and for CT connections are as per table 4
A3
Sheet No 6
Name Equipment Symbol Name Equipment Symbol
C
K
Earth Earth
Leakage Leakage
C C
C
R Y B
X KVAR
380
set
R
P.F.R
DPM
380
set
D.M
Sheet No 7
Legend
Pos Position Of this Breaker in the Cells Magnetic Adj Magnetic Adjustable Setting Range
Type this Breaker Belongs to any family or category Dimensions measruing unit (millimeter)
Trip Unit Breaker trip unit thermal , magnetic , or electronic Control Voltage Voltage of control circuit
DPM
3C.T:
400/5A
R,S,T
PE
N
POS P1 P1 P1 P1 P1 P1
Input/Output TR GEN SUB INCOMING OUTGOING OUTGOING OUTGOING
Producer ABB ABB ABB ABB ABB ABB
Type MCCB MCCB MCCB MCCB MCCB MCCB
Poles 3P 3P 3P 3P 3P 3P
In(A) 400 400 630 63 80 160
Icu(KA) 50 50 50 36 36 36
Trip Unit THERMAL-MAGNETIC THERMAL-MAGNETIC THERMAL-MAGNETIC THERMAL-MAGNETIC THERMAL-MAGNETIC THERMAL-MAGNETIC
QTY x1 x1 x1 x6 x3 x2
CONTROL
CIRCUIT
380
set
D.M
1500
1600
N
E
R,S,T
380 VAC , 50 HZ , 5 Wires
PE
N
POS P1 P1 P1 P1 P1 P1
Input/Output TR GEN SUB INCOMING OUTGOING OUTGOING OUTGOING
Producer ABB ABB ABB ABB ABB ABB
Type MCCB MCCB MCCB MCCB MCCB MCCB
Poles 3P 3P 3P 3P 3P 3P
In(A) 630 630 40 63 80 160
Icu(KA) 50 50 36 36 36 36
Trip Unit THERMAL-MAGNETIC THERMAL-MAGNETIC THERMAL-MAGNETIC THERMAL-MAGNETIC THERMAL-MAGNETIC THERMAL-MAGNETIC
QTY x1 x1 x5 x6 x5 x1
CONTROL
CIRCUIT
1500 1600
N
E