Notes

NOTES (CONTN.)
From 18. Load manager and multi-function meters shall have Ethernet IP Communication 1. Loading are specified in kW, unless otherwise noted.
To HVSB -2
CT of TR-**
To HVSB -2

Table - 54
(For Trip)

Solar System
To CCP-**

415V, 3Ph, 4Wire, 50Hz, AC Supply


To AHF-**

Port & shall have measurement parameter as Indicated in the SLD.


To Neut.

2. Indicating lamps shall be of LED cluster type.


(For Trip)

From TR-09 19. All CTs shall be provided with short links. 3. All indicating meters shall be of digital type.
For MV Panels
20. Power Cables indicated are tentative. It will vary as per final cable routing of cable 4. MCB shall have short-circuit rating of 10KA & category shall be 'C'.
Type of tray routing. 5. Power cables shall be of 1100V grade, compacted solid / stranded aluminium/copper conductor, XLPE
Schneider Siemens ABB
3#3.5Cx300 Sq.mm. A2XFY

Breaker 21. Bus bars shall be electrolyic grade E-91 aluminum with current density of 0.8A/sq insulated, PVC extruded inner sheathed, G.I. flat/round steel armoured and FRLS PVC outer sheathed
for Solar system Invertor

mm mounted on non hygroscopic ceramic or resin cast insulators for both type.
Master pact NW with Horizontal as well as for Vertical sections. 6. Power cables upto & including 10 Sq. mm shall be of copper conductor & aluminum conductor for 16 Sq.
3C x 2.5 Sq.mm.2XWY

Busduct No.-07 (BD-07)


7C-2.5 Sq. mm 2XWY

7C-2.5 Sq. mm 2XWY


PCC-***/-*-/CCP-**/C2

PCC-**/-*-/HVSB-2/C4

PCC-**/-*-/HVSB-2/C5
3Cx2.5 Sq.mm.2XWY

3Cx2.5 Sq.mm.2XWY

Micrologic 6.0E with


PCC-**/-*-/AHF-**/C7

PCC-**/-*-/REF-1/C3

(415V, 4000A, TPN, Aluminum Busbar) Incomer 3WL with Emax with 22. All multi-function and digital meters shall have class-1 accuracy. mm and above.
LSIG Power Quality 23. Knee point voltage shall be suitable for 3C - 2.5 YWY cable with length of 80m 7. Three Phase MCCB specified shall have neutral Isolating Link.
(65kA for 1 Sec) ACB’s ETU 45B PR122
measurement with (TO and FRO) Considering CAG14 Relay of AREVA Make. Knee point voltage Vk 8. Power cable sizing are designed with considering total voltage drop of 2 to 3 % cas basis up to PCC and
See Note-37 Harmonics > 2If (Rct + 2RL) and Im < 30mA at Vk/4. total of 5% upto motor/ Equipment during steady state and starting voltage dip of less than 15%.
24. '' * '' Switchgear rating for AHF feeder indicated in respective PCC table is 9. Control cables shall be of 1100V grade, compacted solid / stranded copper conductor, XLPE insulated,
Outgoing Master pact NW with tentative and Power Cable details for AHF feeder shall be size based on current PVC extruded inner sheathed, G.I. Flat/Round steel armoured and FRLS PVC outer sheathed type.
Micrologic 6.0A with 3WL with Emax with rating of AHF decided by M/s. Asahi, Panel Vendor shall provide cable termination 10. Minimum size of control cable shall be 2.5 Sq. mm.
ACB’s
LSIG with Energy ETU 45B PR122
(³ 800A) arrangement suitable for 3#3.5Cx300sq.mm. A2XFY cable. 11. Cables for instrumentation shall be under scope of instrumentation.
SPD SPD Measurement. 25. Outgoing feeder circuit breakers rating are sized on running load of the respective 12. All ACBs & MCCBs shall have Ics = 100% Icu = 100% Icw.
R G A B W (Class-B) R G A B W (Class-B) feeder with 25% de-ration for switchgear rating and cable size is designed based 13. Electrical contractor shall provide the cable tag as per circuit number indicated in the drawing and also
on runing load. make the actual feeder number of switchboard in the cable tag in place of -*-.
TCH EM TCH EM 26. Feeder rating 2000A and above along with Busbar shall be with IP42 & feeder 14. All MCCBs shall have door operating handle with door defeat mechanism / padlocking facility.
ON OFF
ON OFF Table - 56 rating below 2000A shall be with IP54. 15. ACBs / MCCBs from 250A and above shall be provided with microprocessor based O/C, S/C, E/F
VT
27. PCC shall be form 3B type. releases. All MCCBs below 250A shall be provided with thermal magnatic O/C, S/C releases & Earth
59 27 2
230 AC 4A Details of Control supply voltages for Panels 28. Busbar shall be with heat shrinkable, in PCC for colour coded PVC sleeves. Lekage relay (ELR) with CBCT, scuh MCCB feeders shall have shunt trip coil (STC).
SUPPLY 3# 415/Sq. Root(3) / 230 AC 29. 230V AC supply control bus shall be formed from incomer feeder of panel is in 16. Extended rotary operating handle with IP-54 degree of protection shall be provided for each MCCB.
VDG-11 VDG-13
SWITCH 110V / Sq. root (3), SUPPLY SH panel vendor scope. 17. MCCB handle shall be provided with handle position indication for on, off & tripped position condition.
Voltage
N 50VA, CL-1 SWITCH Panel Accessories Remarks 30. Cable termination for Outgoing feeder shall be suitable for the number of cable
T C Aux. CT Rating
3 # 5/1A, CL-1, 15VA N runs indicated in the respect to table 2 & 3.
SH
T C
For AHF-1 ACB tripping – Direct acting releases/ Shunt trip 31. Outgoing feeder circuit breakers rating are indicated as per details furnished by
P1 230V AC M/s. Asahi through email dated on 02.05.18 in the Utility_Eqpt_List_Format for
CS coil
P1 P2 AIS dated on 19.4.18 and cable size is designed based on runing load.
Hooter 3 # 4000/5A, CT Key to symbols
CL-1, 15VA CS ACB – Closing coil 230V AC 32. CCP panel kVAR rating is designed to improve the power factor from 0.92 to 0.99
P2
R Y B lag at LT side.
For MV ACB – Spring Charging motor 230V AC
ACK TEST RESET Load Manager R Y B 33. 4 Pole Breaker is shown for Incomer for considering interlocking with feature
panels
Indications (for all ACB & MCCB feeders) 230V AC Incomer feeder.
0-500V
Load Manager 34. M/s Asahi instructed to consider 250kVA UPS during meeting on 19 & 20 April
VS V
0-500V Space Heater, Panel Lamp etc. 230V AC 2018 even though running load on UPS is more than 250kVA.
Hz 35. Auxiliary supply for load manager shall be tapped from control supply bus of the
VS V
0-5000A
Auxiliary relays/ Protection relays 230V AC panel.
P1 Hz 36. All the load managers/MFM's communication cable shall be looped at brought at
PF kW kWh THD MDI AS A
3 # 4000/5A, CT ACB tripping – Direct acting releases/ Shunt trip at terminal block for energy monitoring.
CL-1, 15VA 0-800A 230V AC
P1 coil 37. Refer PCC number of the respective panel for '**''.
P2 PF kW kWh THD MDI AS A
3 # 800/5A, CT ACB – Closing coil 230V AC 38. ACB/ MCCB s' ON/OFF feedback (potential free contacts) shall be available up to
4000A, 4P,65KA for 1SEC, CL-1, 15VA Other control Box, through which remote/SCADA status can be seen.
ACB (EDO) microprocessor P2 Panels ACB – Spring Charging motor 230V AC 39. Remote trip wiring has to be done up to TB such that remote trip can be performed
M based O/C, S/C, E/F releases through SCADA or remote emergency switch.
230V AC
CC & 230V AC STC Indications (for all ACB & MCCB feeders) 230V AC 40. Each incomer should have emergency button & It is wired in such a fashion that it
(I/C-1)
should trip it's source breaker. (eg PCC incomer's emergency button should trip
800A, 4P,65KA for 1SEC, Space Heater, Panel Lamp etc.. 230V AC
230V AC from UPSDB source transformer's HT breaker)
3Cx4 Sq.mm.2XWY 86 ACB (EDO) microprocessor 41. Each microprocessor base release of ACB/ MCCB should be communicable to
UPSDB** /-*-/PCC-**/P1 M based O/C, S/C, E/F releases CC SCADA through Modbus or TCP IP.
230V AC & 230V AC STC (See Note 33) Table - 51 42. Arc protection relays shall be provided along with require number of arc sensing
P1
4 # 4000/1A, 64R (I/C-2) sensors duly wired up to arc protection relay in LT panels for bus bar arc
CL-PS CT For Power Control Centres protection.
(See Note - 24)
P2 43. All panel shall be powder coated with RAL7032 colour shed.
4000A, 415V, 50 Hz, TPN, Aluminium Busbar with heat Current Type of Draw out type No. of Operating principle of
shrinkable coloured PVC sleeves, 65KA for 1SEC. (BUS-A) (See Note 42) Feeder
rating Breaker facility Poles releases & Protection
1 R G A W 2 R G A 3 R G A W
Electrically Microprocessor
TCH EM TCH EM Incomer 4000A ACB operated drawout 4P BasedO/C, S/C, E/F,
***A, TPN, ACB (MDO) with ***A, TPN, MCCB with ***A, TPN, ACB (MDO) with (EDO) U/V & STC
microprocessor based O/C, S/C, microprocessor based O/C, S/C, microprocessor based O/C, S/C,
E/F releases & 230V AC STC E/F releases & 230V AC STC E/F releases & 230V AC STC Microprocessor
Manually operated
Load Manager Load Manager ³ 800A ACB draw out (MDO)
TP+N BasedO/C, S/C, E/F
0-500V 4A 0-500V & STC
4A Outgoings
VS V VS V
HZ HZ Microprocessor
P1 0-***A P1 0-***A P1 0-***A < 800A MCCB Fixed type TP+N BasedO/C, S/C, E/F Reference drawings
3#***A/ PF KW KWH THD MDI AS A 3#***A/ PF KW KWH THD MDI AS A 3#***A/ AS A
& STC
5A,CL1, 5A,CL1, 5A,CL1,
15VA 15VA 15VA Drawing No. Rev. Reference Drawings/Documents Remarks
P2 P2 P2
E E Utility_Eqpt_List_Format Process equipment list Dated 19/04/2018
2 Asahi
Cable Chart M/s Asahi email dated 02/05/18
LT Cable Gland (Typ)
1#3C-2.5 Sq.mm.2XWY
See Table-2 for Cable detail
See Table-2 for Circuit Nos.

CCP-**/-*-/PCC-**/C8

380910-PQC-101 0 Utility equipment list MM Process


See Table-2 for Cable detail

See Table-2 for Cable detail


See Table-2 for Circuit Nos.

See Table-2 for Circuit Nos.

Cable Details
For Outgoing Feeder
Details, Refer Table - 2 Core & Conductor Insulation Inner Armoured Outer
Size (Sq. mm) (AL / CU) (PVC / XLPE) Sheath (Wire/Strip) Sheath
Aluminum Conductor (Power )
AL. for 16 Sq.mm and above XLPE Extruded PVC Strip Armoured FRLS PVC
Copper Conductor (Power)
CP CP CP CU for 10 Sq.mm and below XLPE Extruded PVC Wire Armoured FRLS PVC
CL-*** KW CL-*** KW CL-*** KW Copper Cable (Control)
RL-*** KW RL-*** KW RL-*** KW
Type - F1

Type - F2

Type - F3

2.5 Sq.mm upto Including 10C XLPE Extruded PVC Wire Armoured FRLS PVC
Feeder

Feeder

Feeder

2.5 Sqmm 12C & above XLPE Extruded PVC Strip Armoured FRLS PVC
Table-1 (PCC-1) GCB SRB
Legend 0 01.06.18 MGA Client Comment's Incorporated &
Ammeter Issued for Bidding
Busbar Details CT Details Range Power Cable / Busduct Breaker Details Symbol Description Symbol Description
Single / P1 28.05.18 MGA Issued For Approval GCB SRB
Total Double Front Outgoing
Total S/C S/C Feeders Current Transformer AS Ammeter Selector Switch Rev Date Drawn Description Ch’k’d App’d
Connected Accuracy VA Size in Incoming Outgoing Incomer Rating Type
SW. BD. NO. Operating Amps Level Type Ratio Amps Circuit Nos. Level
Load (CL) Class Burden Sq. mm Entry Entry Type (A)
Load (kW) (kA) (kA) A Ammeter VS Voltmeter Selector Switch
(kW) Mott MacDonald House
PCC-04 Top Bottom kW kW - Kilo Watt Meter Space Heater 44/45, Street No - 14
Single
(Transformer-09) 2163 1493 4000 65 Al. 4000/1A 1 15 0-4000A Busduct NA ACB 4000 65 Refer Table - 2 MIDC Area, Andheri - East
(Busduct) (Cable) Fronted
V Voltmeter kWH kWH - Kilo Watt Hour Meter
Mumbai, 400093
3#3.5Cx300
Solar System for Bottom Single India
- - 800 65 Al. 800/1A 1 15 0-800A Sq.mm. NA - ACB 800 65 - LM LM - Load Manager 27 - Under Voltage Relay
PCC-04 Cable Fronted 27
A2XFY (VDG-13) T +91 (0)22 3083 5000
R - Red for Run Indication F +91 (0)22 2825 3779
Drawout Version
(ON) W mottmac.com
Table-2, PCC-04 FLOOR MOUNTED TYPE, TEMP PLANT GROUND FLOOR BETWEEN GRID 15 TO 17 & A-B FOR TEMP PLANT POST PROCESS AND UTILITIES EQUIPMENTS (TRANSFOREMR -09) G - Green for Stationary M Motor
Indication
Indication (OFF)
Lamps
A - Amber for Trip Indication EM Emergency Trip / Stop
Sr.No. Feeder Plant Room/Area Equipment Equipment Description Total Total Outgoing Rating Cable Size in Sq.mm CP-Control Panel
R - Red for 'R' Phase ON
Type Description Tag Nos. Conencted Running Client
(Amps.) Y - Yellow for 'Y' Phase ON
Loads
(kW)
Load (kW)
ACB MCCB
B - Blue for 'B' Phase ON
B - Blue for Spring Charged
59
59 - Over Voltage Relay
(VDG-11)
M/s Asahi India Glass Limited
Power
TP+N TP+N Field
Connection
Remarks Mehsana
(Link) (Link) Run Core Size Conductor Circuit No. Hz Frequency Meter
A.1 F2 TEMP Plant Substation UPS-02 250kVA UPS-02 370 300 - 630 2 3.5 300 Al. PCC-04/-*-/UPS-02/P1,P2 CP See Note-31, 34
Busduct
Near Ahmedabad
SPD
A.2 F2 TEMP Plant PDB-02 Power Distribution Board-02 220 174 - 400 2 3.5 300 Al. PCC-04/-*-/PDB-02/P1,P2 CP See Note-25 M
Motor Operated (EDO)
(Drawout type)Circuit Breaker,
SPD- Surge Protection Device Gujarat
(ACB) Air Circuit Breaker HRC Fuse
A.3 F2 TEMP Plant PDB-03 Power Distribution Board-03 453 307 800 - 3 3.5 240 Al. PCC-04/-*-/PDB-03/P1 to P3 CP See Note-25
A.4 F2 TEMP Plant K-503 Air Compressor -5.5 bar (Phase 1) 175 158 - 400 2 3.5 150 Al. PCC-04/-*-/K-503/P1 to P2 CP See Note-25 Control Panel Hooter
CP
Hooter Title
A.5 F2 TEMP Plant
HVAC
MCC-02
HVAC MCC-02 235 212 - 400 2 3.5 300 Al. PCC-04/-*-/HVAC MCC-02/P1,P2 CP See Note-25
kVAR kilo Volt Amp Reactive Push button
Greenfield Automotive Glass Plant
A.6 F1 Water Block FFP Fire Fighting Panel 180 17 - 630 3 3.5 240 Al. PCC-04/-*-/FFP/P1 to P3 CP See Note-25 MCCB - Moulded Case Circuit Power Control Center - 04
Cable Gland Breaker
A.7 F2 TEMP Plant Substation MLDB-03 Main Lighting Distribution Board-03 150 150 - 400 2 3.5 150 Al. PCC-04/-*-/MLDB-03/P1,P2 CP See Note-25 MCB - Miniature Circuit Breaker (PCC-04) for TEMP Plant
A.8 F2 TEMP Plant Substation MPDB-02 Main Power Distribution Board-02 380 175 - 630 2 3.5 300 Al. PCC-04/-*-/MPDB-02/P1,P2 CP See Note-25 MDI Maximum Demand Indication PF Power Factor Meter Electrical Single Line Diagram
A.9 F3 TEMP Plant Substation CCP-09 450kVAR Capacitor Control Panel-09 - - 1000 5 3.5 240 Al. PCC-04/-*-/CCP-09/P1 to P5 CP See Note-25 & 32
CS CS - Control Switch 2 Timer Relay
A.10 F3 TEMP Plant Substation AHF-09 Active Harmonic Filter-09 - - 800 - 3 3.5 300 Al. PCC-04/-*-/AHF-09/P1 to P3 CP See Note-24 CS
THD Total Harmonic Distortion
A.11 F1 - - Spare - - 800 - - - - - - - 86 Master Trip Relay (VAJH-13) Designed N Hingorani Eng check G C Beldar
Illuminated Push Button for
A.12 F1 - - Spare - - 1000 - - - - - - - TCH Trip Circuit Healthy Drawn M Apastamb Coordination S Mardwar
Potential Transformer
A.13 F2 - - Spare - - 250 - - - - - - - ON OFF Dwg check J Melath Approved S Bartakke
A.C. Supply switch
A.14 F2 - - Spare - - 400 - - - - - - - 64R Restricted Earth Fault Scale at A1 Status Rev Security
A.15 F2 - - Spare - - 630 - - - - - - -
F1 Power Feeder with TPN ACB F3
Power Feeder for Capacitor
Feeder
NTS EXE 0 STD
© Mott MacDonald See Note-13
F2 Power Feeder with TPN MCCB CP Control Panel
Drawing Number
This document is issued for the party which commissioned it and for specific purposes connected with the captioned project only. It should not be relied upon by any other party or used for any other purpose.