You are on page 1of 1

Notes

To PCC-**
1. Specification No.380910-ESD-12 & data sheets No.380910-ESD-12-01 form a part of this document.

1#7Cx2.5 Sq.mm.2XWY
2. KVAR meter is shown separately, however the same shall be deleted if the KVAR meter is included in

CCP-**/-*-/PCC-**/C2
FROM PCC-** (SEE NOTE - 9) the APFC relay itself, APFC Relay shall have RS485 / Ethernet communication port.
3. All capacitor feeder shall be provided with MCCB & contactors.
4. The controller should have cascading option i.e. We can switch on the next capacitor bank if set P.F. is
5#3.5Cx240 Sq.mm.A2XFY (SEE NOTE - 10) not able to maintain by one capacitor bank.
PCC-**/-*-/CCP-**/P1 to P5 5. KVAR out put shown in this SLD are effective out put at 415V.Vendor shall decide the capacitor terminal
To PCC-**
(SEE NOTE - 9) voltage after considering the voltage rise due to 7% series reactor.

1#3Cx2.5 Sq.mm.2XWY
6. Contactor shall be suitable for AC6b duty.

CCP-**/-*-/PCC-**/C8
R Y B 4A MCB 0-500V
ON OFF
7. All MCCB's shall have Thermal magnetic based O/C,S/C protection.
VS V 8. Required number of heavy duty exhaust fan with temperature controller shall be provided for proper
Contactor Capacitor 4A MCB ventilation of Panel.Temperature within the panel should not rise more than 70°C to maintained the
Capacitor Bank Rating (kVAR)
Duty Rating (A)
A.C. SUPPLY SH APFCR temperature rise as specified in IEC-61921
50 kVAR 110 A SWITCH 1000A 9. Refer respective Panel number for '**''.
Capacitor Control Panel -01 & 03 (450kVAR)
Load Break 10. Electrical contractor shall provide the cable tag as per circuit number indicated in the drawing and also
25 kVAR 63 A Switch (Located in LAM Plant & TEMP
ETPB 0-1000A Plant Substation, Ground Floor) make the actual feeder number of switchboard in the cable tag in place of -*-.
3#1000/1A kVAR AS A 11. All the capacitor shall be Metalized Polypropylene (MPP), super heavy duty type.
CL-1.0 /7.5VA 12. All the MCCB of 125A and above rating shall be vertically mounted.
1000A, 415V, 3Ph., 4 WIRE, AL. BUSBAR, 50KA FOR 1 SEC.
13. All indicating meters shall be of digital type, 3 Phase with inbuilt selector switch.
14. Printed ferruling with cross reference wiring ferruling shall be used.
A M 1 A M 2 A M 3 A M 4 A M 5 A M 6 A M 7 A 8 A 9 A M 10
M M 15. APFC relay shall be of 8 steps, required number of steps shall be utilized & remaining steps shall be kept
R G A 125A R G A 125A R G A 125A R G A 125A R G A 125A R G A 125A R G A 63A R G A 63A R G A 63A R G A 63A
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB as a spare.
T OFF T OFF T OFF T OFF T OFF T OFF T OFF T OFF T OFF T OFF
16. Drop link type terminals shall be provided for all CT's.
0-125A 0-125A 0-125A 0-125A 0-125A 0-125A 0-60A 0-60A 0-60A 0-60A
AS A AS A AS A AS A AS A AS A AS A AS A AS A AS A
17. All indicating lamps shall be of led cluster type (min. 3LED).
3#125/5A, 3#125/5A, 3#125/5A, 3#125/5A, 3#125/5A, 3#125/5A, 3#125/5A, 3#125/5A, 3#60/5A, 3#60/5A,
CL1,5VA CL1,5VA CL1,5VA CL1,5VA CL1,5VA CL1,5VA CL1,5VA CL1,5VA CL1,5VA CL1,5VA 18. Panel shall be Compartmentalized with IP-31 degree of protection.
19. Each MCCB shall be provided with external rotary handle with Padlocking facility shall be provided for all
MCCB in open & closed position.
20. APFCR Bank required capacity has been calculated based on actual working load on respective
transformer and improving power factor from 0.92 to 0.99 lag.
21. Panel Shall be powder coated with RAL7032 Color shed.
Copper Cable

Copper Cable

Copper Cable

Copper Cable

Copper Cable

Copper Cable

Copper Cable

Copper Cable

Copper Cable

Copper Cable
3#1C Flexible

3#1C Flexible

3#1C Flexible

3#1C Flexible

3#1C Flexible

3#1C Flexible

3#1C Flexible

3#1C Flexible

3#1C Flexible

3#1C Flexible
Reference drawings
Drawing No Rev. Reference Document/drawing Remarks
380910-EIE-0004-01 0 Electrical Single Diagram PCC-02 & 03 -

50KVAR 50KVAR 50KVAR 50KVAR 50KVAR 50KVAR 50KVAR 50KVAR 25KVAR 25KVAR
380910-EIA-0005-01 0 Electrical Single Diagram PCC-04 -
RATING 7% (TYP)
DE-TUNING REACTOR
CONTROL (TYP).
SUPER HEAVY DUTY METALISED
3PH. 50Hz, DELTA CONNECTED

POLY PROPYLENE (MPP)

LOCATED IN CAPACITOR
TYPE CAPACITOR BANK

CAPACITOR BANK#10.
CAPACITOR BANK#3.

CAPACITOR BANK#4.

CAPACITOR BANK#5.

CAPACITOR BANK#6.

CAPACITOR BANK#7.

CAPACITOR BANK#8.

CAPACITOR BANK#9.
CAPACITOR BANK#1.

CAPACITOR BANK#2.

AL.EARTH
BUSBAR
Key to symbols
REFER NOTE-5

LEGEND 0 15.06.18 SBP Issued for Bidding GCB SRB

P1 06.06.18 SBP Issued For Approval GCB SRB


SYMBOL DESCRIPTION
To PCC-03
Rev Date Drawn Description Ch’k’d App’d
VS VOLTMETER SELECTOR SWITCH
1#7Cx2.5 Sq.mm.2XWY

Mott MacDonald House


CCP-**/-*-/PCC-**/C2

V VOLTMETER 44/45, Street No - 14


FROM PCC-03
MIDC Area, Andheri - East
AS AMMETER SELECTOR SWITCH
3#3.5Cx300 Sq.mm.A2XFY
Mumbai, 400093
To PCC-03
PCC-03/-*-/CCP-02/P1 to P3
A AMMETER India
1#3Cx2.5 Sq.mm.2XWY
CCP-02/-*-/PCC-03/C8

ON OFF
R Y B 4A MCB 0-500V T +91 (0)22 3083 5000
VS V
EMERGENCY TRIP PUSH BUTTON F +91 (0)22 2825 3779
Contactor Capacitor 4A MCB ETPB
Capacitor Bank Rating (kVAR)
Duty Rating (A) A.C. SUPPLY SH APFCR W mottmac.com
50 kVAR 110 A
SWITCH
800A T TDDO TIMER (OFF DELAY 0-60 Sec.)
Capacitor Control Panel-02 (350kVAR)
Load Break
25 kVAR 63 A Switch (Located in LAM Plant First FLoor
ETPB 0-800A Between Grid no. 6-8 & A-B) MCCB-MOULDED CASE CIRCUIT
3#800/1A kVAR AS A BREAKER
CL-1.0 /7.5VA Client
MCB- MINIATURE CIRCUIT BREAKER
800A, 415V, 3Ph., 4 WIRE, AL. BUSBAR, 50KA FOR 1 SEC.
1 2 3 4 5 6 7 8
M/s Asahi India Glass Limited
Mehsana
A M A M A M A M A M A M A M A M
R G A 125A R G A 125A R G A 125A R G A 125A R G A 125A R G A 125A R G A 63A R G A 63A LOAD BREAK SWITCH
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
T OFF T OFF T OFF T OFF T OFF T OFF T OFF T OFF

3#125/5A, AS
0-125A
A 3#125/5A, AS
0-125A
A 3#125/5A, AS
0-125A
A 3#125/5A, AS
0-125A
A 3#125/5A, AS
0-125A
A 3#125/5A, AS
0-125A
A 3#60/5A, AS
0-60A
A 3#60/5A, AS
0-60A
A
A M
AUTO MANUAL SELECTOR SWITCH
Near Ahmedabad
CL1,5VA CL1,5VA CL1,5VA CL1,5VA CL1,5VA CL1,5VA CL1,5VA CL1,5VA OFF
Gujarat
APFCR
AUTOMATIC POWER FACTOR
CORRECTION RELAY
Copper Cable

Copper Cable

Copper Cable

Copper Cable

Copper Cable

Copper Cable

Copper Cable

Copper Cable
3#1C Flexible

3#1C Flexible

3#1C Flexible

3#1C Flexible

3#1C Flexible

3#1C Flexible

3#1C Flexible

3#1C Flexible

CURRENT TRANSFORMER (CT) Title

SPACE HEATER Greenfield Automotive Glass Plant


SH

DE-TUNING REACTOR
350kVAR & 450kVAR
CAPACITOR BANK
Capacitor Control Panel - 01 & 03
50KVAR 50KVAR 50KVAR 50KVAR 50KVAR 50KVAR 25KVAR 25KVAR
Electrical Single Line Diagram
CAPACITOR DUTY TYPE
CONTACTOR WITH O/L RELAY WITH
RATING 7% (TYP)
DE-TUNING REACTOR
CONTROL (TYP).
SUPER HEAVY DUTY METALISED
3PH. 50Hz, DELTA CONNECTED

POLY PROPYLENE (MPP)

LOCATED IN CAPACITOR
TYPE CAPACITOR BANK

CAPACITOR BANK#3.

CAPACITOR BANK#4.

CAPACITOR BANK#5.

CAPACITOR BANK#6.
CAPACITOR BANK#1.

CAPACITOR BANK#2.

CAPACITOR BANK#7.

CAPACITOR BANK#8.

AL.EARTH INBUILT SPPR,ON, OFF & TRIP LAMP,


BUSBAR START-STOP PUSH BUTTON
Designed D Kakade Eng check G C Beldar
REFER NOTE-5

R - RED FOR `R' PHASE ON Drawn S Patil Coordination S Maradwar

INDICATION LAMPS
Y - YELLOW FOR `Y' PHASE ON
B - BLUE FOR `B' PHASE ON Dwg check N Hingorani Approved S Bartakke
R - RED FOR RUNNING
INDICATION (ON)
Scale at A2 Status Rev Security
G - GREEN FOR STATIONARY
INDICATION (OFF)
NTS EXE 0 STD
© Mott MacDonald A - AMBER FOR TRIP INDICATION Drawing Number
This document is issued for the party which commissioned it and for specific purposes connected with the captioned project only. It should not be relied upon by any other party or used for any other purpose.
We accept no responsibility for the consequences of this document being relied upon by any other party, or being used for any other purpose, or containing any error or omission which is due to an error or omission in data supplied to us by other parties. 380910-EIB-0112-01
C:\pwlocal\pims03\pat72510\d0246935\380910-EIB-0112-01 (0).dwg Jun 15, 2018 - 5:13PM PAT72510