FIRE DETECTION SYSTEMS

FIRE DETECTORS

Interactive analogue addressable detector


OWMX 95, OMX 95, WMX 95 and IMX 95
to be connected to the
fire control panel FMZ 5000

Product Range of application Your advantages

The interactive analogue address- Interactive analogue addressable Realization of all security concepts
able detectors stand for a new detectors are applied in many diffe- and guarantee of a maximum cus-
standard in the reliable detection rent fields to ensure reliable detec- tomer benefit are given by the fol-
of fires. tion of all classes of fires, e.g.: lowing features of performance:
Sophisticated software algorithms Multi-sensor fire detectors OWMX 95 five detector sensitivity grades/
and intensely enlarged functionali- – production plants algorithms for each duty applied
ties set new standards. – parking garages can be programmed at the central
– canteens control panel
Burning characteristics are identi-
– restaurants
fied in a way that a fire can be the sensitivity of detectors which is
detected reliably. Optical smoke detectors OMX 95 dependent on the ambient con-
– offices ditions at specific times of the day
Many variable possibilities for indi-
– archives is switchable
vidual setting of the detector sen-
– living areas
sitivity as well as several setting automatic self-adjusting quiescent
– store-rooms
modes being dependent on the value of the measuring system to
– museums
time of day guarantee the opti- ensure a constant sensitivity during
mum detector adaptation to the Heat detectors WMX 95 the whole life time
monitored area. For rooms and plants where a
automatic recognition of dirt accu-
rapid temperature increase can be
Various different detector mounting mulation and early maintenance sig-
expected in case of fire or where
bases round off this system, e.g.: nal for effective employment of the
other fire detectors cannot be
– standard detector bases maintenance personnel
applied.
– bases with dual insulator
– motor test stands automatic function monitoring
– relay bases
– store areas including the sensor mechanism for
– waterproof bases
– industrial plants maximum availibility
– mounting bases
– mounting bases for insulators Ionisation smoke detector IMX 95 indicates an alarm through
– store-rooms two red LEDs
The detectors correspond to EN 54,
– places of work
part 5 and 7.
– industrial plants
Function

OWMX 95 WMX 95
The multi-sensor detector OWMX 95 is an optical smoke The WMX DIS is a reliable heat detector meeting high
detector combined with a heat detector in one housing. demands. The ambient temperature and the temperature
The analysis of the measuring signals can be performed of the detector housing are measured by 2 NTC resistors.
applying either the linked mode or the separated mode Under normal conditions these measuring values are
based on smoke or heat by selecting the stages 1-5. This similar. The temperature of the NTC exposed to ambience
guarantees continuous response to many classes of fire. will increase rapidly in case of fire. Therefore, a rapid
A synthesis of high-grade optoelectronic and thermo- temperature increase cannot only be analysed by maxi-
electronic sensor technology and distributed system mum temperature measurement but also by differential
intelligence in detector and detection control panel measurement, thus supporting early fire detection. The
guarantee the functional reliability. detector can be set in 5 stages with alarm temperatures
from 60 °C to 90 °C and indicates an alarm through
OMX 95 2 red LEDs.
The optical smoke detector OMX 95 is a light scatter
detector containing a measuring chamber shielded IMX 95
against daylight. The measuring chamber consists of a The ionisation smoke detector IMX 95 operates with an
labyrinth, a pulsating IR-LED and a photodiode placed open outer and a half-closed inner ionisation chamber.
outside the IR ray. As soon as smoke penetrates into The air in both chambers will be ionised via a small
the measuring chamber, the pulsating IR light ray will carrier with radioactive AM 241 with low radiation,
be scattered and registered by the photodiode. Depend- thus producing a current flow. The current in the outer
ing on the selected sensitivity 1 to 5, the processor- ionisation chamber will be reduced and analysed by a
controlled electronic analysing system now switches high-grade electronic system when smoke is penetrating
the detector into alarm condition. The alarm is indicated the detector. For the IMX 95 as well the sensitivity can
by 2 red LEDs. The self-adjusting quiescent value in the be set in 5 stages and an alarm is indicated by 2 red LEDs.
detector ensures a constant response sensitivity.

Applications

Multi-sensor smoke detector OWMX 95 Optical smoke detector OMX 95 Heat detector WMX 95 Ionisation smoke detector IMX 95

Clean room, chip fabrication ++ ++ – +


Hotel rooms, living areas < 50 m 2
++ ++ – +
Offices, corridors, hospitals, ++ ++ – +
light industry

Store rooms, department stores,


++ + + ++
discotheques, power stations

Closed parking garages,


++ + + +
loading stations

Kitchen, laundry + – ++ –
Heavy industry + + ++ –

Application: ++ very suitable + well suitable – unsuitable, depending on project

Technical Data

All types Type VdS approval

Rated current 17 - 28 V DC OWMX 95 G208034


Printed in Germany

Quiescent current 0,5 mA OMX 95 G208033


Alarm current 3,5 mA WMX 95 G208035
Alarm indication 2 LEDs, red IMX 95 G208036
Ingress protection IP 43 (WMX 95 = IP 53)
Relative humidity 0 – 95 %, no condensation
PB42Fe_02/ 03.04 /5/09.08/HA

Working temperature – 20 °C to +60 °C, no condensation


Storing temperature – 30 °C to +80 °C
Wind velocity no restriction
Dimensions Ø 100 x 50 mm height (OWMX 95 = 58 mm)
Weight 160 g
Connection cable 2 core
Subject to technical alterations.