You are on page 1of 1

CONDUIT SIZING SHEET

Area occupied by cable(s) inside a conduit <= Filling Factor x Inner area
(FF) of this conduit

n1 (pd12) + n2 (pd22) + n3 (pd32) + … etc. <= FF x pD2


4 4 4 4

p (n1d12+n2d22+n3d32+…etc.) p FF x D
2
<= x
4 4

Snidi2 <= FF x D2

1 Snidi2 <= D2
FF

Where,
D:Inner diameter of conduit
D (mm) >=
√ [ Snidi2
FF
]
d: Outer diameter of cable in mm

n: Number of conductors of same size D (in " ) >=


)‫قيمة نسبة استغالل (مأل‬
√ [ Snidi2
FF
]
‫عدد الكابالت او االسالك‬ ‫الماسورة‬
‫في الماسورة‬
25.4

For Live conductors : FF = 0.4 Conduit size :


/ ‫مساحة مقطع الكابل‬
n= 4 ‫السلك‬
d= 31.1 mm , of 300 mm2 D (mm) >= 101.0 mm
1 -C ‫عدد الكور للكابل‬

For Gnd conductor : ‫ السلك‬/ ‫قطر الكابل‬ D (in) >= 4.0 "

n= 1
‫مساحة مقطع االرضي‬
d= 14.6 mm , of 50 mm2
1 -C

‫قطر كابل االرضي‬