You are on page 1of 1

5.

6 EMERGENCY OPERATION

5.6.1 Stator water flow low Check expansion tank level is normal and drains
are closed.
Check position of recirculation value.

Check whether running pump has tripped. Re-


serve pump should start on Auto, if not start
manually.

Check differential pressure across the filter is


normal.

5.6.2 Stator water conductivity high Check D.M. water conductivity from the D.M. Plant.
If normal, then purge same water from system. If
D.M. tank Water conductivity is high then close
D.M. make up valve.
Check stator water cooler for leakage.

Regenerate-polishing unit resin beds & take it into


service.

5.6.3 Hydrogen pressure low Charge fresh hydrogen. If consumption is high


then investigate leaking points. If the pressure
persist to drop then reduce load on generator. If the
pressure can't be maintained then trip the set.

5.6.4 Hydrogen purity low Purge some hydrogen from casing and charge fresh
hydrogen.
Check seal performance is normal.

5.6.5 Seal oil differential high/low Check DPR is functioning normally. If not change
to the bypass line and get DPR attended.

Adjust the pressure at injector/ pump discharge.

5.6.6. Liquid in generator Open the low point drain of generator and check
nature and amount of leakage.
Check proper functioning of DPR.
Check thrust oil pressure.
Check stator water pressure.

5.6.7 Generator stator cooling water Check gas trap and analyse the gas from it. In case
leakage stator water leakage is suspected then shut down
the unit and attend the leak.

5.6.8 Damper tank level low Check DPR operation. If required open the bypass
valve and make up the level. If the level approaches
16w unit will trip.
145

You might also like