C70

CAPACITOR BANK
PROTECTION & CONTROL SYSTEM
Key Benefits
Protect capacitor banks of a variety of configurations with Custom programmable logics for advanced shunt capacitor
sensitive current and voltage balance protection functions bank controls
Complete IEC 61850 Process Bus solution providing resource Flexible Automatic voltage regulation of shunt capacitor

Specialized Protection & Control


optimization and minimizing total P&C lifecycle costs banks along with control supervision
Adaptive compensation techniques truly compensation for Embedded IEC61850 Protocol
the inherent bank unbalance providing sensitive protection Reduced relay to relay wiring and associated installation
Robust network security enabling Critical Infrastructure costs through high-speed inter-relay communications
Protection through user command logging, and dual Ambient temperature monitoring with alarming when outside
permission access control temperature exceeds upper thresholds

Applications
Protection, Control, Monitoring and Automation of shunt Sensitive protection for grounded, ungrounded single and
capacitor banks of different voltage levels parallel capacitor banks and banks with taps, for a variety of
Suitable for protecting multiple capacitor banks capacitor bank configurations
Shunt capacitor banks based AVR and Capacitor control
supervision
Features
Features
Protection and Control IEC 61850 Process Bus Interface
Voltage differential protection Robust communications with up to 8 HardFiber Bricks
Compensated Bank Neutral Voltage Unbalance Seamless integration with existing C70 functions
Phase Current Unbalance and Neutral Current Unbalance Redundant architecture for dependability and security
protection
Bank phase overvoltage Monitoring and Metering
Negative sequence over voltage Metering - current, voltage, power, energy, frequency
User programmable logics for custom schemes Oscillography analog and digital parameters at
64 samples/cycle
Automatic Voltage Regulator (AVR) for switching capacitor
banks based on voltage, power factor and reactive power Event Recorder - 1024 time tagged events with 0.5ms scan of
digital inputs
Time and Date function allowing capacitor bank switching
based on time of day, week and seasons. Data Logger - 16 channels with sampling rate up to
1 sample / cycle
Capacitor control supervision block for processing
commands from SCADA, remote communication and local Advanced relay health diagnostics
control through front panel HMI Setting Security Audit Trail for tracking changes to C70
configuration
Communications
Networking interfaces 100Mbit Fiber Optic Ethernet, RS485, EnerVistaTM Software
RS232, RS422, G.703, C37.94 Graphical Logic Designer and Logic Monitor to simplify
Multiple Protocols - IEC61850, DNP 3.0 Level 2, Modbus RTU, designing and testing procedures
Modbus TCP/IP, IEC60870-5-104, Ethernet Global Data (EGD) Document and software archiving toolset to ensure
Direct I/O secure, high-speed exchange of data between reference material and device utilities are up-to-date
URs for Direct Transfer Trip and I/O Extension applications EnerVistaTM Integrator providing easy integration of data in
Embedded Managed Ethernet Switch with 4 - 100 Mbit Fiber the C70 into new or existing monitoring and control systems
optic ports and 2 copper ports

g Multilin
393
C70 Capacitor Bank Protection and Control System

Introduction Negative sequence instantaneous Each element has four independent


overcurrent (50_2) stages; each stage has an independent
The C70 is an integrated protection, control,
Negative sequence time overcurrent threshold, restraint slope, and time
and monitoring device for shunt capacitor
(51_2) delay.
banks based on the well established and
proven UR relay platform of GE Multilin. The Provisions to set the inherent bank
C70 provides both the bank and system unbalance factors manually, or by
The C70 also provides breaker failure
protection schemes for shunt capacitor selecting the auto-setting feature.
protections and standard voltage based
bank protection. The current and voltage- The bank unbalance factor can be
protection functions which include:
based protection functions are designed to calculated automatically under user
provide sensitive protection for grounded, supervision either locally or remotely.
Phase overvoltage (59P)
ungrounded single, and parallel capacitor
Phase undervoltage (27P) Bank Phase Overvoltage
banks and banks with taps, for a variety
of capacitor bank configurations. The Auxiliary overvoltage (59X) Applicable for both grounded and
sophisticated built-in control functions can Neutral overvoltage (59N) ungrounded banks. In the later case the
be used to automate capacitor switching Negative sequence undervoltage (27N) relay takes the neutral point voltage in
with ease and flexibility for automatic order to derive the voltage drop across
voltage regulation of the system. Part the capacitor strings.
of the universal relay family, C70 comes Apart from the standard current and
Three phase element with three
with a variety of versatile features truly voltage based functions the C70 comes
definite time stages and one inverse
Specialized Protection & Control

integrating protection, monitoring, with protection functions specifically


time stage; each definite time stage
metering, communication and control in designed to provide sensitive protection
has an independent threshold and
one easy-to-use device. Universal relay for capacitor banks in a single box. Typical
time delay, the inverse time stage
family offers higher degree of modularity configurations with their associated model
has an independent threshold, curve
in its design and functionality providing numbers are shown.
time multiplier and customizable
superior performance in protection and curve shape. Each stage can be
Voltage Differential
control meeting the toughest requirements independently configured for alarming
of the marketplace. The unparalleled Applicable for both grounded and
or tripping.
software toolsets from Enervista with its ungrounded banks. In the ungrounded
case, the algorithm uses the neutral One bank overvoltage element provided
user-friendly interfaces helps managing
point voltage to provide sensitive per VT bank up to a maximum of three.
the relay and the power system in the
easiest way. protection.
Phase Current Unbalance
Based on a simple voltage divider
principle, which compares the bus Based on the balance between phase
Protection voltage with the tap voltage of the currents of two parallel banks and
C70 provides Sensitive protection bank. is applicable to both grounded and
functions designed specifically to protect ungrounded banks.
Three-phase element with four
the shunt capacitor banks effectively. The independent stages for alarming and Compensates for bank unbalances to
C70 provides current based protection control. Each stage has independent provide better sensitivity.
functions, which include phase, ground, per phase settings and a common time Three-phase element with four
and neutral instantaneous and time delay. independent stages for a protection
overcurrent elements for standard and alarming. Each stage has
Provision to set the per phase voltage
overcurrent protection of the bank. Two independent per phase settings and a
divider factors manually, or by
elements per configured CT bank are common time delay.
selecting the auto-setting feature.
available.
The voltage divider factor can be Provision to set the current divider
The standard current based protection
calculated automatically under user factor individually per phase manually,
functions include:
supervision either locally or remotely. or by selecting the auto-setting feature.
One voltage differential element The current divider factor can be
Phase instantaneous overcurrent (50P)
provided per VT bank up to a calculated automatically under user
Phase time overcurrent (51P) supervision either locally or remotely.
maximum of three.
Ground instantaneous overcurrent Immune to system transients, providing
(50G) Compensated Bank Neutral Voltage secure operation without resorting to
Ground time overcurrent (51G) Unbalance any excessive filtering.
Neutral instantaneous overcurrent Applicable to ungrounded banks One phase current unbalance element
(50N) Truly compensates for both the system is provided per CT/VT module up to a
Neutral time overcurrent (51N) unbalance and the bank unbalance. maximum of three.

394 www.GEMultilin.com
C70 Capacitor Bank Protection and Control System

Typical Application: Grounded, parallel banks


Typical Model No: C70-N03-HPH-F8L-H6P-M8N-PXX-UXX-WXX

Typical Application: Ungrounded wye banks with taps


Typical Model No: C70-N03-HPH-F8L-H6P-M8L-PXX-UXX-WXX

Specialized Protection & Control


Typical Application: Ungrounded, parallel banks
Typical Model No: C70-N03-HPH-F8N-H6P-M8L-PXX-UXX-WXX
Typical Application: Ungrounded wye banks
Typical Model No: C70-N03-HPH-F8L-H6P-MXX-PXX-UXX-WXX

Typical Application: Grounded, parallel banks with taps


Typical Model No: C70-N03-HPH-F8N-H6P-M8L-PXX-U8V-WXX

Typical Application: Grounded wye banks with taps


Typical Model No: C70-N03-HPH-F8L-H6P-M8V-PXX-UXX-WXX

www.GEMultilin.com 395
C70 Capacitor Bank Protection and Control System

Neutral Current Unbalance or the single phase auxiliary voltage. Two FlexLogic
applications using the reactive power/power FlexLogic is the powerful UR-platform
Based on the balance between
factor path are shown below. programming logic engine that provides
interconnected neutral current of two
Specialized Protection & Control

parallel banks and is applicable to both the ability of creating customized protection
Time and Date Function
grounded and ungrounded banks. and control schemes thereby minimizing the
Provides the user with ability to program need, and the associated costs, of auxiliary
Grounded banks require a window CT.
certain actions based on time. components and wiring.
Each element has four independent
5 time of day timers Using FlexLogic, the C70 can be
stages; each stage has independent
User accessible time/date information for programmed to provide required tripping
threshold and time delay settings.
more sophisticated custom schemes, that logic along with custom scheme logic for
Provision to set the bank unbalance dynamic setting group changes.
respond to weekdays, weekends, summer
factors manually, or by selecting
or winter
the auto-setting feature. The bank Scalable Hardware
unbalance factor can be calculated The C70 is available with a multitude of I/O
automatically under user supervision configurations to suit the most demanding
either locally or remotely. application needs. The expandable modular
One neutral current unbalance element design allows for easy configuration and
provided per CT/VT module, up to a future upgrades.
maximum of three. Multiple CT/VT configurations allow
for implementation of many different
schemes
Control Flexible, modular I/O covering a broad
The C70 is provided with built-in control range of input signals and tripping
functions to help end users build capacitor Capacitor Control Supervision schemes
bank control schemes of their choice with This feature supervises the capacitor
ease and flexibility. bank open and close commands from the
command sources including the Relay
Automatic Voltage Regulator
front panel HMI (push buttons), AVR and
The AVR is a capacitor bank controller SCADA/HMI.
responding to either voltage, reactive
power, or power factor. One AVR element
is provided per CT/VT module, up to a Advanced Automation
maximum of three. The AVRs can operate The C70 incorporates advanced automation
independently, each on their own section features including powerful FlexLogic
of the bank, or only the one set for present programmable logic, communication, and
conditions/time-of-day, as determined by SCADA capabilities that far surpass what is
FlexLogic (user programmable logic). For found in the average capacitor bank relay.
the voltage control path, a provision is The C70 integrates seamlessly with other UR
made to operate from any phase-phase relays for complete system protection.
voltage (VAB, VBC, VCA), average voltage
(VAVER), positive-sequence voltage (V1) Capacitor control supervision block

396 www.GEMultilin.com
C70 Capacitor Bank Protection and Control System

FlexLogicTM Designer
test its own major functions and critical
hardware. These diagnostic tests monitor
for conditions that could impact security
and availability of protection, and present
device status via SCADA communications
and front panel display. Providing
continuous monitoring and early detection
of possible issues helps improve system
uptime.

Comprehensive device health


diagnostic performed during startup
Monitors the CT/VT input circuitry to
validate the integrity of all signals

Communications
FlexlogicTM allows for customizing the C70 outputs for capacitor bank protection schemes and applications. The C70 provides advanced commun-
ications technologies for remote data and
engineering access, making it easy and
RTDs and DCmA inputs are available to current, and power metering are built into

Specialized Protection & Control


flexible to use and integrate into new and
monitor equipment parameters such as the relay as a standard feature. Current
existing infrastructures. Direct support
temperature & pressure and voltage parameters are available as
for fiber optic Ethernet provides high-
total RMS magnitude, and as fundamental
bandwidth communications allowing for
frequency magnitude and angle.
IEC 61850 Process Bus low-latency controls and high-speed file
Fault and Disturbance Recording transfers of relay fault and event record
The IEC 61850 Process Bus module is information. The available redundant
designed to interface with the GE Multilin The advanced disturbance and event
Ethernet option and the embedded
HardFiber System, allowing bi-directional recording features within the C70 can
managed Ethernet switch provide
IEC 61850 fiber optic communications. significantly reduce the time needed for
the means of creating fault tolerant
The HardFiber System is designed to postmortem analysis of power system
communication architectures in an easy,
integrate seamlessly with the existing events and creation of regulatory reports.
cost-effective manner without the need for
Universal Relay applications, including Recording functions include:
intermediary communication hardware.
protection functions, FlexLogic, metering The C70 supports the most popular
and communications. Sequence of Event (SOE)
industry standard protocols enabling
- 1024 time stamped events
easy, direct integration into DCS and
The GE Multilin HardFiber System offers Oscillography, SCADA systems.
the following benefits:
- 64 digital & up to 40 Analog channels
Communicates using open standard
Data Logger, disturbance recording IEC61850
IEC 61850 messaging
16 channels up to 1 sample / cycle / DNP 3.0
Drastically reduces P&C design,
channel
installation and testing labor by IEC60870-5-104
Fault Reports
eliminating individual copper Modbus RTU, Modbus TCP/IP
- Powerful summary report of pre-fault
terminations
and fault values
Integrates with existing C70s by Interoperability with Embedded
replacing traditional CT/VT inputs with IEC61850
The very high sampling rate and large
IEC 61850 Process Bus module Use the C70 with integrated IEC61850
amount of storage space available for
Does not introduce new Cyber Security to lower costs associated with capacitor
data recording in the C70 can eliminate
concerns bank protection, control and automation.
the need for installing costly standalone
GE Multilins leadership in IEC61850 comes
recording equipment.
Visit the HardFiber System product page on from thousands of installed devices and
the GE Multilin web site for more details. Advanced Device Health follows on seven years of development
Diagnostics experience with UCA 2.0.

The C70 performs comprehensive


Monitoring and Metering device health diagnostic tests during
Replace expensive copper wiring
The C70 includes high accuracy metering between devices with direct transfer of
startup and continuously at runtime to
and recording for all AC signals. Voltage, data using GOOSE messaging

www.GEMultilin.com 397
C70 Capacitor Bank Protection and Control System

Configure systems based on IEC61850 EnerVistaTM Software Guideform Specifications


and also monitor and troubleshoot Brochures
The EnerVista Suite is an industry-leading
them in real-time with EnerVistaTM
set of software programs that simplifies every Wiring Diagrams
Viewpoint Engineer
aspect of using the C70 relay. The EnerVistaTM FAQs
Integrate GE Multilin IEDs and generic suite provides all the tools to monitor the
IEC61850-compliant devices seamlessly Service Bulletins
status of the protected asset, maintain the
in EnerVistaTM Viewpoint Monitoring relay, and integrate information measured
Viewpoint Engineer
by the C70 into DCS or SCADA monitoring
Direct I/O Messaging systems. Convenient COMTRADE and Viewpoint Engineer is a set of powerful tools
Direct I/O allows for sharing of high-speed Sequence of Events viewers are an integral that will allow the configuration and testing
digital information between multiple UR part of the UR Setup software included with of UR relays at a system level in an easy-to-
relays via direct back-to-back connections every UR relay, to carry out postmortem use graphical drag-and-drop environment.
or multiplexed through a standard DS0 event analysis to ensure proper protection Viewpoint Engineer provides the following
multiplexer channel bank. Regardless of system operation. configuration and commissioning utilities:
the connection method, Direct I/O provides Graphical Logic Designer
continuous real-time channel monitoring EnerVista Launchpad Graphical System Designer
that supplies diagnostics information on EnerVista Launchpad is a powerful Graphical Logic Monitor
channel health. software package that provides users
Direct I/O provides superior relay-to-relay Graphical System Monitor
with all of the setup and support tools
communications that can be used in needed for configuring and maintaining GE
EnerVista Integrator
Specialized Protection & Control

advanced interlocking, generation rejection Multilin products. The setup software within
and other special protection schemes. Launchpad allows configuring devices in EnerVistaTM Integrator is a toolkit that allows
real-time by communicating using serial, seamless integration of GE Multilin devices
Communication with up to 16 UR relays Ethernet, or modem connections, or offline into new or existing automation systems.
in single or redundant rings rather by creating setting files to be sent to devices Included in EnerVista Integrator is:
than strictly limited to simplistic point- at a later time.
to-point configurations between two Included in Launchpad is a document OPC/DDE Server
devices archiving and management system that GE Multilin Drivers
Connect to standard DS0 channel ensures critical documentation is up-to-date Automatic Event Retrieval
banks through standard RS422, G.703 and available when needed. Documents
Automatic Waveform Retrieval
or IEEE C37.94 interfaces or via direct made available include:
fiber optic connections
Manuals
No external tester required to provide
channel diagnostic information Application Notes

Power System Troubleshooting


The C70 contains many tools and reports that simplify and reduce the amount of time required for troubleshooting power system events.

Record the operation of the internal C70 elements and external connected
devices with 1ms time-stamped accuracy to identify the Sequence of Operation Analyze capacitor bank faults using both analog and digital power system
of station devices during capacitor bank faults and disturbances. quantities that are measured and recorded up to a rate of 64 samples per cycle.

398 www.GEMultilin.com
C70 Capacitor Bank Protection and Control System

LED Indicators
User Interface
The C70 front panel provides extensive local
HMI capabilities. The local display is used Multi-Language
for monitoring, status messaging, fault Display
English
diagnosis, and device configuration. User
Russian
configurable messages that combine text French
with live data, can be displayed when user- Chinese
defined conditions are met.

User Programmable Pushbuttons

Typical Wiring Diagram

B
52
C

Specialized Protection & Control


Optional
F1a

F1b

F2a

F2b

F3a

F3b

F4a

F4b

F5a

F6a

F7a

F8a

L1a

L1b

L2a

L2b

L3a

L3b

L4a

L4b

L5a

L6a

L7a

L8a
F1c

F2c

F3c

F4c

F5c

F6c

F7c

F8c

L1c

L2c

L3c

L4c

L5c

L6 c

L7c

L8c
VB

VC
VB

VC

VA

VX
VA

VX

IG
IG

IG1
IG1

IA

IC
IC

IB

IC1
IA

IB

IA1
IC1

IB1
IA1

VB
IB1

VC
VB

VC

IG5
IG5

VA

VX
VA

VX

IC5
IC5

IA5

IB5
IA5

IB5

VOLTA VOLTA
8F 8F

H5a CONTA DIGIT 6G I H1a TC 1


H5c CONTACT 5c H1 H1b
V
H6a CONTACT 6a H1c
H6c CONTACT 6c I H2a
H5b C H2 H2b
V
H2c
H7a CONTACT 7a
I H3a
H7c CONTACT 7c
H3 H3b TC 2
H8a CONTACT 8a V
H3c
H8c CONTACT 8c
I H4a
H7b C
H4 H4b
V
H8b SURGE H4c

U7a CONTA DIGIT 6H I U1a


U7c CONTACT 7c U1 U1b
V
U8a CONTACT 8a U1c
U8c CONTACT 8c I U2a
U7b C U2 U2b
V
U2c
U8b SURGE
I U3a
U3 U3b
S1a CONTA V
6D

U3c
S1c CONTACT 1c
I U4a
S2a CONTACT 2a
U4 U4b
S2c CONTACT 2c V
U4c
S1b C
I U5a
S3a CONTACT 3a U5 U5b
V
S3c CONTACT 3c U5c
S4a CONTACT 4a I U6a
S4c CONTACT 4c U6 U6b
V
S3b C U6c
S5a CONTACT INPUT S5a
N1a
6C

S5c CONTACT 5c
N1 N1b
S6a CONTACT 6a
N1c
S6c CONTACT 6c
N2a
S5b C
N2 N2b
S7a CONTACT 7a N2c
S7c CONTACT 7c N3a
S8a CONTACT 8a N3 N3b
S8c CONTACT 8c N3c
DIGIT

N4a
Multilin
S7b C
S8b SURGE N4 N4b
N4c
C70 COMPUTER
B1b N5a
CRITICAL 1 1 8
B1a N5 N5b
FAILURE 2 2 3 RXD
B2b N5c TXD

DC
B3a
B3b OUTPUT C70 N6
N6a
N6b
RXD 3
4
SGND 5
3
4
5
2 TXD
20
7 SGND
Pr
B5b HI N6c
CONTROL 6 6 6
B6b LO N7a
POWER
B6a N7 N7b 7 7 4
*Fibre B8a
B8b
SURGE
FILTER
Contr elay N7c
N8a
8
9
8
9
5
22
P

Optic
DIGIT

N8 N8b
D1b10BaseFL
Tx1 N8c
RS485
NORMAL
D2bRx1 CONNECTOR CONNECTOR
C
D3b10BaseFL
Tx2 com COM
ALTERNATE
D1aRx2 1
RS485
Shielded D2a C
10BaseT
D3a com
Remote
Device D4b
D1a
RS485 RS-232
D4a
D2a IRIG-B
input DB-9
D3a BNCcom
D4b (front)
PERSONAL
D4a BNC IRIG-B
IRIG-B COMPUTER
output
Input
Co-axial BNC

IRIG-B
Co-axial BNC Output

Minimum

X W V U T S R P N M L K J H G F D B
6 6 6 8 6 8 9 1
Inputs/ Inputs/ Inputs/ CT/ Inputs/ CT/ CPU Power
outputs outputs* outputs VT outputs VT supply
PROVIDED * * *

www.GEMultilin.com 399
C70 Capacitor Bank Protection and Control System

Ordering
C70 - * 00 - * * * - F ** - H ** - M ** - P ** - U ** - W/X ** For full sized horizontal mount
Base Unit Base Unit
CPU E RS485 + RS485 (IEC61850 option not available)
G RS485 + Multi-mode ST 10BaseF
H RS485 + Mutli-mode ST Redundant 10BaseF
J RS485 + Multi-mode ST 100BaseFX
N RS485 + 10/100 BaseT
S RS485 + 6 port, 100 Mbps, Managed Ethernet Switch
Software Options 00 None
03 IEC61850
12 Enhanced Capacitor Bank Control (AVR, Capacitor Control Supervision,
Time & Date)
13 Enhanced Capacitor Bank Control (AVR, Capacitor Control Supervision,
Time & Date) + IEC61850
Mounting / Conformal Coating H Horizontal (19 rack) - Standard
A Harsh Chemical Environment Option
User Interface K Enhanced English Front Panel
L Enhanced English Front Panel with User-Programmable Pushbuttons
M Enhanced French Front Panel
N Enhanced French Front Panel with User-Programmable Pushbuttons
Q Enhanced Russian Front Panel
T Enhanced Russian Front Panel with User-Programmable Pushbuttons
U Enhanced Chinese Front Panel
V Enhanced Chinese Front Panel with User-Programmable Pushbuttons
F Vertical Front Panel with English display
Power Supply H 125/250 V AC/DC
L 24 - 48 V (DC only)
CT/VT DSP 8L 8L 8L Standard 4CT/4VT w/ enhanced diagnostics
Specialized Protection & Control

8N 8N 8N Standard 8CT w/ enhanced diagnostics


8V 8V 8V Standard 8VT w/ enhanced diagnostics
IEC 61850 Process Bus 81 8 Port IEC 61850 Process Bus Module
Digital I/O XX XX XX XX XX No Module
6A 6A 6A 6A 6A 2 Form-A (Voltage w/ opt Current) & 2 Form-C Outputs, 8 Digital Inputs
6B 6B 6B 6B 6B 2 Form-A (Voltage w/ opt Current) & 4 Form-C Outputs, 4 Digital Inputs
6C 6C 6C 6C 6C 8 Form-C Outputs
6D 6D 6D 6D 6D 16 Digital Inputs
6E 6E 6E 6E 6E 4 Form-C Outputs, 8 Digital Inputs
6F 6F 6F 6F 6F 8 Fast Form-C Outputs
6G 6G 6G 6G 6G 4 Form-A (Voltage w/ opt Current) Outputs, 8 Digital Inputs
6H 6H 6H 6H 6H 6 Form-A (Voltage w/ opt Current) Outputs, 4 Digital Inputs
6K 6K 6K 6K 6K 4 Form-C & 4 Fast Form-C Outputs
6L 6L 6L 6L 6L 2 Form-A (Current w/ opt Voltage) & 2 Form-C Outputs, 8 Digital Inputs
6M 6M 6M 6M 6M 2 Form-A (Current w/ opt Voltage) & 4 Form-C Outputs, 4 Digital Inputs
6N 6N 6N 6N 6N 4 Form-A (Current w/ opt Voltage) Outputs, 8 Digital Inputs
6P 6P 6P 6P 6P 6 Form-A (Current w/ opt Voltage) Outputs, 4 Digital Inputs
6R 6R 6R 6R 6R 2 Form-A (No Monitoring) & 2 Form-C Outputs, 8 Digital Inputs
6S 6S 6S 6S 6S 2 Form-A (No Monitoring) & 4 Form-C Outputs, 4 Digital Inputs
6T 6T 6T 6T 6T 4 Form-A (No Monitoring) Outputs, 8 Digital Inputs
6U 6U 6U 6U 6U 6 Form-A (No Monitoring) Outputs, 4 Digital Inputs
6V 6V 6V 6V 6V 2 Form-A (Cur w/ opt Volt) 1 Form-C Output, 2 Latching Outputs, 8
Digital Inputs
Transducer I/O 5A 5A 5A 5A 4 dcmA Inputs, 4 dcmA Outputs
Inter-Relay Communications 7H 820 nm, multi-mode, LED, 2 Channels
7I 1300 nm, multi-mode, LED, 2 Channels
7S G.703, 2 Channels
7W RS422, 2 Channels
77 IEEE C37.94, 820 nm, multimode, LED, 2 Channel
2S 6 port, 100 Mbps, Managed Ethernet Switch, HI (125/250V AC/DC)
2T 6 port, 100 Mbps, Managed Ethernet Switch, LO (24-48 Vdc)

Accessories for the C70 Visit www.GEMultilin.com/C70 to:


UR Applications I Learning CD TRCD-URA1-C-S-1 View Guideform Specifications
Multilink Ethernet Switch ML2400-F-HI-HI-A2-A2-A6-G1 Download the instruction manual
Viewpoint Engineer VPE-1 Review applications notes and support documents
Viewpoint Maintenance VPM-1 Buy a C70 online
Viewpoint Monitoring IEC61850 VP-1-61850 View the UR Family brochure

Ordering Note: To view the latest options available for the C70, or to order the UR Classic Front Panel, please visit our online store for more details.

080626-v1
400 www.GEMultilin.com