You are on page 1of 33

CHAPTER-4

Power System apparatus


Protection

1. Generator protection
INTRODUCTION

Protection of Generator

 The generators used in the power system are used to


produce very high a.c.voltage

 The protection of generators is very much complex due to


the following reasons

1.The generators are very large machines producing very


high voltages and are connected to busbars.

2. Various other equipments are always associated with the


generators such equipments are

 Prime movers
 Excitation system
 Voltage regulation
 Cooling systems etc
con

Thus protection of generator must consider the presence of


these other equipment also.

3. generators is important factor in a power system. the failure


of the generator causes entire outage of the system so the
protection scheme needs great consideration .

 All these factors make the design of protection scheme for


the generator, very much complex.
Generator faults

1. Stator faults
2. Rotor faults
3. Abnormal running conditions

1. Stator faults
A. Phase to ground faults
B. Phase to phase faults
C. Stator inter-turn faults

3. Abnormal running conditions


a. Overloading
b. over speeding
c. unbalanced loading
d. Overvoltage
e. failure of prime mover
f. loss of excitation (field
g. cooling system failure
a. Overloading

 Due to continuous overloading the overheating of stator


Results .this may increase the winding temperature if the
temperature rise exceeds certain limit the insulation of the
winding may get damage

• Over current protection is used to protect the overloading


problem

b. Over speeding

 In case of hydraulic generator a sudden loss of load


results in over speeding of the generator .
C. Unbalanced loading

 The unbalance loading of the generator results in the circulation of negative


sequence current these current produce the rotating magnetic field

 Negative sequence protection is important to protect this situation.

e. Failure of prime mover


 The failure of prime mover results in motoring operation of the

synchronous generator the generator draws active power from the network
and continues to run as synchronous motor

 Reverse power protection is used to protect such problem.

f. loss of excitation
The loss of excitation or reduced excitation is possible due to the field failure
(opening of Field winding or due to short circuit in field )

g. Cooling system failure

The failure of cooling system also causes sever overheating to rise the
temperature above safe limit it may lead insulation failure.
Protective schemes employed for generator protection

1. Differential protection
2. Inter-turn fault protection
3. Stator earth fault protection
4. Over current & earth fault protection
5. Rotor earth fault protection
6. Reverse power protection
7. Field failure protection
8. Negative phase-sequence protection
9. Over load protection
10. Over voltage protection
11. Pole slipping protection
12. Back up impedance protection
13. Under frequency protection
1.Differential Protection of Generator

Cases & Consequences of Stator Insulation Failure

 The breakdown of insulation (failure) may result in fault


between conductors or between conductor & iron core.

 The breakdown may be caused by


 over voltage
 over heating
 over-loads
 unbalanced currents
 ventilation troubles
 failure of cooling of system etc.
1.Differential Protection of Generator (Circulating current principle)

In ideal condition IA1=IA2


ia1=ia2

But in real condition IA1=IA2


ia1 ≠ ia2 due to
Unequal CT saturation and un equal
Pilot wire length
1.Differential Protection of Generator (Circulating current principle)

 If the CTs are identical nature ,in practice it is


impossible to achieve CTs With identical saturation
characteristics

 Hence the secondary currents of CTs are unequal even


though the primary currents are the same.

 This current is known as spill current. The spill current


pass through the relay And may mal-operate the relay
if its value exceeds the setting of the relay.

 Moreover if the length of the connecting wires (pilot


wire) is unequal the value of the spill current increase
1.Differential Protection of Generator (Circulating current principle)

 In order to avoid mal-operation of the differential relay by the


spill current two solutions are used

i. a Stabilizer resistance is connected in series with the relay


ii. Biased percentage differential protection scheme

 However incorporation of stabilizing resistance reduces the


sensitivity of the relay during an internal fault,
1.Differential Protection of Generator (Circulating current principle)
1.Differential Protection of Generator (Circulating current principle)

Where RR= relay resistance


1.Percentage differential Protection of Generator
2. Inter-turn fault protection of generator

 The inter-turn fault is a short circuit between the turns of


the same phase winding.

 The produced fault current does not affect the entering and
leaving current to the CTs .

 If the short circuit is developed between the adjacent turns


then current through S1 and S2 no longer remain same.

 Thus unequal current will be induced in the secondaries of


the CT the difference current flows through the rely R and
the breaking of the CB isolate the generator.
2. Inter-turn fault protection of generator
3.Stator earth fault protection of generator

 The fault happen b/n the stator conductor and core of


stator occurs due to failure of insulation between
conductor and core.

 Stator earth fault will happen due to failure of insulation


b/n the stator conductor and core

 Hence the stator earth fault are very destructive faults if


ground fault current is large.
A. Restricted earth fault protection of generator

 The differential protection based on circulating current


principle provides the protection against internal faults.

 When the neutral is solidly grounded then the generator gets


completely (100%) protected against phase-to-ground fault.

 But the neutral is grounded through earth resistance ,then


the stator windings get partly (85%) protect against earth
faults.

 However neutral is earthed through resistance to limit e/f


current.
A. Restricted earth fault protection of generator

A restricted earth fault is a normal earth fault that is restricted to a


particular zone. Hence, the restricted earth fault protection takes
care of the faults that occurred only within that particular zone
neglecting the faults outside the restricted zone.

Earth faults are not likely occur near the neutral point due to
less voltage with respect to earth

It is usual practice to protect about 80 to 85% of winding against


earth fault. The remaining 15-20% winding from neutral side left
unprotected .

A separate e/f protection is provided to take care of complete


winding against e/f (100% winding protection).
A. Restricted earth fault protection of generator

 A restricted e/f relay in the differential protection is shown in


figure below.

 In figure below, during earth fault the current if in the


alternator winding flows through a part of winding and
neutral to ground circuit.

 The corresponding secondary current Is flows through the


operating coil & restricted e/f relay the relay would operate
instantaneously if current is more than the pick-up setting of
the relay .
 Hence the earth fault current if will reduced.
Restricted earth fault protection of generator
Restricted earth fault protection of generator

For an internal line to ground faults i.e., fault at F1 which is in the


protected zone, the neutral side CT is more energized and hence the
relay operates if the residual current is greater than the relay pickup
value.

For an internal line to line faults, no CT is energized and hence the relay
does not operate. However, in most cases, the internal line-to-line faults
develop into earth faults. Under these circumstances, the relay will
operate as the neutral side CT will be more energized.
B. Unrestricted earth fault protection of generator
4. Overcurrent & Earth Fault Protection:

Figure: Overcurrent & Earth fault protection of generator.


Continued……

 In such a case, the relay have to be actuated by the short


circuit current supplied by the system.

 Such protection (by o/c and e/f relay) is ineffective when the
main breaker is open or if the system has no other generating
source.

 The normal practice is to monitor the over current relays by


an instantaneous under-voltage relay.

 The latter is connected to control the overcurrent relay


making it faster and more sensitive if the voltage drops
indicating a fault in the machine.
5. Rotor Earth Fault Protection:
 The rotor carries the field winding which is kept isolated from
the ground. Neither the positive nor the negative terminal of
the dc supply is grounded. Thus any ground fault on the
rotor field winding does not affect the working of the
alternator.

 However subsequent fault would cause a section of the rotor


winding to be short circuited ground fault due to insulation
failure will happen.
Continued....
 A rotor earth fault increase the current in part of the winding may also
cause local heating which may distort rotor causing dangerous
irregularity, this also can cause vibration & serious damage.

 To protect generator from the rotor e/f, a high resistance is connected


across the rotor circuit.

 The center point of this is connected to earth through a sensitive relay.

 The relay detects the earth faults for most of the rotor circuit.
6. Reverse Power Protection:

 Reverse power protection is provide against the failure of


prime mover of an alternator.

 When the prime mover of one of the alternator fails in a


power plant, the alternator will not stop but will run as a
synchronous motor taking power from the bus.

 There is no harm for the alternator when it is run as a


synchronous motor but the reversal of power is harmful to
the prime mover. The prime mover act as a load on the
motor. i.e. flow of power is reversed.

 The reversal of power is sensed by a reverse power relay.


7. Field Failure Protection:

 Field failure can be caused by failure of the exciter when the


generator losses its field result

 loss of synchronism
 Slightly increase the generator speed.

 If the generator is a single unit supplying a local load, the


loss of field causes loss of terminal voltage, sub-sequently
loss of synchronism depending upon the load condition.

 If the generator is connected in parallel with other units, it


can draw the magnetizing currents (reactive power) from the
bus bars & continuous to run as an induction generator.
Continued….

 This magnetizing current is large of the order of 2 to 4 times


the rated current .
 The stator currents may increase above normal current rating
of generator during the run as induction generator.

 High currents may cause voltage drop & over heating of


generator bus-bars, stator winding etc.

 Figure illustrating the loss of field protection by means of an


Under Current Relay connected across a shunt in series with the
field winding.
END ????

You might also like