You are on page 1of 27

Format No.

MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 1 OF 27

Setting
Addr. Setting Title Options Set Value

Configuration File

103 Group Chage OPTION Disabled Disabled


Enabled

110 Trip Mode 3pole only 1 & 3 pole


1-/3pole

112 Phase Distance Quadrilateral Quadrilateral


MHO
Disabled

113 Earth Distance Quadrilateral Quadrilateral


MHO
Disabled

120 Power Swing Disabled Enabled


Enabled

PUTT(Z1B
121 Teleprot. Dist. acceleration) PUTT
POTT
UNBLOCKING
BLOCKING
Disabled

122 DTT Direct Trip Disabled Disabled


Enabled

124 SOTF Overcurr. Disabled Enabled


Enabled

125 Weak infeed Disabled Disabled


Enabled

ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 2 OF 27

126 Back-Up O/C Disabled Disabled


TOC IEC
TOC ANSI

131 Earth Fault O/C Disabled TOC IEC


TOC IEC
TOC ANSI
TOC
Logarithm.
Definite Time

Dir. Comp.
132 Teleprot. E/F Pickup Disabled
UNBLOCKING
BLOCKING
Disabled
PUTT Over
Protection
interface

133 Auto Reclose Disabled Disabled


1 AR-cycle
2 AR-cycles
3 AR-cycles
4 AR-cycles
5 AR-cycles
6 AR-cycles
7 AR-cycles
8 AR-cycles
ADT(Adaptive
Dead Time)

134 AR Control Mode Pickup w/Tact Pickup w/Tact


Pickup w/o
Tact
Trip w/Tact
Trip w/o Tact

135 Synchro-Check Disabled Disabled

ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 3 OF 27

Enabled

137 U/O Voltage Disabled Enabled


Enabled

138 Fault Locator Disabled Enabled


Enabled

139 BREAKER FAILURE Disabled Disabled


Enabled

140 Trip Circ. Superv Disabled Disabled


1 trip circuit
2 trip circuit
3 trip circuit

Power System
Data

201 CT Starpoint Towards Line Towards Line


towards Busbar

203 Unom PRIMARY 1.0.1200.0 KV 400

204 Unom SECONDARY 80.125 V 110

205 CT PRIMARY 10.5000 A 2000

206 CT SECONDARY 1A 1
5A

210 U4 transformer not connected Not connected


Udelta
transformer
Usync
transformer
ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 4 OF 27

Ux reference
transformer

211 Uph/Udelta 0.10.9.99 1.73

212 Usync connect L1-E L1-E


L2-E
L3-E
L1-L2
L2-L3
L3-L1

214 Usync-Uline 0.36 0

215 U-line / Usync 0.80.1.20 1

Neutral Current
220 14 transformer Not connected of
Neutral Current
(of the parallel line
the protected
line)
Neutral Current
of
the parallel line
Starpoint
Curr.of earthed
power transf.

221 I4/Iph CT 0.010.5.000 1

230 Rated Frequency 50 Hz 50 Hz


60 Hz

235 PHASE SEQ L1L2L3 L1L2L3


L1L3L2

236 Distance Unit km 196


miles

ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 5 OF 27

Zero seq. Zero seq.comp.


237 Format Z0/Z1 comp.factors Factor KO
RE/RL and
XE/XL and angle(KO)
Zero seq.comp.
Factor KO
and angle(KO)

239 T-CB close 0.01..0.60 sec NA

240 Tmin TRIP CMD 0.02..30.00 sec 0.10 sec

241 Tmax CLS CMD 0.01..30.00 sec NA

242 T-CB test-dead 0.00..30.00 sec 1.0 Second

302 CHANGE Group A Group A


Group B
Group C
Group D
Binary Input
Protocol

D R Settings

WAVE FORM Save with


402A TRIGGER Pickup Save with Trip
Save with TRIP
Start with TRIP

403A WAVE FORM DATA Fault event Fault Event


Power System
fault

410 MAX LENGTH 0.30..5.00 sec 2.00 sec

411 PRE. TRING. TIME 0.05..5.00 sec 0.10 sec

ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 6 OF 27

412 POST REC. TIME 0.05..5.00 sec 0.1

415 BiIin CAPT.TIME 0.10..5.00 sec 1.0 seconds

Dusplay
Targets on Display Targets
610 Flt Disp. LED/LCD every on every
Pickup Pickup
Display Targets
on TROP
only
615 Spont. Flt. Disc. NO YES
YES

Line Parametrs (
In
ohms/perkm/per
phase primary
ohms )

R1 = 0.02880
X1 = 0.3280

Ro = 0.28500
Xo = 1.0200

RoM = 0.0000
XoM = 0.0000

Zone Reaches ( In
percentage )

Z1 = 80.00%
Z1B = 120.00%
Z2 = 120.00%
Z3 = 125.00%

ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 7 OF 27

Z4 (R,F) = 10.00% (Reverse)


Z5 = 150.00%

General
Protection Data

1103 Full Scale Volt. 1.0.001200 kV 400 kV

1104 Full Scale Curr. 10..5000 A 2000

1105 Line Angle 30..89 85

0.005..6.500
1110 x' Ohm/km 0.1804

1111 Line Length 1.0..1000.0 km 196.000

0.005..10.500
1112 x' Ohm/mile NA

0.6..650.0
1113 Line Length Miles NA

1116 RE/RL(Z1) -0.33..7.00 2.97


Note: value of
RE/RL(Z1) at
address 1116
&
RE/RL(Z1B..Z5)
at 1118 shall
be restricted to
1.20
1117 XE/XL(Z1) -0.33..7.00 0.70

1118 RE/RL(Z1B..Z5) -0.33..7.00 2.97

1119 XE/XL(Z1B..Z5) -0.33..7.00 0.70

1120 K0(Z1) 0.000.4.00 0.739


ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 8 OF 27

1121 Angle KO(Z1) -135.00..135.00 -15.3

1122 KO(>Z1) 0.000..4.000 0.739

1123 Angle KO(>Z1) -135.00..135.00 -15.3

1126 RM/RL ParalLine 0.00..8.00 0.00

1127 XM/XL ParalLine 0.00..8.00 0.00

1128 RATIO Par. Comp 50..95% 85%

1130 Pole Open Current 0.05..1.00 A 0.05 Amps

1131 Pole Open Voltage 2..70 V 20 V

1132 Sl Time all Cl. 0.01..30.00 0.2 seconds

Minimum time for line


1133A open before SOTF 500 ms

Manual Close Current OR


1134 Line Closure BI only voltage or
Current OR Manual close BI
voltage or
Manual close
BI
Cbaux OR
Current or
Man-
ual close BI
Current flow or
Manual close
BI
with Pole Open with Pole Open
1135 Reset Trip CMD Current Current
Threshold only Threshold only
with Cbaux
ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 9 OF 27

AND Pole
Open Current

with
1136 Open Pole detector measurement

1140 I-CTsat. Thres. 0.2..50.0 A 20.0 Amps

1150 Sl Time Man.Cl 0.01..30.00 sec 0.2 Seconds

with without
Synchronism- Synchronism-
1151 MAN.CL check check
without
Synchronism-
check
NO

1155 3pole coupling with Pickup With Trip


with Trip

1156 Trip2ph Flt 3 pole 3 pole


1 pole, leading
phase
1 pole, lagging
phase

Distance
Protection data

1201 FCT Distance ON ON


OFF

1202 Minimum Iph> 0.10..4.00 A 0.100 Amps

1203 3I0> Threshold 0.05..4.00 A 0.100 A

1204 3U0> Threshold 1..100 V 5V

ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 10 OF
27
1207 3I0>/Iphmax 0.05..0.30 0.15

3I0>OR 3U0
1209A E/F Configuration 3I0>AND 3U0 3I0>OR 3U0

1215 Paral. Line Comp NO YES


YES

Blcok leading Block leading


1221 2Ph-E faults ph-e loop ph-e loop
block lagging
ph-e loop
all loops
only phase-
phase loops
only phase-
earth loops

with
Pickup(non-
1232 SOTF Zone directional) with Zone Z1B
with Zone Z1B
Inactive

0.10..250.00
1241 R load (ph-E) Ohm 46.5696

1242 Angle Load (ph-E) 20..60 degree 25.84

0.10..250.00
1243 R load (ph-ph) Ohm 46.570

1244 Angle load (ph-ph) 20..60 degree 25.84

Distance
Protection with
polygonal tripping
Chatracteristic

1301 Op. mode Z1 Forward Forward

ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 11 OF
27
Reverse
Non-directional
Inactive

0.05..250.00
1302 R(Z1) (ph-ph) Ohm 8.25

0.05..250.00
1303 X(Z1) Ohm 28.29

0.05..250.00
1304 RE(Z1) Ph-E Ohm 30.25

1305 T1 - 1 phase 0.00..30.00 sec 0.00 sec

1306 T1 - multi-phase 0.00..30.00 sec 0.00 sec

1307 Zone reduction 0..30 degree 0 degree

1311 Op.mode Z2 Forward Forward


Reverse
Non-Directional
Inactive

0.05..250.00
1312 R(Z2) ( ph-ph) Ohm 16.50

0.05..250.00
1313 X (Z2) Ohm 42.43

0.05..250.00
1314 RE(Z2) ph-E Ohm 38.50

0.00 - 30.00
1315 T2-1 phase sec 0.3 Secs

0.00 - 30.00
1316 T2- multi phase sec 0.3 Secs

ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 12 OF
27
1317 Trip 1 pole Z2 NO NO
YES

1321 Op. mode Z3 Forward Forward


Reverse
Non-Directional
Inactive

0.05..250.00
1322 R(Z3) ph-ph Ohm 27.50

0.05..250.00
1323 X(Z3) Ohm 44.20

0.05..250.00
1324 RE(Z3) ph-E Ohm 46.75

1325 T3 DELAY 0.00..30.00 sec 1.0 secs

1325 T3 DELAY 0.00..30.00 sec 1.0 secs

1331 Op. mode Z4 Forward Reverse


Reverse
Non-Directional
Inactive

0.05..250.00
1332 R(Z4) ph-ph Ohm 27.50

0.05..250.00
1333 X(Z4) Ohm 3.54

0.05..250.00
1334 RE(Z4) ph-E Ohm 46.75

1335 T4 DELAY 0.00..30.00 sec 1.1 Secs

Non-
1341 Op. mode Z5 Forward Directional
ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 13 OF
27
Reverse
Non-Directional
Inactive

0.05..250.00
1342 R(Z5) ph-ph Ohm 33.00

0.05..250.00
1343 X ( Z5 ) Ohm 53.04

0.05..250.00
1344 RE(Z5) ph-E Ohm 56.10

1345 T5 DELAY 0.00..30.00 sec INFINITE

0.05..250.00
1346 X(Z5) - Ohm 53.04

1351 Op. mode Z1B Forward Forward


Reverse
Non-Directional
Inactive

0.05..250.00
1352 R(Z1B) ph-ph Ohm 16.50

0.05..250.00
1353 X(Z1B) Ohm 42.43

0.05..250.00
1354 R(Z1B) ph-E Ohm 38.50

0.00 - 30.00
1355 T1B-1 phase sec 0.0 secs

0.00 - 30.00
1356 T1B- multi phase sec 0.00 sec

1357 1st AR-> Z1B NO NO


YES
ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 14 OF
27

Note : Settings
form1401 to 1452
are not Applicable
as these are for
Ohmic
characteristics

1401 Op. mode Z1 Forward NA


Reverse
Inactive

0.05..200.00
1402 ZR(Z1) Ohm NA

1411 Op. mode Z2 Forward NA


Reverse
Inactive

0.05..200.00
1412 ZR(Z2) Ohm NA

1421 Op. mode Z3 Forward NA


Reverse
Inactive

0.05..200.00
1422 ZR(Z3) Ohm NA

1431 Op. mode Z4 Forward NA


Reverse
Inactive

0.05..200.00
1432 ZR(Z4) Ohm NA

1441 Op mode Z5 Forward NA


Reverse
Inactive

ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 15 OF
27
0.05..200.00
1442 ZR(Z5) Ohm NA

1451 Op mode Z1B Forward NA


Reverse
Inactive

0.05..200.00
1452 ZR(Z1B) Ohm NA

Power Swing
Settings

all zones Z2 to Z5
2002 P/S Op. mode blocked blocked
(as per
regional
Z1/Z1B blocked philosophy)
Z2 to Z5
bocked
1.Z1B,Z2
blocked

2006 Power Swing trip NO NO


YES

Trip delay after Power


2007 Swing Block 2 sec

Distance
protection
teleprotection
Schemes

PUTT(Z1B
2101 FCT Telep. Dis. ON acceleration)
PUTT(Z1B
acceleration)
POTT
ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 16 OF
27
OFF

2102 Type of Line Two terminals Two terminals


Three terminals

0.00 - 30.00
2103 Send Prolong sec 0.10 sec

0.00 - 30.00
2107 Delay for alarm sec NA

0.00 - 30.00
2108 Release Delay sec NA

0.00 - 30.00
2109 TrBlk Wait Time sec NA

0.00 - 30.00
2110 TrBlk Block Time sec NA

2201 FCT Direct Trip ON OFF


OFF

0.00 - 30.00
2202 Trip time DELAY sec NA

2401 FCT SOTF-O/C ON ON


OFF

2404 I>>> 0.00 - 25.00 A 1.0 Amp

Weak End Infeed

2501 FCT Weak Infeed OFF OFF


Echo only
Echo and Trip

ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 17 OF
27
0.00 - 30.00
2502 Trip/Echo DELAY sec NA

0.00 - 30.00
2503 Trip EXTENSION sec NA

2505 UNDERVOLTAGE 2..70 V NA

Back up O/C
current Function
Settings

2601 Operating Mode ON OFF


Only Active
with Loss of
VT sec. Circuit
OFF

2610 1ph> 0.10..25.00 A NA

2611 T1ph> 0.00..30.00 sec NA

2612 310>>PICKUP 0.05..25.00 A NA

2613 T 310>> 0.00..30.00 sec NA

2614 I>> Telep/B1 NO NO


YES

2615 l>> SOTF NO NO


YES

2620 1ph> 0.10..25.00 A NA

2621 T 1ph> 0.00..30.00 sec NA

2622 310> 0.05..25.00 A NA

ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 18 OF
27
2633 T 310> 0.00..30.00 sec NA

2624 I> Telep/B1 NO NO


TES

2625 I> SOTF NO NO


YES

2630 Iph> STUB 0.10..25.00 A 1.5 A

2631 T Iph STUB 0.00..30.00 sec 0.1 sec

2632 310> STUB 0.05..25.00 A 1.5 A

2633 T 310> STUB 0.00..30.00 sec 0.1 sec

2634 I -STUB Tele/B1 NO NO


YES

2635 I -STUB SOTF NO NO


YES

2640 Ip> 0.10..4.00 A NA

2642 T lp Time Dial 0.05..3.00 sec NA

2643 Time Dial TD lp 0.50..15.00 NA

2646 T lp Add 0.00..30.00 sec NA

2650 310p PICKUP 0.05..4.00 A NA

2652 T 310p Time Dial 0.05..3.00 sec NA

2653 Time Dial TD310p 0.50..15.00 NA

2656 T 310p Add 0.00..30.00 sec NA

ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 19 OF
27
2660 IEC Curve Normal Inverse NA
Very Inverse
Extremely
Inverse
Long time
inverse

2661 ANSI Curve Inverse NA


Short inverse
Long inverse
Moderately
inverse
Very Inverse
Extremely
Inverse
Definite inverse

2670 l(310)p Tele/B1 NO NO


YES

2671 l(310)p SOTF NO NO


YES

2680 SOTF Time DELAY 0.00..30.00 sec 0.2 sec

Supervision
function Settings

2901 MEASURE SUPERV ON OFF


YES

2902 BALANCE U-LIMIT 10..100 V NA

2903 BAL. FACTOR U 0.58..0.95 NA

2904 BALANCE LIMITE 0.10..1.00 A NA

2905 BAL. FACTOR 1 0.10..0.95 NA

ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 20 OF
27

2906 El THRESHOLD 0.05..2.00 A NA

2907 El FACTOR 0.00..00.95 NA

2910 FUSE FAIL MON ON ON


OFF

2911 FFM U> (min) 10.100 V 50 Volts

2912A FFM U> (max) 0.10..1.00 A 0.2 Amps

2913A FFM U<max (3ph) 2..100 V 5V

2914A FFM ldelta (3p) 0.05..1.00 A 0.10 A

2921 T mcb 0..30 ms 0 ms

Earth Fault
Overcurrent
Settings

3101 FCT EarthFltO/C ON ON


YES

With every With every


3102 BLOCK for Dist. Pickup Pickup
with single-
phase Pickup
with multi-
phase Pickup
NO

3103 BLOCK 1pDead Tim YES YES


NO

3104 lph-STAB Slope 0- 30 % 10%

ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 21 OF
27
3105 31oMin Teleprot 0.01..1.00 A NA

3105 31oMin Teleprot 0.003..1.000 A NA

3110 Op. mode 310 >>> Forward Inactive


Reverse
Non-Directional
Inactive

3111 310>>> 0.50..25.00 A NA

3112 T 310>>> 0.00..30.00 sec NA

3113 310>>>Telep/Bl NO NO
YES

3114 310>>>SOTF-Trip NO NO
YES

3115 310>>>InrushBlk NO YES


YES

3120 Op. mode 310>> Forward Inactive


Reverse
Non-Directional
Inactive

3121 310>> 0.20..25.00 A NA

3122 T 310>> 0.00..30.00 sec NA

3123 310>>Telep/Bl NO NO
YES

3124 310>>SOTF-Trip NO NO
YES

3125 310>>InrushBlk NO YES


ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 22 OF
27
YES

3130 Op. mode 310> Forward Inactive


Reverse
Non-Directional
Inactive

3131 310> 0.20..25.00 A NA

0.003..25.000
3132 T 310> A NA

3133 310>Telep/Bl NO NO
YES

3134 310>SOTF-Trip NO NO
YES

3135 310>InrushBlk NO YES


YES

3140 Op. mode 310p Forward Forward


Reverse
Non-Directional
Inactive

3141 310p PICKUP 0.20..25.00 A 0.1 Amps

3142 T 310p MinT DELAY 0.00..30.000 A NA

3143 310p Time Dial 0.05..3.00 sec 0.37

3144 310p Time Dial 0.50..15.00 NA

3145 310p Time Dial 0.50..15.00 sec NA

3146 T 310p MaxT DELAY 0.00..30.00 sec NA

ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 23 OF
27
3147 Add.T-DELAY 0.00..30.00 sec NA

3148 310p Telep/B1 NO NO


YES

3149 310p SOTF-Trip NO NO


YES

3150 310p InrushBlk NO YES


YES

3151 IEC curve Normal Inverse Normal Inverse


Very Inverse
Extremely
Inverse
Long time
Inverse

3152 ANSI Curve Inverse NA


Short Inverse
Long Inverse
Moderately
Inverse
Very Inverse
Extremely
Inverse
Definite Inverse

Logarithmic
3153 LOG Curve Inverse NA

3154 310p Startpoint 1.0..4.0 NA

with UO and 1Y with U2 and 12


3160 POLARIZATION (dual (negative
polorized) sequence)
with 1Y
(transformer
star
point current)
ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 24 OF
27
with U2 and 12
(negative
sequence)

3162 Dir. ALPHA 0..360 degree 338 degree

3163 Dir. BETA 0..360 degree 122 degree

3164 3U0> 0.5..10.0 V NA

3165 IY> 0.05..1.00 A NA

3166 3U2> 0.5..10.0 V 5V

3167 312> 0.05..1.00 A 0.1 A

3170 2nd InrushRest 10..45% NA

3171 Imax InrushRest 0.50..25.00 A NA

with Pickup
3172 SOTF Op. Mode (non- NA
directional)
with Pickup and
direction

3173 SOTF Time DELAY 0.00..30.00 sec 0.00 sec

Teleprotection for
Earth fault Relay

3201 FCT Telep. E/F ON OFF


OFF

3202 Line Config. Two Terminals NA


Three
Terminals

3203 Sed Prolong. 0.00..30.00 sec NA

ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 25 OF
27

3207 Delay for alarm 0.00..30.00 sec NA

0.00..30.000
3208 Release Delay sec NA

3209 TrBlk Wait Time 0.00..30.00 sec NA

3210 TrBlk lock time 0.00..30.00 sec NA

Auto reclose
Function

3401 Automatic Reclosure ON / OFF OFF

Synchronism
Function

3501 FCT Synchronism ON/ OFF OFF

Voltage Protection
Function

U>Alarm
3701 U Phase-e>(>) OFF U>>Trip
ALARM ONLY
ON
U>Alarm
U>>Trip

3702 Uph -e> 1.0-170V; 69.85

0.00-30.00
3703 T Uph -e > secs 5 sec for Ckt-I

3704 Uph -e>> 1.0-170V; 95.26

ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 26 OF
27
0.05 - 0.50
3705 T Uph-e>> secs 0.1 secs

3721 3 Uo > Staus OFF ALARM ONLY


ALARM ONLY
ON

3722 3 Uo 1.00 -220 volts 30 volts

3723 3 Uo Reset ratio 0.50 - 0.95 0.95

3724 T 3 Uo 0.00- 0.30 secs NA

3725 T sen Impulse 3Uo 0.05-0.50secs NA

Fault Locator
Settings

3802 START Pick Up Pick up


Trip

Parallel line
3805 Compensation NO YES
YES

3806 Load Compensation NO NO


YES

Breaker Failure
Function Settings

3901 FCT Breaker Failure ON OFF


OFF

Trip Circuit
supervision

ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION


Format No. MR/ENGG/07 Rev-0

RECOMMENDED RELAY SETTINGS PRPD : DEPTT: ENGINEE


FOR 7SA522(M-I) 400kV ANGUL RING
S/c line
DATE : REV :
AT BOLANGIR S/S CHKD : 28-03-2013 NO.: 00
SUBSTATION APPD : THIS SHEET : 27 OF
27
4001 FCT Trip Supervision ON OFF
OFF

ABOVE SETTINGS IMPLEMENTED ON DATE ..

Signature (s/s in charge)

NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION