MR/ENGG/07 Rev-0
Setting
Addr. Setting Title Options Set Value
Configuration File
PUTT(Z1B
121 Teleprot. Dist. acceleration) PUTT
POTT
UNBLOCKING
BLOCKING
Disabled
Dir. Comp.
132 Teleprot. E/F Pickup Disabled
UNBLOCKING
BLOCKING
Disabled
PUTT Over
Protection
interface
Enabled
Power System
Data
206 CT SECONDARY 1A 1
5A
Ux reference
transformer
Neutral Current
220 14 transformer Not connected of
Neutral Current
(of the parallel line
the protected
line)
Neutral Current
of
the parallel line
Starpoint
Curr.of earthed
power transf.
D R Settings
Dusplay
Targets on Display Targets
610 Flt Disp. LED/LCD every on every
Pickup Pickup
Display Targets
on TROP
only
615 Spont. Flt. Disc. NO YES
YES
Line Parametrs (
In
ohms/perkm/per
phase primary
ohms )
R1 = 0.02880
X1 = 0.3280
Ro = 0.28500
Xo = 1.0200
RoM = 0.0000
XoM = 0.0000
Zone Reaches ( In
percentage )
Z1 = 80.00%
Z1B = 120.00%
Z2 = 120.00%
Z3 = 125.00%
General
Protection Data
0.005..6.500
1110 x' Ohm/km 0.1804
0.005..10.500
1112 x' Ohm/mile NA
0.6..650.0
1113 Line Length Miles NA
AND Pole
Open Current
with
1136 Open Pole detector measurement
with without
Synchronism- Synchronism-
1151 MAN.CL check check
without
Synchronism-
check
NO
Distance
Protection data
3I0>OR 3U0
1209A E/F Configuration 3I0>AND 3U0 3I0>OR 3U0
with
Pickup(non-
1232 SOTF Zone directional) with Zone Z1B
with Zone Z1B
Inactive
0.10..250.00
1241 R load (ph-E) Ohm 46.5696
0.10..250.00
1243 R load (ph-ph) Ohm 46.570
Distance
Protection with
polygonal tripping
Chatracteristic
0.05..250.00
1302 R(Z1) (ph-ph) Ohm 8.25
0.05..250.00
1303 X(Z1) Ohm 28.29
0.05..250.00
1304 RE(Z1) Ph-E Ohm 30.25
0.05..250.00
1312 R(Z2) ( ph-ph) Ohm 16.50
0.05..250.00
1313 X (Z2) Ohm 42.43
0.05..250.00
1314 RE(Z2) ph-E Ohm 38.50
0.00 - 30.00
1315 T2-1 phase sec 0.3 Secs
0.00 - 30.00
1316 T2- multi phase sec 0.3 Secs
0.05..250.00
1322 R(Z3) ph-ph Ohm 27.50
0.05..250.00
1323 X(Z3) Ohm 44.20
0.05..250.00
1324 RE(Z3) ph-E Ohm 46.75
0.05..250.00
1332 R(Z4) ph-ph Ohm 27.50
0.05..250.00
1333 X(Z4) Ohm 3.54
0.05..250.00
1334 RE(Z4) ph-E Ohm 46.75
Non-
1341 Op. mode Z5 Forward Directional
ABOVE SETTINGS IMPLEMENTED ON DATE ..
0.05..250.00
1342 R(Z5) ph-ph Ohm 33.00
0.05..250.00
1343 X ( Z5 ) Ohm 53.04
0.05..250.00
1344 RE(Z5) ph-E Ohm 56.10
0.05..250.00
1346 X(Z5) - Ohm 53.04
0.05..250.00
1352 R(Z1B) ph-ph Ohm 16.50
0.05..250.00
1353 X(Z1B) Ohm 42.43
0.05..250.00
1354 R(Z1B) ph-E Ohm 38.50
0.00 - 30.00
1355 T1B-1 phase sec 0.0 secs
0.00 - 30.00
1356 T1B- multi phase sec 0.00 sec
Note : Settings
form1401 to 1452
are not Applicable
as these are for
Ohmic
characteristics
0.05..200.00
1402 ZR(Z1) Ohm NA
0.05..200.00
1412 ZR(Z2) Ohm NA
0.05..200.00
1422 ZR(Z3) Ohm NA
0.05..200.00
1432 ZR(Z4) Ohm NA
0.05..200.00
1452 ZR(Z1B) Ohm NA
Power Swing
Settings
all zones Z2 to Z5
2002 P/S Op. mode blocked blocked
(as per
regional
Z1/Z1B blocked philosophy)
Z2 to Z5
bocked
1.Z1B,Z2
blocked
Distance
protection
teleprotection
Schemes
PUTT(Z1B
2101 FCT Telep. Dis. ON acceleration)
PUTT(Z1B
acceleration)
POTT
ABOVE SETTINGS IMPLEMENTED ON DATE ..
0.00 - 30.00
2103 Send Prolong sec 0.10 sec
0.00 - 30.00
2107 Delay for alarm sec NA
0.00 - 30.00
2108 Release Delay sec NA
0.00 - 30.00
2109 TrBlk Wait Time sec NA
0.00 - 30.00
2110 TrBlk Block Time sec NA
0.00 - 30.00
2202 Trip time DELAY sec NA
0.00 - 30.00
2503 Trip EXTENSION sec NA
Back up O/C
current Function
Settings
Supervision
function Settings
Earth Fault
Overcurrent
Settings
3113 310>>>Telep/Bl NO NO
YES
3114 310>>>SOTF-Trip NO NO
YES
3123 310>>Telep/Bl NO NO
YES
3124 310>>SOTF-Trip NO NO
YES
0.003..25.000
3132 T 310> A NA
3133 310>Telep/Bl NO NO
YES
3134 310>SOTF-Trip NO NO
YES
Logarithmic
3153 LOG Curve Inverse NA
with Pickup
3172 SOTF Op. Mode (non- NA
directional)
with Pickup and
direction
Teleprotection for
Earth fault Relay
0.00..30.000
3208 Release Delay sec NA
Auto reclose
Function
Synchronism
Function
Voltage Protection
Function
U>Alarm
3701 U Phase-e>(>) OFF U>>Trip
ALARM ONLY
ON
U>Alarm
U>>Trip
0.00-30.00
3703 T Uph -e > secs 5 sec for Ckt-I
Fault Locator
Settings
Parallel line
3805 Compensation NO YES
YES
Breaker Failure
Function Settings
Trip Circuit
supervision