Case: When Both DC incoming 1 and incoming 2 are ON and Bus coupler is OFF, DC under voltage occurs
at incoming 1.
6. Simultaneously with the de-energization of 1K2 its NC contacts (31-32) closes and supply flows
through 1K3 NC contacts (21-22) and reaches to energize Timer relay 44K4, relay 44K1 and
breaker 44Q1 under voltage relay.
7. As timer relay 44K4 energizes after a delay contact (15-18) are closed, also with energization of
relay 44K1 NO contacts (13-14) also closes. This make the path of DC supply to Close coil of
breaker and Breaker 44Q1 is switched ON.
With the energization of 1K2 relay its NC contacts (31-32) opens and supply flowing from 1K3 Contacts
(2