TYPE CAM-333
Made for the preparation of automatic emergency intervention switchboards.
This controls and commands the genset unit. It commands the mains and generator
contactors to supply the user.
INSTRUCTION AND USER MANUAL
DISPLAYING:
13 INSTRUMENTS
(Simultaneous reading
of 6 instruments)
ERROR MESSAGES
USEFUL PROGRAMMING
GENERATOR SET
MANAGEMENT
PARMA ITALY
GB CAM-333/1
www.elcos.it 1
6XPPDU\
Technical data 2
Brief instructions 3
,QVWUXPHQWV 3
2SHUDWLRQ
Functions selection. Manual, Automatic, Test 4
Off/Reset, Start up, Stop, Detection of engine running, Clock 5
Generator set protection devices, General alarm, Preventive maintenance, Communication port
remote operation (on request) 6
Call start and stop commands enabled with control unit in automatic, Emergency stop, Stopping failure
Voltmetric mains and generator relays inside control unit, Three-phase mains relay,
Two-phase generator relay 7
3URJUDPPLQJ
7(&+1,&$/'$7$
Battery power supply: 12 VDC and 24 VDC
Supply voltage: 8 32V
For generators with nominal voltage: 220 450Vac 10%; frequency 50 60Hz
Consumption with stopped engine: 70mA at 12V 40mA at 24V
Max consumption 190mA at 12V 130mA at 24V
Nominal insulation voltage:
- Terminal board of mains: 380V
- Terminal board of generator: 450V
- Terminal board of battery: 32V
Amperes of contacts for gen./mains contactors: 250V 3A
Max amperes of the outputs 15 (starting) 3W
17 (stopping) 7W, 19 (key) 3W,
70 (general alarm) 3W
Degree of rear protection: IP20
Degree of front protection: IP 64
Temperature range: 10 +50 C
Weight: 410 g
Dimensions 144x96x49 mm
Hole 88X136 mm
Hour-meter: 4 digits
Battery voltmeter: Max 38V, Precision 2%
Mains voltmeter Max 500V, Precision 2%
Generator voltmeter: Max 500V, Precision 2%
Generator ammeters: Max 2400A, Precision 2%
Frequency-meter: 0-85 Hz, Precision 0,1 Hz
Voltammeter Max 1500kVA, Precision 4%
Tachometer Max 4000 RPM Precision 10 RPM
Serial output parameters 9600 baud, 8 bit data, 1 bit stop; no parity
2 GB CAM-333/1
%5,(),16758&7,216
CUMULATIVE GENERATOR IS PUSH BRIEFLY
MAINS IS
ALARM DISPLAY TO SHOW THE
ONTO USER ONTO USER
INSTRUMENTS,
PUSH FOR LONG
TIME TO CHECK
THE FUNCTIONING
OF THE LED TEST.
PUSH TO SILENCING OF
START THE GENERAL
ENGINE ALARM.
WHEN THE
CONTROL
IS IN
MANUAL
FUNCTION
PRESS TO
SELECT THE
0$1
FOLLOWING
PUSH TO FUNCTIONS:
STOP THE $87 MANUAL
ENGINE AUTOMATIC
WHEN THE 7(67 TEST
CONTROL RESET:
UNIT - RESETS THE
IS IN 2))5(6(7 CONTROL
MANUAL C
UNIT
FUNCTION - STOPS THE
GENSET
- PREVENTS
STARTING
ZZZHOFRVLW
KEY ENABLED WHEN
MAINS VOLTAGE THE CONTROL UNIT
IS PRESENT IS IN MANUAL OPERATION,
PRESS TO DIVERT GENERATOR
ENGINE IS
VOLTAGE IS
THE MAINS TO THE RUNNING
POWER USERS, OR TO THE PRESENT
GENERATOR WHEN THE
ENGINE IS RUNNING
,167580(176
Normally the display THREE MAINS For three-phase voltages up to 500 V~ connected on CBV-015.
shows three mains VOLTMETERS
voltmeters. With the THREE GENERATOR Compatible with the amperometric transformers of type 30/5,
engine running the AMMETERS 40/5, 50&5, 60/5, 80/5, 100/5, 200/5, 250/5, 300/5, 400/5, 500/5,
600/5, 800/5, 1000/5, 1200/5, 1500/5, 2000/5. Maximum reading
generator set of 2000A or 110% of the base scale current of the chosen
transformer.
instruments are shown.
GENERATOR
In the event of a fault, VOLTMETER For single-phase or two-phase of nominal value up to 500 V~.
instead of the GENERATOR From 0 Hz to 85 Hz for alternating voltages with amplitude
measurement, the FREQUENCY METER greater than 20 V~.
display shows the VOLTAMMETER Displays apparent power up to 1500KVA
message of the fault. BATTERY For voltages between 9 and 38 volt.
VOLTMETER
The data can be HOUR-METER With four figures and a maximum reading of 9999. The
transmitted hour-meter numbers flash when it is necessary to perform the
periodic maintenance operations planned by the manufacturer
(by cable or of the genset unit.
GSM modem)
STARTUP COUNTER Displays the number of startups that have occurred up to 9999.
to a personal
computer. TACHOMETER Displays the number of engine revs up to 8500 rpm.
6,08/7$1(2865($',1*2)7+(,167580(176
- WITH MAINS PRESENT: 3 MAINS VOLTMETERS
- WITH ENGINE RUNNING: GENSET VOLTMETER, GENSET FREQUENCY
METER, 3 GENSET AMMETERS, HOUR-METER.
GB CAM-333/1 3
23(5$7,21
0$1
)81&7,216(/(&7,21
$87
The function selected
7(67 with the key is shown by
2))5(6(7 the associated warning light.
0$18$/
The control unit commands are enabled.
Starting with key 67$57 , stopping with key 6723 (keep pressed until the engine stops).
$8720$7,&
When a fault occurs on the mains, detected by the internal voltmetric relay, or by an external call, once the MAINS
FAULT STARTUP DELAY time has elapsed (programmed to 1 sec.), the control unit commands the opening of
the mains contactor control, and starts the generator set. With engine running and generator voltage normal and
once the GENERATOR CONNECTION TO POWER USERS DELAY has elapsed (programmed to 5 sec.)
the generator contactor closes.
While it is running the generator set is protected from possible faults. When the mains voltage is restored and the
MAINS ACCEPTANCE time has elapsed (programmed to 100 sec.), after the GENERATOR-MAINS
INTERLOCK time (programmed to 1 sec.), the mains contactor closes. The COOLING TIME (programmed
to 120 sec.) Then allows the engine to be cooled easily before it is stopped.
7(67
7(67
On pressing key , we obtain the engine startup cycle as in automatic, and the power users
remain supplied by the mains. If a mains fault occurs during the test, the power unit remains in test mode,
positions itself as in automatic operation and commands the closing of the generator contactor.
WEEKLY AUTOTEST
ENABLED WITH POWER UNIT IN AUTOMATIC OR TEST MODE
If the lever is positioned on TEST ENGAGED the general alarm is activated intermittently (for 8 sec.). When the
general alarm is deactivated, and after a pause of 3 seconds, the engine starts and continues to run for the
WEEKLY TEST TIME (programmed to 3 minutes).
This test will be repeated automatically every week on the exact day and at the hour to which the TEST ENGAGED
lever has been positioned. During the automatic test cycle, WEEKLY TEST is shown on the display.
STOPPING OF ENGINE DURING THE TEST
Press key .
The weekly test cycle is therefore obtained as if the switch had been repositioned.
4 GB CAM-333/1
23(5$7,21
2))5(6(7
2))5(6(7
When key is pressed until Led comes on.
The engine cannot be started in any way and, if the running engine is stopped without carrying out engine
cooling; it reactivates the protection devices and all the stopped functions. The mains contactor stays closed.
The Leds and the instruments are active.
67$5783
67$57
- In manual with key .
- In automatic, when a mains fault occurs, as detected by the internal voltmetric relay or with the remote
controls, and after the MAINS FAULT STARTUP DELAY (programmed to 1 second) time has elapsed.
To make starting easier, a special circuit establishes a series of programmable startups (programmed
to 4 STARTUPS); the number of startups, the length of the pause time and the start up time can
be programmed.
STARTING FAILURE
If the whole series of attempts is unable to start the engine, at the end of this cycle STARTING FAILURE
is shown on the display and the stop signal is activated.
6723
6723
- In PDQXDO mode using key .
- In 7HVW mode when the protection systems or the remote controls intervene.
- In DXWRPDWLF mode when the mains power returns, or when the protection systems or remote
controls intervene.
Stopping can occur in two ways:
With the solenoid deactivated while the engine is running and activated when stopped. This condition is
maintained during the STOP TIME (programmed to 20 seconds) after the engine stopped detection.
With solenoid or electro-valve activated while the engine is running and deactivated when stopped.
This condition is maintained even when the engine is stationary.
'(7(&7,212)(1*,1(5811,1*
This is obtained with detection (adjustable P1) of the battery charger alternator voltage
(PERMANENT MAGNETS or PRE-EXCITATION) and from the frequency and residual voltage of
the generator. When detection has been made it disconnects the starter motor and lights the LED .
&/2&.
It allows generator set operation or stopping to be programmed. In AUT operation.
67$57,1*
GB CAM-333/1 5
23(5$7,21
*(1(5$7256(73527(&7,21'(9,&(6
The intervention of the fault is displayed; it can cause the engine to be stopped and activates the general
alarm. SEE TABLE on page 13.
FAULT DISPLAY
The display usually shows the mains voltmeters. When the engine is running the generator set instruments
are shown.
When there is a fault, instead of the reading, the display shows the intervened fault message, and the
associated LED flashes.
FAULT RESET
Reactivates protection devices and all stopped functions, by pressing key , until the RESET LED
comes on.
*(1(5$/$/$50
This is produced by mounting an acoustic signal, linked to the appropriate terminal.
It can be arranged so that it is activated continually or for a set time.
35(9(17,9(0$,17(1$1&(
When preventive maintenance operations need to be carried out, the figures of the hour-meter flash while the
number of the intervened maintenance appears.
The timing for the maintenance operations and the procedure for zeroing the time up maintenance indication
can be programmed by the manufacturer of the generator set unit.
&20081,&$7,213257
5(027(23(5$7,21215(48(67
When the special adaptor cable is connected to a personal computer remote operation is possible, in various
ways, using a programme for the Windows operating system. The instructions for use and loading are on the
program disk.
6 GB CAM-333/1
&$//67$5783$1'6723&200$1'6
(1$%/(':,7+&21752/81,7,1$8720$7,&
CALL
On closing the call contact (see page 10), operation is as with mains fault.
(1$%/(':,7+&21752/81,7,1$8720$7,&
START UP
When the start up contact (see page 10) is closed REMOTE STARTUP is shown on the display. After the
REMOTE STARTUP DELAY time (programmed to 1 sec.) has elapsed, the start up begins, the general
alarm is activated intermittently (for 8 seconds), then the general alarm is deactivated and after a pause of
3 seconds the start up cycle begins and operation is as with mains fault.
STOP
When the test contact is closed REMOTE TEST is shown on the display.
The control unit does not allow any start up operation, and if the generator set is running it is stopped.
(0(5*(1&<6723
The emergency stop can be activated in all working conditions, by mounting one or more click down push.
The stop is immediate (without engine cooling) and EMERGENCY STOP is shown on the display.
Do not use the emergency push-button linked to a stop system that is not energized when the unit is
running.
67233,1*)$,/85(
This intervenes if the engine running signal is detected 60 seconds after the stop command.
STOPPING FAILURE will be read on the display.
92/70(75,&0$,16$1'*(1(5$7255(/$<6
These check the mains and generator set voltage. They intervene when there is over-voltage (generator
only), or voltage value failure or lowering even on just one phase of the voltage value.
The relay is divided into two parts: the mains input part is managed by CBV-015-type equipment,
the adjustments of the times and thresholds are managed by the control unit.
OPERATION
When voltage has been detected on the three phases, with a value within the preset limits, and after the
PDLQVYROWDJHSUHVHQW delay (programmed to 100 sec.), the generator set stops. When the voltage goes
down, so going outside the normal range, the generator set starts (for the starting and stopping procedures
see automatic operation on page 4).
When voltage is detected on the two phases of the running generator set, with a value within the preset
limits, and after the GENERATOR CONNECTION TO POWER USERS delay (programmed to 5 sec.) the
generator contactor is closed. When the voltage goes up or down, so going outside the normal range, the
generator contactor becomes de-energized.
GB CAM-333/1 7
352*5$00,1*
TO BE CARRIED OUT WITH THE ENGINE OFF BEFORE
ENABLING POWER UNIT OPERATION
1RUPDOO\LWLVUHDG\IRURSHUDWLRQZLWMXVWWKHSURJUDPPLQJRIWKHDPSHURPHWULFWUDQVIRUPHU
*(16(7
6723 *(1(5 3527(& %$7 0$,16 0$,16
6<6 $725 7,216 :((./< 7(5< *(16(7 5(/$<
7(06 )5( ,10$1 $872 92/7 92/7 &%9
48(1&< 8$/ 0$7,& $*( $*(
7(67
(;&, :,7+ (1 127
7(',1 287 9 6,1*/( &21
6723 +] 3+$6( 1(&7('
2102'( 6723 *$*('
(;&, +] :,7+ (;&/8 9 7+5(( &21
7(',1 6723 '(' 3+$6( 1(&7('
'5,9(
02'(
DIP$ DIP B
6(77,1*2)5811,1*(1*,1(7+5(6+2/'
FOR PRE-EXCITATION OR PERMANENT-
MAGNET RECHARGE ALTERNATOR
It is not usually necessary to perform any calibration operations.
If, however, such operation should prove WHERE THERE IS A PRE-EXCITATION
necessary, perform the following operations: ALTERNATOR HOOK THE DIVERTER
- Start the engine manually and turn it to the IN THE POSITION CORRESPONDING
minimum running speed. Engine threshold TO THE RATED VOLTAGE OF THE
running speed 12 24 BATTERY (12 - 24V).
- Turn the potentiometer P2 anti-clockwise VOLT '2127+22.:,7+27+(5
until the indicator light is on. 7<3(62)$/7(51$7256
- Bring the engine back up to rated speed.
1 2 3 4 5 6 7 8 910
ON Move DIP-B
switches 1-3-5-7-9 MOVE ALL THE DIP-B
1 2 3 4 5 6 7 8 910 to21 SWITCHES BACK TO
Press for at
2)).
least 1
second, 34
J20 DIP-A1
352*5$00,1*2)7+()2//2:,1*,6127 until the 33
writing
5(6725('
R202
R205
R203
K1
(0(5*(1&<67233$*( (0(5*(1&<386+%87721
C201
This can be obtained in all operating Remove the jumper if the emergency
JP10 K2
conditions, by mounting one or button is mounted.
K4
K3
C202
more push/buttons (release). Mai installare un pulsante
demergenza abbinato ad un S10
C204
C203
M13
sistema darresto che
non sia eccitato in marcia.
AUTOMATIC EXIT
Move DIP-B
1
1
switch 1 to 21
(/ FROM PROGRAMMING
6723 3AMP. TRANSFORMER When 3 minutes have passed during which no switch
AMP. TRANSFORMER 67$57 0 programmers has been moved and no keys have been
$ 100/5
50/5
Press to choose ;( pressed, the control unit will exit the programming.
Press and wait until
the value of the the writing appears:
amperometric THE CONTROL UNIT ACCEPTS
transformer. PROGRAMMED COMPLETE PROGRAMMING ONLY
AUTOMATIC CALIBRATION (A.C.)
GENERATOR OVERLOAD GEN. OVERLOAD To abandon an incomplete programming
FAULT FAULT (without confirmation as shown by the written
GENERATOR OVERLOAD 95A item PROGRAMMED) move all the DIP-B
Once the A.C. has been programmed switches to OFF.
the thresholds set themselves automatically.
The FAULT threshold is set to 95%, the GENERATOR
overload threshold to 100% of the OVERLOAD
nominal value of the A.C. 100A
To change the thresholds manually
see page 16.
8 GB CAM-333/1
67$57,1*7,0(6WDUWXSDWWHPSWRSHUDWLRQWLPH
21 Move DIP-B 21 Move DIP-B
2 switch 2 to ON 2 switch 2 to OFF
Time 5 sec.
67$57,1* 6723 Decreases
7,0( Increases 67$57 5 sec.
Press and wait for
Press to Press to change the time PROGRAMMED to be written
display
3$86(7,0(3DXVHEHWZHHQVWDUWXSDWWHPSWV
21 Move DIP-B 21 Move DIP-B
switch 2 to ON 2 switch 2 to OFF
2
Time 5 sec.
3$86(
7,0( Increases 67$57 6723 Decreases 5 sec.
Press and wait for
Press to Press to change the time PROGRAMMED to be written
display
GB CAM-333/1 9
:,5,1*',$*5$0
DETECTION OF
MAINS THREE-
PHASE
MAX500VAC
50 60Hz
FOR CORRECT
OPERATION THE
&$0
THREE PHASES AND
NEUTRAL MUST BE
CONNECTED
9 :
~
GENERATOR
( AMMETERS
(3 6$+ ; 9 /
<7 9% 3 $0 = FOR THE CONNECTION
& 6 (( 7 + 8 / OF A SINGLE
1, 5 8 AMMETER USE
$ + 31 1
07, / TERMINALS 75-77
,& '(7(&7,212)0$,16*(1(5$72592/7$*(
5 <$/ 57( ( 0$,1692/70(75,&5(/$< !
(* (5 0 *$
FOR SINGLE PHASE SYSTEMS MOVE
Voltage on terminals DIP-A SWITCH 6 TO ON (see page 9).
5$ ,& 7/2 /72 86-87-88-89 is 1/100 of Neutral phase connections
+& 57 9 < 9 78
the alternating voltage, MAINS 90 -91 (CBV-015) 86-87 (CAM-333)
connected on mains terminals
< (0 61 $ 61 3 GENERATOR 96 - 97 (CAM-333)
5( 7/ ,$ /( ,$ 78
90-91-92-93 of
CBV-015.
77 29 0 5 0 2 OUTPUTS (+) MAX
REMOTE
$% '
EXAMPLE: CONTROLS
<5 With voltage of 220 V between terminals WITH CONTROL
1$ (7 90-91 of CBV-015; a voltage of 2,2 V is 3W 7W 3W UNIT IN
7$ measured between terminals 86-87 of AUTOMATIC
%
CAM-333. 10m MAX
With voltage of 380 V between terminals
EMERGENCY PUSH-BUTTON
PROTECTION INPUTS
The tester used to measure the described
/,
$9
START UP
START UP
$
We reserve the right to change the charectistics
STOP
STOP
{
CALL
SUPPLY
1
at any moment and without warning.
2.5mm min.
FU1 10m MAX
$
AVAILABLE
EMERG- AVAILABLE
ENCY
PUSH-
BUT-
TON
:
RELAY
50
30
STARTER
FUEL
FLOAT
+ -
30 85
RELAY
87 86 !
NEVER INSTALL THE EMERG-
ENCY PUSH-BUTTON LINKED
STOP TO A STOP SYSTEM WHICH IS NOT
ENERGIZED WHEN THE UNIT IS RUNNING
FU8
FU6
FU7
FU7 1A
FU8
COMMUNICATION
PORT
CONTACTORS
N1
CONTROL
MAINS FU2 $ U1
CONTACTS X-MAINS 400V
CAPACITY
MAX V1
3A 250VAC
GENERATOR FU3 $ KM-R KM-G W1
TWO-PHASE FU4 $ KM-G KM-R
DETECTION 8
GENERATOR INPUT
OF RUNNING
GENERATOR FU5 $
MAX 500VAC
5060Hz 9
,03257$17
TA2
GENERAL ALARM
ALTERNATOR
ALTERNATOR
PERMANENT
30 85
RELAY TA1
OUTPUT (+)
MAGNET
GENERAL
ALARM 87 86 N2
U2
X-USER 400V
V2
D+ W2
DETECTION IF THE LOW COOLANT LEVEL
OF ENGINE B+ FUNCTION IS NOT USED
RUNNING
CONNECT THE
YELLOW PRE-EXCITATION TERMINAL 50 TO GROUND
RED ALTERNATOR
YELLOW
&22/$17/(9(/352%(
R +
FOR RADIATORS WITH FOR RADIATORS WITH
PLASTIC EXPANSION TANKS METAL EXPANSION TANKS
GRGB L C
+
THERMO- REGULATOR
STATIC
SWITCH PERMANENT
MAGNET
ALTERNATOR
PRESSU- 155 155
FOR DIFFERENT SCREW ROD
RE ELECTRODES ELECTRODE
REGULATORS
SWITCH
ASK FOR DIAGRAM
- BEFORE CONNECTING THE CONTROL UNIT READ THE NOTES
ON PAGE 8. WHEN THE CONNECTIONS HAVE BEEN MADE
THE CONTROL UNIT IS 2))5(6(7 OFF.
5(027(67$5783'(/$<
:KHQWKHGHOD\WLPHLVXSWKHVWDUWXSEHJLQV
21 Move DIP-B 21 Move DIP-B
switch 2 to ON switch 2 to OFF
2 2
Intervention
5(027(67$5783 delay 1 sec.
'(/$< Increases 67$57 6723 Decreases 1 sec.
Press to Press and wait for
display Press to change the time PROGRAMMED to be written
*(1(5$/$/$50,16(57,217,0(
1XPEHUPHDQVFRQWLQXDORSHUDWLRQZLWKRXWWLPHOLPLWV
21 Move DIP-B 21 Move DIP-B
2 switch 2 to ON switch 2 to OFF
2
:((./<$8727(677,0(
:KHQWKHWHVWWLPHLVXSWKHHQJLQHVWRSV
21 Move DIP-B 21 Move DIP-B
switch 2 to ON switch 2 to OFF
2 2
Time 3 min.
:((./<$8727(67
7,0( Increases 67$57 6723 Decreases
3 min.
Press to change the time Press and wait for
Press to PROGRAMMED to be written
display
12 GB CAM-333/1
%$6,&7$%/(
352*5$00,1*
)76 &(
*(1(5$725 7+5(6+2/'6 ,17(59(17,21 8 + 72 21 6723
6(7
$ ,
1 ( 2*
1
0 * 35 /$ 5 72 )$
6
'(/$<
&
& 5
6
/, ,1
(
3527(&7,21 $5 2 7 (* 5 & ,17(59(17,212&&856:+(1
7 7
1( %$
2 9 $
',63/$< 1
$
7
1
7 5(*8 0(17 725< 2 * /( 0 ,2 8 <
,1)250$7,21 /$7,21 725< 5$1*( 1 1
' ,
2
6(77,1*
2
6
1
),(/' 6(77,1*
)
6(&21'6
BATTERY AL- Battery voltage remains lower than the
WAYS 812(12V) 11 (12V)
UNDER- AC-
15 2 YES NOT DOES NOT STOP programmed threshold for the whole of the
1624(24V) 22 (24 V)
VOLTAGE TIVE intervention delay time.
BATTERY WITH-
1218(12V) 16 (12V) Battery voltage exceeds the programmed
OVER- "
2436(24V) 32 (24V)
= 5 YES YES YES OUT
threshold for the whole of the intervention time.
VOLTAGE STOP
OVERTEMPE-
RATURE
DETECTED BY IMMEDI- The temperature exceeds the threshold set by the
" = = = YES NOT STOPS
THERMO- ATE thermostatic switch. No programming is possible.
STATIC
SWITCH
The fuel level remains lower than the programmed
WITH
NO FUEL " = = 15 3 YES YES YES
STOP
threshold for the whole of the intervention delay
time.
10 AFTER
LOW OIL DETEC- IMMEDI- The pressure is lower than the threshold set by the
TION OF = = = YES NOT STOP
PRESSURE ENGINE ATE pressure switch.
RUNNING
10 after 335V two-
GENERATOR the The generator voltage remains lower than the
phase
thresh- 80 WITH programmed threshold for the whole of the
UNDER- old is 193V 110 3 YES YES YES
400V~ STOP intervention delay time (opens the generator
VOLTAGE exceed- single-
contactor).
ed phase
GENER-
355V two- ATOR The voltage (controlled on two phases) stays
GENERATOR Al- phase CONNEC- permanently above the programmed threshold for
100
VOLTAGE ways 205V 115 TION TO NOT NOT DOES NOT STOP the whole of the delay time for generator
400V~ POWER
PRESENT active single- connection to power users (closes the genset
USERS
phase contactor)
DELAY 7
440V
After TWO-
GENERATOR detec- Generator voltage remains above the programmed
100 PHASE WITH
OVER- tion of 010 3 YES NOT YES threshold for the whole of the intervention delay
engine 500V~ 254V STOP
VOLTAGE time (opens the generator contactor).
running SINGLE-
PHASE
10 after
GENERATOR the Generator frequency remains lower than the
thresh- WITH programmed threshold for the whole of the
UNDER- old is 060Hz 0 Hz 010 5 YES NOT YES
STOP intervention delay time (opens the generator
FREQUENCY exceed- contactor).
ed
1 2
Available completely programmable faults.
See page 17.
GB CAM-333/1 13
(1*,1(352*5$00,1*
6(77,1*7+(7$&+20(7(5%ULQJWKHHQJLQHWRFRQVWDQWNQRZQUHYVIRUH[DPSOHXVLQJDWDFKRPHWHU
,QWKLVFDVHWKHVHWWLQJLVFDUULHGRXWZLWKWKHHQJLQHUXQQLQJ
21 Move DIP-B Threshold 21 Move DIP-B
1 2 switches 1-2 to ON Set the R.P.M. ENGINE 1 2 switches 1-2 to OFF
engine
3000 RPM R.P.M. ENGINE
7$&+20(7(5
revs
21 Move DIP-B
Threshold 21 Move DIP-B
switch 2 to ON 11 Volt. switch 2 to OFF
2 2
Intervention
2 sec.
%$77(5< delay 11 Volt.
81'(592/7$*( Increases 67$57 6723 Decreases 2 sec.
Press to Press and wait for
Press when the arrow is next to
display PROGRAMMED to be written
the parameter to be modified.
21 Move DIP-B
Threshold
16 Volt
21 Move DIP-B
2 switch 2 to ON Engine 2 switch 2 to OFF
NO STOP stopping
%$77(5< Increases
16 Volt.
29(592/7$*( with stop 67$57 6723
Decreases
without stop NO STOP
Press to (STOP) (NO STOP) Press and wait for
display Press when the arrow is next to
PROGRAMMED to be written
the parameter to be modified.
14 GB CAM-333/1
*(1(5$725352*5$00,1*
*(1(5$725'2(6 Increases
67$57 6723
Decreases
1276833/< with stop
(STOP)
without stop
(NO STOP) 60 sec. NO STOP
Press to Press when the arrow is next to Press and wait for
display the parameter to be modified. PROGRAMMED to be written
GB CAM-333/1 15
*(1(5$725352*5$00,1*
21 Move DIP-B
Threshold
60 Hz.
21 Move DIP-B
switch 2 to ON 2
switch 2 to OFF
2 Intervention
delay 2 sec.
60 Hz
*(1(5$725 67$57 6723
29(5)5(48(1&< Increases Decreases 2 sec.
Press to Press and wait for
Press when the arrow is next to
display PROGRAMMED to be written
the parameter to be modified
*(1(5$72529(5&855(17The protection can be regulated at two levels and intervenes when they are
excedeed. 'RHVQRWUHSODFHWKHRYHUORDGVZLWFKThe warning level acts only as a signal, while the other level
can be programmed to stop the engine. For example, if we choose transformer 100/5 the factory setting of the
overcurrent will trigger the intervention at 100A, but only when the amperometric transformer withstands that
current.
0$,16352*5$00,1*
627727(16,21(5(7(7KHJHQHUDWRUVHWVWDUWVLIDWOHDVWRQHSKDVHKDVDYDOXHORZHUWKDQWKHSURJUDPPHGWKUHVKROGDQG
WKHLQWHUYHQWLRQGHOD\KDVHODSVHG
21 Move DIP-B
Threshold
338 V.
21 Move DIP-B
2 switch 2 to ON 2 switch 2 to OFF
Intervention
delay 1 sec.
338 V.
/,1(0$,1
81'(592/7$*( Increases 67$57 6723 Decreases 1 sec.
Press and wait for
Press to Press when the arrow is next to PROGRAMMED to be written
display the parameter to be modified
16 GB CAM-333/1
352*5$00,1*2)$9$,/$%/()$8/76$1'/$1*8$*(&+2,&(
1 2
+2:72:5,7(
21 Move DIP-B
switch 6 to ON
1 :5,7(
Press to choose a letter or number, release
the key for at least 1 second; the letter or
EXAMPLE
1
7KHIDXOWQDPH number will remain written on the display.
)$,/85( GHVFULSWLRQLVILQLVKHG
3$5$//(/ 67$57 Press to Press to 6723
Press to read the functions leave a space delete &
and the delay to be programmed
FUNCTIONS TO BE PROGRAMMED DESCRIPTION
DESCRIBED ON THE DISPLAY
Choice of whether to stop the engine
NO STOP STOP
Choice of whether to store
NOT STORED STORED the cause of the alarm
32/$5,7< 32/$5,7< The probe intervenes when it closes or
ACTIVE AT GROUND ACTIVE OPEN opens to ground
$&7,9$7,21 $&7,9$7,21 Instant of probe
ALWAYS ACTIVE ACTIVE RUNNING activation
Choice of whether to cool the engine
COOLING NOT ACTIVE COOLING ACTIVE before stopping it
INTERVENTION DELAY The intervention occurs when the
(ADJUSTABLE) 0 60 SEC. intervention delay has elapsed
6(/(&7/$1*8$*(The language set up in the factory is ITALIAN; the languages that can be selected are: ENGLISH, SPANISH, GERMAN and FRENCH
21 Move DIP-B 21 Move DIP-B
10 switch 10 to ON 10 switch 10 to OFF
6(/(=,21(/,1*8$ 6(/(=,21(/,1*8$
,7$/,$12 67$57 6723 (1*/,6+
Press and wait for
Press to select PROGRAMMED to be written
&/2&.352*5$00,1*
&/2&.$OORZVJHQHUDWRUVHWRSHUDWLRQRUVWRSSLQJWREHSURJUDPPHG
7,0(6(77,1*6ZLWFKLQJRIIWKHSRZHUVXSSO\WRWKHFRQWUROXQLWZLOO]HURWKHFORFN
SELECT THE OFF FUNCTION (see page 4) ([DPSOH
&/2&.
&/2&.
67$57 6723
Press to Increases Decreases
display
Press to set the clock
67$57,1*&216(172SHUDWLRQREWDLQHGDVGXULQJPDLQVIDLOXUH
21 ([DPSOH 21
Move DIP-B FROM 12:15 Move DIP-B
10 switch 10 to ON Intervention
10 switch 10 to OFF
delay
TO 15:20
FROM 12:15
7,0(567$57
*(1(5$725 Increases
67$57 6723
Decreases
TO 15:20
67236WRSVVWDUWLQJRUUXQQLQJRIJHQHUDWRUVHW
21 ([DPSOH 21
Move DIP-B FROM 23:00 Move DIP-B
10 switch 10 to ON Intervention
10 switch 10 to OFF
delay
TO 07:30
FROM 23:00
7,0(56723
*(1(5$725 Increases
67$57 6723
Decreases
TO 07:30
GB CAM-333/1 17
127,&(6
Used only to check and command a genset unit. It commands the mains and generator contactors to supply the user. It
has been designed to be installed only inside on an electrical panel as a single unit and so that it can be connected to
other components (contactors, fuses, thermo-magnetic switches, etc.) which the installer will have available to complete
the plant.
:DUQLQJ&RPSRQHQWVFDUU\LQJGDQJHURXVYROWDJHOHYHOV
Only assigned and suitably trained personnel are allowed access to the control unit. No maintenance
operations are permitted unless the plant is disconnected from the mains and the battery. As an
additional safety measure, the plant phases should be short-circuited and earthed.
Not withstanding the above, only assigned and trained personnel can perform the following
operations with the plant on:
- make a visual inspection of the control unit, the connections and their markings;
- measure the voltage and/or current values;
- programming of the functions.
These interventions, however, must be performed using equipment which ensures appropriate levels of electrical
protection.
:DUQLQJ
$GKHUHFORVHO\WRWKHIROORZLQJDGYLFH
- When making connections always follow the instructions and the Wiring Diagram on page 10-11.
- Any interventions on the unit must be performed with the motor stationary and terminal 50 of the starting motor
disconnected.
- Check that the consumption of the connected equipment are compatible with the described technical characteristics.
- Install in such a way that there is always adequate heat disposal.
- Always install under other equipment which produces or spreads heat.
- Handle and connect without mechanically stressing the electronic card.
- Make sure that no copper conductor cuttings or other waste material fall inside the control unit.
- Never disconnect the terminals of the battery with engine running.
- Never use a battery charger for the emergency start-up; the control panel could be damaged.
- In order to safeguard people and equipment, before connecting an external battery charger, disconnect the electrical
system terminals from the battery poles.
THIS CONTROL UNIT IS NOT SUITABLE FOR OPERATING IN THE FOLLOWING CONDITIONS:
- Where the environmental temperature is outside the limits indicated in the manual.
- Where the air pressure and temperature variations are so rapid as to produce exceptional condensation.
- Where there are high levels of pollution caused by dust, smoke, vapour, salts and corrosive or radioactive particles.
- Where there are high levels or heat from radiation caused by the sun, ovens or the like.
- Where attacks from mould or small animals are possible.
- Where there is the risk of fire or explosions.
- Where the control panel can receive strong vibrations or knocks.
- Where the control panel is protected by barriers or casing with protection level less than IP20.
ELECTROMAGNETIC COMPATIBILITY
This control unit functions correctly only if inserted in plants which conform with the CE marking standards; it meets the
exemption requirements of the standard EN50082-2 but it cannot be excluded that malfunctions could occur in extreme
cases due to particular situations.
The installer has the task of checking that the disturbance levels are within the requirements of the standards.
81/(66:(0$.($:5,77(1'(&/$5$7,2167$7,1*7+(&2175$5<7+,6&21752/81,7,6127
68,7$%/()2586($6$&5,7,&$/&20321(17,1(48,30(17253/$1765(63216,%/()25.((3,1*
3(562162527+(5/,9,1*%(,1*6$/,9(
18 GB CAM-333/1
ORDERING DATA
ACCESSORIES SUPPLIED
ACCESSORIES ON REQUEST
CONFORMITY DECLARATION
The company Elcos s.r.l. assumes full responsibility for declaring that the
control unit:
Ruggero Lombardo
GB CAM-333/1 19
READ BEFORE USING
www.elcos.it
Parma (Italy) CONTROL UNIT CAM-333
Before inserting the white connectors on the terminal boards, check that on the fastons
there are no voltages differing from the battery ones.
2))5(6(7
When the connections have been made the power unit is OFF,
to enable the other functions press the relevant key .
If CBV-015 does not connect: move DIP 7A to ON and connect a voltmetric relay
using input 30 (CALL)
EMERGENCY STOP
There are no jumpers JP1 (see page 8)
or else the emergency push-button is pressed
20 GB CAM-333/1