CHAPTER 3
PRELIMINARY DESIGN AND ANALYSIS
CHAPTER 3
PRELIMINARY ANALYSIS AND DESIGN CALCULATIONS
MEMBER LOAD CALCULATIONS
WORKING STRESS DESIGN
LOAD COMBINATION
DL+LL
BEAM
GRID 1&6
MEMBER Ll(m) Ls(m) FORMULA TRIBUTARY
LOAD
AB 6 6 16.14
BC 6 4 14.63
CD 6 6 16.14
DE 6 6 16.14
EF 6 6 16.14
GRID 2&3
MEMBER Ll(m) Ls(m) FORMULA TRIBUTARY
LOAD(kN/m)
AB 6 6 32.3
BC 6 4 21.52
CD 6 6 32.3
DE 6 6 32.3
EF 6 6 32.3
GRID 4&5
MEMBER Ll(m) Ls(m) FORMULA TRIBUTARY
LOAD(kN/m)
AB 6 6 16.14
BC 6 4 21.52
CD 6 6 32.3
DE 6 6 32.3
EF 6 6 32.3
GRID A&F
MEMBER Ll(m) Ls(m) FORMULA TRIBUTARY
LOAD(kN/m)
1-2 6 6 16.14
2-3 6 4 16.14
3-4 6 6 16.14
4-5 6 6 16.14
5-6 6 6 16.14
GRID B
MEMBER Ll(m) Ls(m) FORMULA TRIBUTARY
LOAD(kN/m)
1-2 6 4 29.89
2-3 6 4 29.89
3-4 6 4 29.89
4-5 6 4 13.75
5-6 6 4 29.89
GRID C
MEMBER Ll(m) Ls(m) FORMULA TRIBUTARY
LOAD(kN/m)
1-2 6 4 29.89
2-3 6 4 29.89
3-4 6 4 29.89
4-5 6 4 29,.89
5-6 6 4 29.89
GRID D&E
MEMBER Ll(m) Ls(m) FORMULA TRIBUTARY
LOAD(kN/m)
1-2 6 6 32.3
2-3 6 6 32.3
3-4 6 6 32.3
4-5 6 6 32.3
5-6 6 6 32.3
COLUMN
DL=6.17KPa
LL=1.9KPa
LOAD COMBINATION
DL+LL
FIFTH FLOOR
EXTERIOR COLUMNS
A1 = (8.07KPa)(9m2) + 1.5(.2m)2(23.6KN/m3) = 74.05KN C1
B1 = (8.07KPa)(15m2) + 1.5(.2m)2(23.6KN/m3) = 122.47KN C2
D1 = (8.07KPa)(18m2) + 1.5(.2m)2(23.6KN/m3) = 146.68KN C3
INTERIOR COLUMNS
B2 = (8.07KPa)(30m2) + 1.5(.2m)2(23.6KN/m3) = 243.52KN C4
D2 = (8.07KPa)(36m2) + 1.5(.2m)2(23.6KN/m3) =291.94KN C5
FOURTH FLOOR
EXTERIOR COLUMNS
A1 = (8.07KPa)(9m2) + 3(.25m)2(23.6KN/m3) + 74.05 = 151.11KN C6
B1 = (8.07KPa)(15m2) + 3(.25m)2(23.6KN/m3) +122.47 = 247.95KN C7
D1 = (8.07KPa)(18m2) + 3(.25m)2(23.6KN/m3) +146.68 = 296.37KN C8
INTERIOR COLUMNS
B2 = (8.07KPa)(30m2) + 3(.25m)2(23.6KN/m3) + 243.52= 490.05KN C9
D2 = (8.07KPa)(36m2) + 3(.25m)2(23.6KN/m3) + 291.94 = 586.89KN C10
THIRD FLOOR
EXTERIOR COLUMNS
A1 = (8.07KPa)(9m2) + 3(.35m)2(23.6KN/m3) + 151.11 = 232.41KN C11
B1 = (8.07KPa)(15m2) + 3(.35m)2(23.6KN/m3) +247.95 = 377.67KN C12
D1 = (8.07KPa)(18m2) + 3(.35m)2(23.6KN/m3) +296.37= 450.3 KN C13
INTERIOR COLUMNS
B2 = (8.07KPa)(30m2) + 3(.35m)2(23.6KN/m3) + 490.05= 740.82KN C14
D2 = (8.07KPa)(36m2) + 3(.35m)2(23.6KN/m3) + 586.89 = 886.08KN C15
SECOND FLOOR
EXTERIOR COLUMNS
A1 = (8.07KPa)(9m2) + 3(.35m)2(23.6KN/m3) + 232.41 = 313.71KN C16
B1 = (8.07KPa)(15m2) + 3(.35m)2(23.6KN/m3) +377.67 = 507.39KN C17
D1 = (8.07KPa)(18m2) + 3(.35m)2(23.6KN/m3) +450.3 = 604.23KN C18
INTERIOR COLUMNS
B2 = (8.07KPa)(30m2) + 3(.35m)2(23.6KN/m3) + 740.82 = 991.59KN C19
D2 = (8.07KPa)(36m2) + 3(.35m)2(23.6KN/m3) + 886.08 = 1185.27KN C20
GROUND FLOOR
EXTERIOR COLUMNS
A1 = (8.07KPa)(9m2) + 3(.4m)2(23.6KN/m3) + 313.71 = 397.67KN C21
B1 = (8.07KPa)(15m2) + 3(.4m)2(23.6KN/m3) +507.39 = 639.77KN C22
D1 = (8.07KPa)(18m2) + 3(.4m)2(23.6KN/m3) +604.23 = 760.82KN C23
A PROPOSED FIVE (5) STOREY RESIDENTIAL BUILDING WITH ROOF DECK
GOTONERO
GASPAR Page | 12
MOJICA
RODOLFO
CE 502/REINFORCED CONCRETE DESIGN
CHAPTER 3
PRELIMINARY DESIGN AND ANALYSIS
INTERIOR COLUMNS
B2 = (8.07KPa)(30m2) + 3(.4m)2(23.6KN/m3) + 991.59= 1245.02KN C24
D2 = (8.07KPa)(36m2) + 3(.4m)2(23.6KN/m3) + 1185.27 = 1487.12KN C25
SLAB
DL=6.17KPa
LL=1.9KPa
LOAD COMBINATION
DL+LL
BC 6 4 25.7
CD 6 6 20.89
DE 6 6 20.89
EF 6 6 20.89
GRID 2&3
MEMBER Ll(m) Ls(m) FORMULA TRIBUTARY
LOAD(kN/m)
AB 6 6 41.78
BC 6 4 27.85
CD 6 6 41.78
DE 6 6 41.78
EF 6 6 41.78
GRID 4&5
MEMBER Ll(m) Ls(m) FORMULA TRIBUTARY
LOAD(kN/m)
AB 6 6 20.89
BC 6 4 27.85
CD 6 6 41.78
DE 6 6 41.78
EF 6 6 41.78
GRID A&F
MEMBER Ll(m) Ls(m) FORMULA TRIBUTARY
LOAD(kN/m)
1-2 6 6 20.89
2-3 6 4 20.89
3-4 6 6 20.89
4-5 6 6 20.89
5-6 6 6 20.89
GRID B
MEMBER Ll(m) Ls(m) FORMULA TRIBUTARY
LOAD(kN/m)
1-2 6 4 38.68
2-3 6 4 38.68
3-4 6 4 38.68
4-5 6 4 17.79
5-6 6 4 38.68
GRID C
MEMBER Ll(m) Ls(m) FORMULA TRIBUTARY
LOAD(kN/m)
1-2 6 4 38.68
2-3 6 4 38.68
3-4 6 4 38.68
4-5 6 4 38.68
5-6 6 4 38.68
GRID D&E
MEMBER Ll(m) Ls(m) FORMULA TRIBUTARY
LOAD(kN/m)
1-2 6 6 41.78
2-3 6 6 41.78
3-4 6 6 41.78
4-5 6 6 41.78
5-6 6 6 41.78
COLUMN
DL=7.40KPa
LL=3.04KPa
LOAD COMBINATION
1.2DL+1.6LL
FIFTH FLOOR
EXTERIOR COLUMNS
A1 = (10.44KPa)(9m2) + 1.5(.2m)2(23.6KN/m3) = 95.38KN C1
B1 = (10.44KPa)(15m2) + 1.5(.2m)2(23.6KN/m3) = 158.02KN C2
D1 = (10.44KPa)(18m2) + 1.5(.2m)2(23.6KN/m3) = 189.34KN C3
INTERIOR COLUMNS
B2 = (10.44KPa)(30m2) + 1.5(.2m)2(23.6KN/m3) = 314.62KN C4
D2 = (10.44KPa)(36m2) + 1.5(.2m)2(23.6KN/m3) =377.26KN C5
FOURTH FLOOR
EXTERIOR COLUMNS
A1 = (10.44KPa)(9m2) + 3(.25m)2(23.6KN/m3) + 95.38 = 193.77KN C6
B1 = (10.44KPa)(15m2) + 3(.25m)2(23.6KN/m3) +158.02 = 319.05KN C7
D1 = (10.44KPa)(18m2) + 3(.25m)2(23.6KN/m3) +146.68 = 381.69KN C8
INTERIOR COLUMNS
B2 = (10.44KPa)(30m2) + 3(.25m)2(23.6KN/m3) + 314.62 = 632.25KN C9
D2 = (10.44KPa)(36m2) + 3(.25m)2(23.6KN/m3) + 377.26 = 757.53KN C10
THIRD FLOOR
EXTERIOR COLUMNS
A1 = (10.44KPa)(9m2) + 3(.35m)2(23.6KN/m3) + 193.77 = 390.36KN C11
B1 = (10.44KPa)(15m2) + 3(.35m)2(23.6KN/m3) + 319.05 = 484.32KN C12
D1 = (10.44KPa)(18m2) + 3(.35m)2(23.6KN/m3) + 381.69 = 578.28KN C13
INTERIOR COLUMNS
B2 = (10.44KPa)(30m2) + 3(.35m)2(23.6KN/m3) + 490.05= 811.92KN C14
D2 = (10.44KPa)(36m2) + 3(.35m)2(23.6KN/m3) + 586.89 = 971.40KN C15
SECOND FLOOR
EXTERIOR COLUMNS
A1 = (10.44KPa)(9m2) + 3(.35m)2(23.6KN/m3) + 390.36 = 492.99KN C16
B1 = (10.44KPa)(15m2) + 3(.35m)2(23.6KN/m3) + 484.32 = 649.59KN C17
D1 = (10.44KPa)(18m2) + 3(.35m)2(23.6KN/m3) + 578.28 = 774.87KN C18
INTERIOR COLUMNS
B2 = (10.44KPa)(30m2) + 3(.35m)2(23.6KN/m3) + 811.92 = 1133.79KN C19
D2 = (10.44KPa)(36m2) + 3(.35m)2(23.6KN/m3) + 971.04 = 1355.91KN C20
GROUND FLOOR
EXTERIOR COLUMNS
A PROPOSED FIVE (5) STOREY RESIDENTIAL BUILDING WITH ROOF DECK
GOTONERO
GASPAR Page | 18
MOJICA
RODOLFO
CE 502/REINFORCED CONCRETE DESIGN
CHAPTER 3
PRELIMINARY DESIGN AND ANALYSIS
SLAB
DL=7.40KPa
LL=3.04KPa
LOAD COMBINATION
1.2DL+1.6LL
GROUND FLOOR
SECOND FLOOR
THIRD FLOOR
FOURTH FLOOR
FIFTH FLOOR
BEAM CALCULATION
B-1
Given
STEP 1: MOMENT
Mu = 64.350 KN-m
b = 0.028914
A PROPOSED FIVE (5) STOREY RESIDENTIAL BUILDING WITH ROOF DECK
GOTONERO
GASPAR Page | 61
MOJICA
RODOLFO
CE 502/REINFORCED CONCRETE DESIGN
CHAPTER 3
PRELIMINARY DESIGN AND ANALYSIS
STEP 3: CHECK FOR RHO THEO IF LESS THAN RHO MAX OR GREATER THAN RHO MIN
S.R. Note: If D.R. where theo > max use the other template for doubly reinforced beam
64.3500= 0.90(4.5048)bd2
bd = 1.5872E+07
d = 316.6321794 mm
b = 158.3160897 mm
ACTUAL
d = 350 mm
b = 200 mm
As = theobd
As = 0.012173913043478329(158.3200)(316.6300)
As = 610.2644021 mm2
Bar Diameter = 25 mm Option, increase the diameter of bar if the no. of layer
exceed to (3) or decrease the cover
STEP 10: DETERMINE THE NO. OF BARS ALLOWED PER LAYER @ TENSION SIDE
Note: Minimum Spacing shall be equal to the ff. 25mm, bar , and at least 3/4 of aggregates size
Cover = 40 mm
Spacing= 40 mm
No. of Bars Allowed per Layer = b-2cc + 1
spacing
No. of Bars Allowed per Layer = 2.204923077 pcs say 2 pcs
No. of layer if no. of bars req'd < no. of bars allowed per layer = 1 layer say 13 (OK)
No. of Bars Allowed per Layer @ Tension Side > No. of Bars Req'd (OK)
If no. of bars allowed per layer is less than the no. of bars req'd. use the ff., but if the no.of layer exceed to
3, see option!
GROUND FLOOR
CULUMN 1
COLUMN 2
COLUMN 3
COLUMN 4
CULUMN 5
SECOND FLOOR
COLUMN 1
COLUMUN 2
COLUMN 3
CULUMN 4
COLUMN 5
A PROPOSED FIVE (5) STOREY RESIDENTIAL BUILDING WITH ROOF DECK
GOTONERO
GASPAR Page | 72
MOJICA
RODOLFO
CE 502/REINFORCED CONCRETE DESIGN
CHAPTER 3
PRELIMINARY DESIGN AND ANALYSIS
THIRD FLOOR
COLUMN 1
COLUMN 2
COLUMN 3
COLUMN 4
COLUMN 5
FOURTH FLOOR
COLUMN 1
COLUMN 2
A PROPOSED FIVE (5) STOREY RESIDENTIAL BUILDING WITH ROOF DECK
GOTONERO
GASPAR Page | 79
MOJICA
RODOLFO
CE 502/REINFORCED CONCRETE DESIGN
CHAPTER 3
PRELIMINARY DESIGN AND ANALYSIS
COLUMN 3
COLUMN 4
COLUMN 5
A PROPOSED FIVE (5) STOREY RESIDENTIAL BUILDING WITH ROOF DECK
GOTONERO
GASPAR Page | 82
MOJICA
RODOLFO
CE 502/REINFORCED CONCRETE DESIGN
CHAPTER 3
PRELIMINARY DESIGN AND ANALYSIS
FIFTHF LOOR
COLUMN 1
COLUMN 2
COLUMN 3
A PROPOSED FIVE (5) STOREY RESIDENTIAL BUILDING WITH ROOF DECK
GOTONERO
GASPAR Page | 85
MOJICA
RODOLFO
CE 502/REINFORCED CONCRETE DESIGN
CHAPTER 3
PRELIMINARY DESIGN AND ANALYSIS
COLUMN 4
A PROPOSED FIVE (5) STOREY RESIDENTIAL BUILDING WITH ROOF DECK
GOTONERO
GASPAR Page | 86
MOJICA
RODOLFO
CE 502/REINFORCED CONCRETE DESIGN
CHAPTER 3
PRELIMINARY DESIGN AND ANALYSIS
COLUMN 5
A PROPOSED FIVE (5) STOREY RESIDENTIAL BUILDING WITH ROOF DECK
GOTONERO
GASPAR Page | 87
MOJICA
RODOLFO
CE 502/REINFORCED CONCRETE DESIGN
CHAPTER 3
PRELIMINARY DESIGN AND ANALYSIS
GROUND FLOOR
COLUMN 1
COLUMN 2
COLUMN 3
COLUMN 4
A PROPOSED FIVE (5) STOREY RESIDENTIAL BUILDING WITH ROOF DECK
GOTONERO
GASPAR Page | 91
MOJICA
RODOLFO
CE 502/REINFORCED CONCRETE DESIGN
CHAPTER 3
PRELIMINARY DESIGN AND ANALYSIS
COLUMN 5
2ND FLOOR
A PROPOSED FIVE (5) STOREY RESIDENTIAL BUILDING WITH ROOF DECK
GOTONERO
GASPAR Page | 93
MOJICA
RODOLFO
CE 502/REINFORCED CONCRETE DESIGN
CHAPTER 3
PRELIMINARY DESIGN AND ANALYSIS
COLUMN 1
COLUMN 2
COLUMN 3
A PROPOSED FIVE (5) STOREY RESIDENTIAL BUILDING WITH ROOF DECK
GOTONERO
GASPAR Page | 95
MOJICA
RODOLFO
CE 502/REINFORCED CONCRETE DESIGN
CHAPTER 3
PRELIMINARY DESIGN AND ANALYSIS
COLUMN 4
A PROPOSED FIVE (5) STOREY RESIDENTIAL BUILDING WITH ROOF DECK
GOTONERO
GASPAR Page | 96
MOJICA
RODOLFO
CE 502/REINFORCED CONCRETE DESIGN
CHAPTER 3
PRELIMINARY DESIGN AND ANALYSIS
COLUMN 5
3RD COLUMN
COLUMN 1
A PROPOSED FIVE (5) STOREY RESIDENTIAL BUILDING WITH ROOF DECK
GOTONERO
GASPAR Page | 98
MOJICA
RODOLFO
CE 502/REINFORCED CONCRETE DESIGN
CHAPTER 3
PRELIMINARY DESIGN AND ANALYSIS
COLUMN 2
COLUMN 3
COLUMN 4
A PROPOSED FIVE (5) STOREY RESIDENTIAL BUILDING WITH ROOF DECK
GOTONERO
GASPAR Page | 101
MOJICA
RODOLFO
CE 502/REINFORCED CONCRETE DESIGN
CHAPTER 3
PRELIMINARY DESIGN AND ANALYSIS
COLUMN 5
4TH FLOOR
COLUMN 1
COLUMN 2
COLUMN 3
A PROPOSED FIVE (5) STOREY RESIDENTIAL BUILDING WITH ROOF DECK
GOTONERO
GASPAR Page | 105
MOJICA
RODOLFO
CE 502/REINFORCED CONCRETE DESIGN
CHAPTER 3
PRELIMINARY DESIGN AND ANALYSIS
COLUMN 4
COLUMN 5
A PROPOSED FIVE (5) STOREY RESIDENTIAL BUILDING WITH ROOF DECK
GOTONERO
GASPAR Page | 107
MOJICA
RODOLFO
CE 502/REINFORCED CONCRETE DESIGN
CHAPTER 3
PRELIMINARY DESIGN AND ANALYSIS
5TH FLOOR
COLUMN 1
COLUMN 2
A PROPOSED FIVE (5) STOREY RESIDENTIAL BUILDING WITH ROOF DECK
GOTONERO
GASPAR Page | 109
MOJICA
RODOLFO
CE 502/REINFORCED CONCRETE DESIGN
CHAPTER 3
PRELIMINARY DESIGN AND ANALYSIS
COLUMN 3
COLUMN 4
COLUMN 5