COMMENTS AND ITS ANSWERS

1. Provide attachment of wind tunnel test report highlighting the area of design
consideration, i.e. as you mentioned on steel mast.
Ans: Please refer to Wind Tunnel Test Report.
2. Provide attachment for the allowable deflection considered since it is not as
per the project specifications.
Ans: Refer page 10 from the report Clading_Statik final
3. Attach rivet technical data to compare the values computed.
Ans: Refer page 13 from the report Clading_Statik final
4. Check bending capacity of angle cleat.
Ans: Refer page 15 from the report Clading_Statik final
5. Check screw fixation of cleat to runner.
Ans: Refer page 17 from the report Clading_Statik final
6. Check bending capacity of runner.
Ans: Since runner is not in our Scope ,therefore this check is ignored.
7. Check bolt fixation of runner to steel subframe.
Ans: Refer page 16 from the report Clading_Statik final