You are on page 1of 6

Hourly Air System Design Day Loads for CONTROL ROOM

Project Name: 21014 BARKA MALL R4 08/01/2017


Prepared by: Amjaad 07:55AM

DESIGN MONTH: JANUARY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 30.5 547 4.9 5.4 0.0 0.0 0.0 0.0 0.0 0.0
0100 30.1 547 5.0 5.4 0.0 0.0 0.0 0.0 0.0 0.0
0200 29.7 547 4.9 5.4 0.0 0.0 0.0 0.0 0.0 0.0
0300 29.3 547 5.0 5.4 0.0 0.0 0.0 0.0 0.0 0.0
0400 29.1 547 4.9 5.4 0.0 0.0 0.0 0.0 0.0 0.0
0500 29.0 547 5.0 5.4 0.0 0.0 0.0 0.0 0.0 0.0
0600 29.2 547 5.0 5.4 0.0 0.0 0.0 0.0 0.0 0.0
0700 29.6 547 4.9 5.3 0.0 0.0 0.0 0.0 0.0 0.0
0800 30.3 547 4.8 5.2 0.0 0.0 0.0 0.0 0.0 0.0
0900 31.4 547 4.9 5.3 0.0 0.0 0.0 0.0 0.0 0.0
1000 32.6 547 5.0 5.4 0.0 0.0 0.0 0.0 0.0 0.0
1100 34.0 547 5.0 5.5 0.0 0.0 0.0 0.0 0.0 0.0
1200 35.4 547 5.0 5.5 0.0 0.0 0.0 0.0 0.0 0.0
1300 36.4 547 5.0 5.4 0.0 0.0 0.0 0.0 0.0 0.0
1400 37.0 547 5.2 5.6 0.0 0.0 0.0 0.0 0.0 0.0
1500 37.3 547 5.0 5.4 0.0 0.0 0.0 0.0 0.0 0.0
1600 37.0 547 5.2 5.6 0.0 0.0 0.0 0.0 0.0 0.0
1700 36.4 547 5.1 5.6 0.0 0.0 0.0 0.0 0.0 0.0
1800 35.5 547 5.2 5.6 0.0 0.0 0.0 0.0 0.0 0.0
1900 34.5 547 5.2 5.6 0.0 0.0 0.0 0.0 0.0 0.0
2000 33.4 547 5.0 5.5 0.0 0.0 0.0 0.0 0.0 0.0
2100 32.5 547 5.2 5.6 0.0 0.0 0.0 0.0 0.0 0.0
2200 31.6 547 5.0 5.4 0.0 0.0 0.0 0.0 0.0 0.0
2300 31.0 547 5.0 5.5 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: FEBRUARY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 31.6 547 5.2 5.6 0.0 0.0 0.0 0.0 0.0 0.0
0100 31.2 547 5.1 5.5 0.0 0.0 0.0 0.0 0.0 0.0
0200 30.8 547 5.1 5.5 0.0 0.0 0.0 0.0 0.0 0.0
0300 30.4 547 5.1 5.5 0.0 0.0 0.0 0.0 0.0 0.0
0400 30.2 547 5.1 5.5 0.0 0.0 0.0 0.0 0.0 0.0
0500 30.1 547 5.0 5.4 0.0 0.0 0.0 0.0 0.0 0.0
0600 30.3 547 5.0 5.4 0.0 0.0 0.0 0.0 0.0 0.0
0700 30.7 547 5.1 5.5 0.0 0.0 0.0 0.0 0.0 0.0
0800 31.4 547 5.1 5.5 0.0 0.0 0.0 0.0 0.0 0.0
0900 32.5 547 5.1 5.5 0.0 0.0 0.0 0.0 0.0 0.0
1000 33.7 547 5.0 5.4 0.0 0.0 0.0 0.0 0.0 0.0
1100 35.1 547 5.0 5.5 0.0 0.0 0.0 0.0 0.0 0.0
1200 36.5 547 5.2 5.6 0.0 0.0 0.0 0.0 0.0 0.0
1300 37.5 547 5.3 5.7 0.0 0.0 0.0 0.0 0.0 0.0
1400 38.1 547 5.2 5.7 0.0 0.0 0.0 0.0 0.0 0.0
1500 38.4 547 5.4 5.8 0.0 0.0 0.0 0.0 0.0 0.0
1600 38.1 547 5.3 5.7 0.0 0.0 0.0 0.0 0.0 0.0
1700 37.6 547 5.4 5.8 0.0 0.0 0.0 0.0 0.0 0.0
1800 36.6 547 5.4 5.9 0.0 0.0 0.0 0.0 0.0 0.0
1900 35.6 547 5.2 5.6 0.0 0.0 0.0 0.0 0.0 0.0
2000 34.5 547 5.3 5.8 0.0 0.0 0.0 0.0 0.0 0.0
2100 33.6 547 5.4 5.8 0.0 0.0 0.0 0.0 0.0 0.0
2200 32.7 547 5.1 5.6 0.0 0.0 0.0 0.0 0.0 0.0
2300 32.1 547 5.1 5.6 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.50 Page 1 of 6


Hourly Air System Design Day Loads for CONTROL ROOM
Project Name: 21014 BARKA MALL R4 08/01/2017
Prepared by: Amjaad 07:55AM

DESIGN MONTH: MARCH


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 33.9 547 5.4 5.8 0.0 0.0 0.0 0.0 0.0 0.0
0100 33.5 547 5.4 5.8 0.0 0.0 0.0 0.0 0.0 0.0
0200 33.1 547 5.3 5.7 0.0 0.0 0.0 0.0 0.0 0.0
0300 32.8 547 5.3 5.7 0.0 0.0 0.0 0.0 0.0 0.0
0400 32.5 547 5.3 5.7 0.0 0.0 0.0 0.0 0.0 0.0
0500 32.5 547 5.4 5.8 0.0 0.0 0.0 0.0 0.0 0.0
0600 32.6 547 5.1 5.5 0.0 0.0 0.0 0.0 0.0 0.0
0700 33.0 547 5.3 5.7 0.0 0.0 0.0 0.0 0.0 0.0
0800 33.8 547 5.2 5.6 0.0 0.0 0.0 0.0 0.0 0.0
0900 34.9 547 5.3 5.7 0.0 0.0 0.0 0.0 0.0 0.0
1000 36.1 547 5.3 5.7 0.0 0.0 0.0 0.0 0.0 0.0
1100 37.5 547 5.3 5.8 0.0 0.0 0.0 0.0 0.0 0.0
1200 38.8 547 5.3 5.8 0.0 0.0 0.0 0.0 0.0 0.0
1300 39.8 547 5.3 5.8 0.0 0.0 0.0 0.0 0.0 0.0
1400 40.5 547 5.4 5.8 0.0 0.0 0.0 0.0 0.0 0.0
1500 40.7 547 5.5 5.9 0.0 0.0 0.0 0.0 0.0 0.0
1600 40.5 547 5.6 6.0 0.0 0.0 0.0 0.0 0.0 0.0
1700 39.9 547 5.6 6.0 0.0 0.0 0.0 0.0 0.0 0.0
1800 39.0 547 5.5 5.9 0.0 0.0 0.0 0.0 0.0 0.0
1900 37.9 547 5.5 5.9 0.0 0.0 0.0 0.0 0.0 0.0
2000 36.8 547 5.6 6.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 35.9 547 5.4 5.8 0.0 0.0 0.0 0.0 0.0 0.0
2200 35.1 547 5.3 5.8 0.0 0.0 0.0 0.0 0.0 0.0
2300 34.4 547 5.5 5.9 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: APRIL


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 35.2 547 5.6 6.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 34.8 547 5.5 5.9 0.0 0.0 0.0 0.0 0.0 0.0
0200 34.4 547 5.6 6.0 0.0 0.0 0.0 0.0 0.0 0.0
0300 34.0 547 5.5 5.9 0.0 0.0 0.0 0.0 0.0 0.0
0400 33.8 547 5.3 5.8 0.0 0.0 0.0 0.0 0.0 0.0
0500 33.7 547 5.4 5.8 0.0 0.0 0.0 0.0 0.0 0.0
0600 33.9 547 5.4 5.8 0.0 0.0 0.0 0.0 0.0 0.0
0700 34.3 547 5.3 5.7 0.0 0.0 0.0 0.0 0.0 0.0
0800 35.0 547 5.3 5.7 0.0 0.0 0.0 0.0 0.0 0.0
0900 36.1 547 5.4 5.8 0.0 0.0 0.0 0.0 0.0 0.0
1000 37.3 547 5.4 5.8 0.0 0.0 0.0 0.0 0.0 0.0
1100 38.7 547 5.6 6.0 0.0 0.0 0.0 0.0 0.0 0.0
1200 40.1 547 5.5 6.0 0.0 0.0 0.0 0.0 0.0 0.0
1300 41.1 547 5.6 6.0 0.0 0.0 0.0 0.0 0.0 0.0
1400 41.7 547 5.7 6.1 0.0 0.0 0.0 0.0 0.0 0.0
1500 42.0 547 5.6 6.1 0.0 0.0 0.0 0.0 0.0 0.0
1600 41.7 547 5.6 6.0 0.0 0.0 0.0 0.0 0.0 0.0
1700 41.2 547 5.6 6.1 0.0 0.0 0.0 0.0 0.0 0.0
1800 40.2 547 5.7 6.1 0.0 0.0 0.0 0.0 0.0 0.0
1900 39.2 547 5.7 6.1 0.0 0.0 0.0 0.0 0.0 0.0
2000 38.1 547 5.6 6.1 0.0 0.0 0.0 0.0 0.0 0.0
2100 37.2 547 5.6 6.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 36.3 547 5.6 6.1 0.0 0.0 0.0 0.0 0.0 0.0
2300 35.7 547 5.6 6.0 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.50 Page 2 of 6


Hourly Air System Design Day Loads for CONTROL ROOM
Project Name: 21014 BARKA MALL R4 08/01/2017
Prepared by: Amjaad 07:55AM

DESIGN MONTH: MAY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 37.4 547 5.7 6.2 0.0 0.0 0.0 0.0 0.0 0.0
0100 37.0 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
0200 36.6 547 5.7 6.2 0.0 0.0 0.0 0.0 0.0 0.0
0300 36.3 547 5.7 6.1 0.0 0.0 0.0 0.0 0.0 0.0
0400 36.0 547 5.6 6.1 0.0 0.0 0.0 0.0 0.0 0.0
0500 35.9 547 5.6 6.1 0.0 0.0 0.0 0.0 0.0 0.0
0600 36.1 547 5.6 6.0 0.0 0.0 0.0 0.0 0.0 0.0
0700 36.5 547 5.6 6.0 0.0 0.0 0.0 0.0 0.0 0.0
0800 37.2 547 5.4 5.8 0.0 0.0 0.0 0.0 0.0 0.0
0900 38.3 547 5.6 6.0 0.0 0.0 0.0 0.0 0.0 0.0
1000 39.6 547 5.6 6.0 0.0 0.0 0.0 0.0 0.0 0.0
1100 41.0 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
1200 42.3 547 5.6 6.1 0.0 0.0 0.0 0.0 0.0 0.0
1300 43.3 547 5.7 6.2 0.0 0.0 0.0 0.0 0.0 0.0
1400 44.0 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
1500 44.2 547 5.9 6.4 0.0 0.0 0.0 0.0 0.0 0.0
1600 44.0 547 5.9 6.3 0.0 0.0 0.0 0.0 0.0 0.0
1700 43.4 547 6.0 6.4 0.0 0.0 0.0 0.0 0.0 0.0
1800 42.5 547 5.9 6.3 0.0 0.0 0.0 0.0 0.0 0.0
1900 41.4 547 5.9 6.3 0.0 0.0 0.0 0.0 0.0 0.0
2000 40.3 547 6.0 6.4 0.0 0.0 0.0 0.0 0.0 0.0
2100 39.4 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
2200 38.6 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
2300 37.9 547 5.9 6.3 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: JUNE


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 38.7 547 5.9 6.3 0.0 0.0 0.0 0.0 0.0 0.0
0100 38.2 547 5.9 6.3 0.0 0.0 0.0 0.0 0.0 0.0
0200 37.8 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
0300 37.5 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
0400 37.2 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
0500 37.2 547 5.7 6.2 0.0 0.0 0.0 0.0 0.0 0.0
0600 37.3 547 5.7 6.2 0.0 0.0 0.0 0.0 0.0 0.0
0700 37.7 547 5.7 6.1 0.0 0.0 0.0 0.0 0.0 0.0
0800 38.5 547 5.7 6.1 0.0 0.0 0.0 0.0 0.0 0.0
0900 39.6 547 5.7 6.1 0.0 0.0 0.0 0.0 0.0 0.0
1000 40.8 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
1100 42.2 547 5.7 6.2 0.0 0.0 0.0 0.0 0.0 0.0
1200 43.5 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
1300 44.5 547 6.0 6.4 0.0 0.0 0.0 0.0 0.0 0.0
1400 45.2 547 5.9 6.3 0.0 0.0 0.0 0.0 0.0 0.0
1500 45.4 547 6.0 6.4 0.0 0.0 0.0 0.0 0.0 0.0
1600 45.2 547 6.0 6.4 0.0 0.0 0.0 0.0 0.0 0.0
1700 44.6 547 6.1 6.5 0.0 0.0 0.0 0.0 0.0 0.0
1800 43.7 547 6.0 6.4 0.0 0.0 0.0 0.0 0.0 0.0
1900 42.6 547 6.0 6.5 0.0 0.0 0.0 0.0 0.0 0.0
2000 41.6 547 6.1 6.5 0.0 0.0 0.0 0.0 0.0 0.0
2100 40.6 547 6.0 6.4 0.0 0.0 0.0 0.0 0.0 0.0
2200 39.8 547 5.9 6.4 0.0 0.0 0.0 0.0 0.0 0.0
2300 39.2 547 6.0 6.4 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.50 Page 3 of 6


Hourly Air System Design Day Loads for CONTROL ROOM
Project Name: 21014 BARKA MALL R4 08/01/2017
Prepared by: Amjaad 07:55AM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 39.2 547 6.0 6.4 0.0 0.0 0.0 0.0 0.0 0.0
0100 38.8 547 5.8 6.3 0.0 0.0 0.0 0.0 0.0 0.0
0200 38.4 547 5.9 6.3 0.0 0.0 0.0 0.0 0.0 0.0
0300 38.1 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
0400 37.8 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
0500 37.7 547 5.7 6.1 0.0 0.0 0.0 0.0 0.0 0.0
0600 37.9 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
0700 38.3 547 5.7 6.1 0.0 0.0 0.0 0.0 0.0 0.0
0800 39.0 547 5.7 6.1 0.0 0.0 0.0 0.0 0.0 0.0
0900 40.1 547 5.7 6.1 0.0 0.0 0.0 0.0 0.0 0.0
1000 41.4 547 5.7 6.2 0.0 0.0 0.0 0.0 0.0 0.0
1100 42.8 547 5.9 6.3 0.0 0.0 0.0 0.0 0.0 0.0
1200 44.1 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
1300 45.1 547 5.9 6.3 0.0 0.0 0.0 0.0 0.0 0.0
1400 45.8 547 6.1 6.5 0.0 0.0 0.0 0.0 0.0 0.0
1500 46.0 547 6.0 6.4 0.0 0.0 0.0 0.0 0.0 0.0
1600 45.8 547 6.0 6.4 0.0 0.0 0.0 0.0 0.0 0.0
1700 45.2 547 6.1 6.5 0.0 0.0 0.0 0.0 0.0 0.0
1800 44.3 547 6.1 6.6 0.0 0.0 0.0 0.0 0.0 0.0
1900 43.2 547 6.0 6.4 0.0 0.0 0.0 0.0 0.0 0.0
2000 42.1 547 6.0 6.4 0.0 0.0 0.0 0.0 0.0 0.0
2100 41.2 547 6.1 6.5 0.0 0.0 0.0 0.0 0.0 0.0
2200 40.4 547 5.9 6.4 0.0 0.0 0.0 0.0 0.0 0.0
2300 39.7 547 5.9 6.3 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: AUGUST


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 39.2 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
0100 38.8 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
0200 38.4 547 5.9 6.3 0.0 0.0 0.0 0.0 0.0 0.0
0300 38.1 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
0400 37.8 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
0500 37.7 547 5.8 6.3 0.0 0.0 0.0 0.0 0.0 0.0
0600 37.9 547 5.7 6.1 0.0 0.0 0.0 0.0 0.0 0.0
0700 38.3 547 5.7 6.1 0.0 0.0 0.0 0.0 0.0 0.0
0800 39.0 547 5.7 6.1 0.0 0.0 0.0 0.0 0.0 0.0
0900 40.1 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
1000 41.4 547 5.7 6.1 0.0 0.0 0.0 0.0 0.0 0.0
1100 42.8 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
1200 44.1 547 5.7 6.1 0.0 0.0 0.0 0.0 0.0 0.0
1300 45.1 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
1400 45.8 547 5.9 6.3 0.0 0.0 0.0 0.0 0.0 0.0
1500 46.0 547 6.0 6.4 0.0 0.0 0.0 0.0 0.0 0.0
1600 45.8 547 5.9 6.4 0.0 0.0 0.0 0.0 0.0 0.0
1700 45.2 547 6.0 6.4 0.0 0.0 0.0 0.0 0.0 0.0
1800 44.3 547 6.1 6.5 0.0 0.0 0.0 0.0 0.0 0.0
1900 43.2 547 5.9 6.4 0.0 0.0 0.0 0.0 0.0 0.0
2000 42.1 547 5.9 6.4 0.0 0.0 0.0 0.0 0.0 0.0
2100 41.2 547 6.0 6.4 0.0 0.0 0.0 0.0 0.0 0.0
2200 40.4 547 5.8 6.3 0.0 0.0 0.0 0.0 0.0 0.0
2300 39.7 547 5.8 6.3 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.50 Page 4 of 6


Hourly Air System Design Day Loads for CONTROL ROOM
Project Name: 21014 BARKA MALL R4 08/01/2017
Prepared by: Amjaad 07:55AM

DESIGN MONTH: SEPTEMBER


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 38.1 547 5.7 6.2 0.0 0.0 0.0 0.0 0.0 0.0
0100 37.7 547 5.7 6.2 0.0 0.0 0.0 0.0 0.0 0.0
0200 37.3 547 5.7 6.1 0.0 0.0 0.0 0.0 0.0 0.0
0300 36.9 547 5.7 6.1 0.0 0.0 0.0 0.0 0.0 0.0
0400 36.7 547 5.6 6.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 36.6 547 5.6 6.0 0.0 0.0 0.0 0.0 0.0 0.0
0600 36.8 547 5.6 6.0 0.0 0.0 0.0 0.0 0.0 0.0
0700 37.2 547 5.5 6.0 0.0 0.0 0.0 0.0 0.0 0.0
0800 37.9 547 5.6 6.0 0.0 0.0 0.0 0.0 0.0 0.0
0900 39.0 547 5.6 6.0 0.0 0.0 0.0 0.0 0.0 0.0
1000 40.3 547 5.6 6.0 0.0 0.0 0.0 0.0 0.0 0.0
1100 41.7 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
1200 43.0 547 5.7 6.1 0.0 0.0 0.0 0.0 0.0 0.0
1300 44.0 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
1400 44.6 547 5.8 6.3 0.0 0.0 0.0 0.0 0.0 0.0
1500 44.9 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
1600 44.6 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
1700 44.1 547 5.9 6.3 0.0 0.0 0.0 0.0 0.0 0.0
1800 43.2 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
1900 42.1 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
2000 41.0 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0
2100 40.1 547 5.9 6.3 0.0 0.0 0.0 0.0 0.0 0.0
2200 39.3 547 5.7 6.1 0.0 0.0 0.0 0.0 0.0 0.0
2300 38.6 547 5.8 6.2 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: OCTOBER


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 36.3 547 5.7 6.1 0.0 0.0 0.0 0.0 0.0 0.0
0100 35.9 547 5.6 6.0 0.0 0.0 0.0 0.0 0.0 0.0
0200 35.5 547 5.4 5.8 0.0 0.0 0.0 0.0 0.0 0.0
0300 35.1 547 5.3 5.8 0.0 0.0 0.0 0.0 0.0 0.0
0400 34.9 547 5.4 5.8 0.0 0.0 0.0 0.0 0.0 0.0
0500 34.8 547 5.4 5.9 0.0 0.0 0.0 0.0 0.0 0.0
0600 35.0 547 5.4 5.9 0.0 0.0 0.0 0.0 0.0 0.0
0700 35.4 547 5.4 5.8 0.0 0.0 0.0 0.0 0.0 0.0
0800 36.1 547 5.2 5.7 0.0 0.0 0.0 0.0 0.0 0.0
0900 37.2 547 5.4 5.9 0.0 0.0 0.0 0.0 0.0 0.0
1000 38.5 547 5.5 5.9 0.0 0.0 0.0 0.0 0.0 0.0
1100 39.9 547 5.4 5.8 0.0 0.0 0.0 0.0 0.0 0.0
1200 41.2 547 5.6 6.0 0.0 0.0 0.0 0.0 0.0 0.0
1300 42.2 547 5.6 6.0 0.0 0.0 0.0 0.0 0.0 0.0
1400 42.8 547 5.6 6.1 0.0 0.0 0.0 0.0 0.0 0.0
1500 43.1 547 5.7 6.1 0.0 0.0 0.0 0.0 0.0 0.0
1600 42.8 547 5.6 6.1 0.0 0.0 0.0 0.0 0.0 0.0
1700 42.3 547 5.7 6.2 0.0 0.0 0.0 0.0 0.0 0.0
1800 41.4 547 5.7 6.1 0.0 0.0 0.0 0.0 0.0 0.0
1900 40.3 547 5.7 6.1 0.0 0.0 0.0 0.0 0.0 0.0
2000 39.2 547 5.6 6.1 0.0 0.0 0.0 0.0 0.0 0.0
2100 38.3 547 5.5 6.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 37.5 547 5.5 6.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 36.8 547 5.5 6.0 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.50 Page 5 of 6


Hourly Air System Design Day Loads for CONTROL ROOM
Project Name: 21014 BARKA MALL R4 08/01/2017
Prepared by: Amjaad 07:55AM

DESIGN MONTH: NOVEMBER


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 33.4 547 5.2 5.6 0.0 0.0 0.0 0.0 0.0 0.0
0100 33.0 547 5.4 5.8 0.0 0.0 0.0 0.0 0.0 0.0
0200 32.6 547 5.2 5.6 0.0 0.0 0.0 0.0 0.0 0.0
0300 32.2 547 5.2 5.7 0.0 0.0 0.0 0.0 0.0 0.0
0400 32.0 547 5.0 5.5 0.0 0.0 0.0 0.0 0.0 0.0
0500 31.9 547 5.3 5.7 0.0 0.0 0.0 0.0 0.0 0.0
0600 32.1 547 5.1 5.5 0.0 0.0 0.0 0.0 0.0 0.0
0700 32.5 547 5.2 5.6 0.0 0.0 0.0 0.0 0.0 0.0
0800 33.2 547 5.2 5.6 0.0 0.0 0.0 0.0 0.0 0.0
0900 34.3 547 5.2 5.6 0.0 0.0 0.0 0.0 0.0 0.0
1000 35.5 547 5.3 5.7 0.0 0.0 0.0 0.0 0.0 0.0
1100 36.9 547 5.3 5.7 0.0 0.0 0.0 0.0 0.0 0.0
1200 38.3 547 5.2 5.6 0.0 0.0 0.0 0.0 0.0 0.0
1300 39.3 547 5.3 5.8 0.0 0.0 0.0 0.0 0.0 0.0
1400 39.9 547 5.3 5.8 0.0 0.0 0.0 0.0 0.0 0.0
1500 40.2 547 5.5 5.9 0.0 0.0 0.0 0.0 0.0 0.0
1600 39.9 547 5.5 5.9 0.0 0.0 0.0 0.0 0.0 0.0
1700 39.4 547 5.4 5.8 0.0 0.0 0.0 0.0 0.0 0.0
1800 38.4 547 5.5 5.9 0.0 0.0 0.0 0.0 0.0 0.0
1900 37.4 547 5.4 5.8 0.0 0.0 0.0 0.0 0.0 0.0
2000 36.3 547 5.5 5.9 0.0 0.0 0.0 0.0 0.0 0.0
2100 35.4 547 5.2 5.6 0.0 0.0 0.0 0.0 0.0 0.0
2200 34.5 547 5.4 5.9 0.0 0.0 0.0 0.0 0.0 0.0
2300 33.9 547 5.2 5.6 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: DECEMBER


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 31.0 547 5.1 5.6 0.0 0.0 0.0 0.0 0.0 0.0
0100 30.6 547 5.1 5.5 0.0 0.0 0.0 0.0 0.0 0.0
0200 30.2 547 4.9 5.3 0.0 0.0 0.0 0.0 0.0 0.0
0300 29.9 547 5.0 5.4 0.0 0.0 0.0 0.0 0.0 0.0
0400 29.6 547 5.1 5.5 0.0 0.0 0.0 0.0 0.0 0.0
0500 29.5 547 4.9 5.3 0.0 0.0 0.0 0.0 0.0 0.0
0600 29.7 547 4.9 5.3 0.0 0.0 0.0 0.0 0.0 0.0
0700 30.1 547 5.0 5.4 0.0 0.0 0.0 0.0 0.0 0.0
0800 30.9 547 4.8 5.2 0.0 0.0 0.0 0.0 0.0 0.0
0900 31.9 547 5.0 5.4 0.0 0.0 0.0 0.0 0.0 0.0
1000 33.2 547 4.9 5.3 0.0 0.0 0.0 0.0 0.0 0.0
1100 34.6 547 5.0 5.4 0.0 0.0 0.0 0.0 0.0 0.0
1200 35.9 547 5.1 5.5 0.0 0.0 0.0 0.0 0.0 0.0
1300 36.9 547 5.2 5.6 0.0 0.0 0.0 0.0 0.0 0.0
1400 37.6 547 5.1 5.6 0.0 0.0 0.0 0.0 0.0 0.0
1500 37.8 547 5.2 5.6 0.0 0.0 0.0 0.0 0.0 0.0
1600 37.6 547 5.1 5.5 0.0 0.0 0.0 0.0 0.0 0.0
1700 37.0 547 5.3 5.7 0.0 0.0 0.0 0.0 0.0 0.0
1800 36.1 547 5.3 5.8 0.0 0.0 0.0 0.0 0.0 0.0
1900 35.0 547 5.1 5.5 0.0 0.0 0.0 0.0 0.0 0.0
2000 33.9 547 5.1 5.5 0.0 0.0 0.0 0.0 0.0 0.0
2100 33.0 547 5.1 5.5 0.0 0.0 0.0 0.0 0.0 0.0
2200 32.2 547 5.2 5.6 0.0 0.0 0.0 0.0 0.0 0.0
2300 31.5 547 5.0 5.4 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.50 Page 6 of 6