Professional Documents
Culture Documents
Markings on Circuit
Breakers Mean?
by Ed Larsen, P. E.
Markings Visible without Removing
H
ave you ever been confused about what the Trims or Covers
markings on circuit breakers mean? Under- UL 489 requires that some markings be visible without
standing the markings on electrical equip- removing trims or covers. This location is typically re-
ment is a fundamental need to ensure a safe and re- ferred to as the handle escutcheon (see photo 1).
liable electrical installation. Circuit breaker marking
requirements are established by the requirements Markings Visible with Trims or Covers Removed
found in the NEC and the UL 489 product standard. UL 489 requires other markings be visible on an installed
This article will discuss the most common markings circuit breaker with trims or covers removed. This lo-
and where they can be found. cation is typically referred to as the face of the circuit
The UL 489 product standard for Molded Case Cir- breaker (see photos 24).
cuit Breakers specifies the information to be marked Other markings which should be visible with trims or
on circuit breakers and where it is to be located, so lets covers removed are:
discuss what information needs to be marked on the Independent trip Multi-pole circuit breakers are
circuit breaker and the location where you will find constructed with either a common trip, where all poles
those markings. Keep in mind the UL standard speci- are mechanically tripped when one of the poles trips, or
fies minimum requirements. Circuit breaker manufac- an independent trip construction where only the pole
turers may provide additional information or provide that is involved with the overcurrent condition trips. If
information in a more convenient location. a 2-pole circuit breaker does not have an internal com-
3 1 2
Photo 1. Markings Visible with Trims or Covers in Place
1. ON and OFF The ON and OFF (closed and open) positions of the handle must be marked (NEC 240.81). These positions may also be marked with the internationally recog-
nized I and O symbols, although this is not a UL requirement. If these markings are not visible when a motor operator is installed over the circuit breaker markings, then
they must appear on the motor operator. Motor operators may be found in applications where remote or automatic operation of a circuit breaker is required.
2. Ampere rating (if 100 A or less) The ampere rating may be located on the handle escutcheon or on the handle itself (NEC 240.83(B)). Circuit breakers that are rated more
than 100 A may have their ampere rating marked in a position that is not visible with trims or covers in place.
2
1
3
mon trip feature, then it must be marked Independent Markings Found in Other Locations
Trip or No Common Trip. NEC 240.20(B) is the The markings we will discuss below may appear in any
foundational requirement for a common trip function location except the back of the circuit breaker. These
in a circuit breaker; however, it also goes on to explain markings include:
where independent trip is permitted.
40C This marking indicates the maximum ambient
For Replacement Use Only not-CTL The Class
temperature in which the circuit breaker can be applied at
CTL (circuit limiting) panelboard has only been in
its marked ampere rating without rerating the ampacity
existence for about 25 years, even though the lighting
of the circuit breaker. This marking is required for ther-
and appliance branch circuit panelboard has been in
mal-magnetic circuit breakers and is optional for elec-
the NEC for decades. CTL panelboards have a rejec-
tronic trip circuit breakers unless they are only suitable
tion means designed to reject more than the appro-
for a 25C ambient, in which case they must be marked
priate number of circuit breakers that can be installed
25C. When the ambient temperature rises above 40C,
in the panel. The marking For replacement Use Only
the designer may need to consult the manufacturer to ob-
Not CTL Assemblies means that the circuit break-
tain rerating information (see item 4 in photo 3).
er does not have CTL rejection provisions and is in-
tended for replacement in older equipment pre-dating Class CTL Circuit breakers marked Class CTL have
the CTL requirements for circuit breakers and panel- a rejection means designed into the circuit breaker.
boards. Circuit breakers with this designation should Class CTL panelboards or assemblies, in conjunction
not be installed in a panelboard marked Class CTL with Class CTL circuit breakers, prevent more circuit
Panelboard since that would be a violation of the list- breaker poles from being installed than the number for
ing of the assembly [ NEC 110.3(B)]. which the equipment is rated.
more than 125 A are rated for use with 75C wire; the mark-
ing is optional. It is always permissible to use wire with a
higher temperature rating, but it must be sized in accordance
with the temperature marking on the circuit breaker and NEC
Table 310.16. If the width of the circuit breaker is 1- inches
per pole or less, then this marking may be in any location
except on the back (NEC 110.14(C)1).
Arc-Fault Protection
1 Circuit breakers may also include arc-fault protection
(AFCI) that, like GFCIs, also has a number of unique
marking and instruction requirements.