You are on page 1of 6

Hourly Air System Design Day Loads for CORRIDOR 4a

Project Name: 21014 BARKA MALL R4 08/01/2017


Prepared by: Amjaad 07:56AM

DESIGN MONTH: JANUARY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 30.5 2359 27.8 35.1 0.0 0.0 0.0 0.0 0.0 0.0
0100 30.1 2359 26.3 33.6 0.0 0.0 0.0 0.0 0.0 0.0
0200 29.7 2359 26.3 33.6 0.0 0.0 0.0 0.0 0.0 0.0
0300 29.3 2359 26.8 34.1 0.0 0.0 0.0 0.0 0.0 0.0
0400 29.1 2359 26.6 33.9 0.0 0.0 0.0 0.0 0.0 0.0
0500 29.0 2359 25.8 33.1 0.0 0.0 0.0 0.0 0.0 0.0
0600 29.2 2359 24.7 32.0 0.0 0.0 0.0 0.0 0.0 0.0
0700 29.6 2359 24.8 32.1 0.0 0.0 0.0 0.0 0.0 0.0
0800 30.3 2359 25.5 32.8 0.0 0.0 0.0 0.0 0.0 0.0
0900 31.4 2359 25.0 32.3 0.0 0.0 0.0 0.0 0.0 0.0
1000 32.6 2359 24.7 32.0 0.0 0.0 0.0 0.0 0.0 0.0
1100 34.0 2359 26.1 33.4 0.0 0.0 0.0 0.0 0.0 0.0
1200 35.4 2359 26.8 34.1 0.0 0.0 0.0 0.0 0.0 0.0
1300 36.4 2359 27.1 34.4 0.0 0.0 0.0 0.0 0.0 0.0
1400 37.0 2359 28.9 36.2 0.0 0.0 0.0 0.0 0.0 0.0
1500 37.3 2359 29.5 36.8 0.0 0.0 0.0 0.0 0.0 0.0
1600 37.0 2359 30.3 37.6 0.0 0.0 0.0 0.0 0.0 0.0
1700 36.4 2359 30.3 37.6 0.0 0.0 0.0 0.0 0.0 0.0
1800 35.5 2359 30.2 37.5 0.0 0.0 0.0 0.0 0.0 0.0
1900 34.5 2359 29.5 36.8 0.0 0.0 0.0 0.0 0.0 0.0
2000 33.4 2359 28.7 36.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 32.5 2359 29.3 36.6 0.0 0.0 0.0 0.0 0.0 0.0
2200 31.6 2359 28.6 35.9 0.0 0.0 0.0 0.0 0.0 0.0
2300 31.0 2359 27.4 34.7 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: FEBRUARY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 31.6 2359 29.3 36.6 0.0 0.0 0.0 0.0 0.0 0.0
0100 31.2 2359 28.6 35.9 0.0 0.0 0.0 0.0 0.0 0.0
0200 30.8 2359 27.1 34.4 0.0 0.0 0.0 0.0 0.0 0.0
0300 30.4 2359 27.1 34.4 0.0 0.0 0.0 0.0 0.0 0.0
0400 30.2 2359 27.6 34.9 0.0 0.0 0.0 0.0 0.0 0.0
0500 30.1 2359 27.0 34.3 0.0 0.0 0.0 0.0 0.0 0.0
0600 30.3 2359 26.0 33.3 0.0 0.0 0.0 0.0 0.0 0.0
0700 30.7 2359 26.5 33.8 0.0 0.0 0.0 0.0 0.0 0.0
0800 31.4 2359 25.4 32.7 0.0 0.0 0.0 0.0 0.0 0.0
0900 32.5 2359 26.6 33.9 0.0 0.0 0.0 0.0 0.0 0.0
1000 33.7 2359 26.7 34.0 0.0 0.0 0.0 0.0 0.0 0.0
1100 35.1 2359 27.4 34.7 0.0 0.0 0.0 0.0 0.0 0.0
1200 36.5 2359 28.1 35.4 0.0 0.0 0.0 0.0 0.0 0.0
1300 37.5 2359 28.6 35.9 0.0 0.0 0.0 0.0 0.0 0.0
1400 38.1 2359 29.2 36.5 0.0 0.0 0.0 0.0 0.0 0.0
1500 38.4 2359 31.1 38.4 0.0 0.0 0.0 0.0 0.0 0.0
1600 38.1 2359 31.2 38.5 0.0 0.0 0.0 0.0 0.0 0.0
1700 37.6 2359 32.1 39.4 0.0 0.0 0.0 0.0 0.0 0.0
1800 36.6 2359 31.8 39.1 0.0 0.0 0.0 0.0 0.0 0.0
1900 35.6 2359 31.5 38.8 0.0 0.0 0.0 0.0 0.0 0.0
2000 34.5 2359 30.7 38.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 33.6 2359 30.2 37.5 0.0 0.0 0.0 0.0 0.0 0.0
2200 32.7 2359 29.3 36.6 0.0 0.0 0.0 0.0 0.0 0.0
2300 32.1 2359 29.7 37.0 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.50 Page 1 of 6


Hourly Air System Design Day Loads for CORRIDOR 4a
Project Name: 21014 BARKA MALL R4 08/01/2017
Prepared by: Amjaad 07:56AM

DESIGN MONTH: MARCH


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 33.9 2359 30.3 37.6 0.0 0.0 0.0 0.0 0.0 0.0
0100 33.5 2359 29.8 37.1 0.0 0.0 0.0 0.0 0.0 0.0
0200 33.1 2359 29.3 36.6 0.0 0.0 0.0 0.0 0.0 0.0
0300 32.8 2359 28.8 36.1 0.0 0.0 0.0 0.0 0.0 0.0
0400 32.5 2359 27.9 35.2 0.0 0.0 0.0 0.0 0.0 0.0
0500 32.5 2359 28.2 35.6 0.0 0.0 0.0 0.0 0.0 0.0
0600 32.6 2359 28.2 35.5 0.0 0.0 0.0 0.0 0.0 0.0
0700 33.0 2359 27.4 34.7 0.0 0.0 0.0 0.0 0.0 0.0
0800 33.8 2359 26.8 34.1 0.0 0.0 0.0 0.0 0.0 0.0
0900 34.9 2359 28.1 35.4 0.0 0.0 0.0 0.0 0.0 0.0
1000 36.1 2359 27.4 34.7 0.0 0.0 0.0 0.0 0.0 0.0
1100 37.5 2359 29.3 36.6 0.0 0.0 0.0 0.0 0.0 0.0
1200 38.8 2359 29.5 36.8 0.0 0.0 0.0 0.0 0.0 0.0
1300 39.8 2359 30.6 37.9 0.0 0.0 0.0 0.0 0.0 0.0
1400 40.5 2359 32.2 39.5 0.0 0.0 0.0 0.0 0.0 0.0
1500 40.7 2359 31.9 39.2 0.0 0.0 0.0 0.0 0.0 0.0
1600 40.5 2359 33.8 41.1 0.0 0.0 0.0 0.0 0.0 0.0
1700 39.9 2359 33.0 40.3 0.0 0.0 0.0 0.0 0.0 0.0
1800 39.0 2359 34.0 41.3 0.0 0.0 0.0 0.0 0.0 0.0
1900 37.9 2359 33.2 40.5 0.0 0.0 0.0 0.0 0.0 0.0
2000 36.8 2359 32.7 40.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 35.9 2359 31.6 38.9 0.0 0.0 0.0 0.0 0.0 0.0
2200 35.1 2359 31.7 39.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 34.4 2359 31.3 38.6 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: APRIL


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 35.2 2359 30.8 38.1 0.0 0.0 0.0 0.0 0.0 0.0
0100 34.8 2359 31.3 38.6 0.0 0.0 0.0 0.0 0.0 0.0
0200 34.4 2359 29.7 37.0 0.0 0.0 0.0 0.0 0.0 0.0
0300 34.0 2359 30.2 37.5 0.0 0.0 0.0 0.0 0.0 0.0
0400 33.8 2359 29.5 36.8 0.0 0.0 0.0 0.0 0.0 0.0
0500 33.7 2359 28.2 35.5 0.0 0.0 0.0 0.0 0.0 0.0
0600 33.9 2359 28.6 35.9 0.0 0.0 0.0 0.0 0.0 0.0
0700 34.3 2359 28.7 36.0 0.0 0.0 0.0 0.0 0.0 0.0
0800 35.0 2359 28.5 35.8 0.0 0.0 0.0 0.0 0.0 0.0
0900 36.1 2359 28.9 36.3 0.0 0.0 0.0 0.0 0.0 0.0
1000 37.3 2359 28.8 36.1 0.0 0.0 0.0 0.0 0.0 0.0
1100 38.7 2359 29.1 36.4 0.0 0.0 0.0 0.0 0.0 0.0
1200 40.1 2359 30.8 38.1 0.0 0.0 0.0 0.0 0.0 0.0
1300 41.1 2359 31.3 38.6 0.0 0.0 0.0 0.0 0.0 0.0
1400 41.7 2359 33.2 40.5 0.0 0.0 0.0 0.0 0.0 0.0
1500 42.0 2359 33.6 40.9 0.0 0.0 0.0 0.0 0.0 0.0
1600 41.7 2359 34.6 41.9 0.0 0.0 0.0 0.0 0.0 0.0
1700 41.2 2359 34.6 41.9 0.0 0.0 0.0 0.0 0.0 0.0
1800 40.2 2359 35.3 42.6 0.0 0.0 0.0 0.0 0.0 0.0
1900 39.2 2359 34.1 41.4 0.0 0.0 0.0 0.0 0.0 0.0
2000 38.1 2359 32.9 40.2 0.0 0.0 0.0 0.0 0.0 0.0
2100 37.2 2359 32.7 40.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 36.3 2359 33.1 40.4 0.0 0.0 0.0 0.0 0.0 0.0
2300 35.7 2359 31.9 39.2 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.50 Page 2 of 6


Hourly Air System Design Day Loads for CORRIDOR 4a
Project Name: 21014 BARKA MALL R4 08/01/2017
Prepared by: Amjaad 07:56AM

DESIGN MONTH: MAY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 37.4 2359 32.3 39.6 0.0 0.0 0.0 0.0 0.0 0.0
0100 37.0 2359 31.8 39.1 0.0 0.0 0.0 0.0 0.0 0.0
0200 36.6 2359 31.2 38.5 0.0 0.0 0.0 0.0 0.0 0.0
0300 36.3 2359 30.7 38.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 36.0 2359 30.3 37.6 0.0 0.0 0.0 0.0 0.0 0.0
0500 35.9 2359 29.9 37.2 0.0 0.0 0.0 0.0 0.0 0.0
0600 36.1 2359 29.1 36.4 0.0 0.0 0.0 0.0 0.0 0.0
0700 36.5 2359 30.0 37.3 0.0 0.0 0.0 0.0 0.0 0.0
0800 37.2 2359 29.3 36.6 0.0 0.0 0.0 0.0 0.0 0.0
0900 38.3 2359 29.6 37.0 0.0 0.0 0.0 0.0 0.0 0.0
1000 39.6 2359 30.6 37.9 0.0 0.0 0.0 0.0 0.0 0.0
1100 41.0 2359 31.1 38.4 0.0 0.0 0.0 0.0 0.0 0.0
1200 42.3 2359 32.0 39.3 0.0 0.0 0.0 0.0 0.0 0.0
1300 43.3 2359 33.0 40.3 0.0 0.0 0.0 0.0 0.0 0.0
1400 44.0 2359 33.5 40.8 0.0 0.0 0.0 0.0 0.0 0.0
1500 44.2 2359 35.2 42.5 0.0 0.0 0.0 0.0 0.0 0.0
1600 44.0 2359 34.9 42.2 0.0 0.0 0.0 0.0 0.0 0.0
1700 43.4 2359 36.2 43.5 0.0 0.0 0.0 0.0 0.0 0.0
1800 42.5 2359 35.3 42.6 0.0 0.0 0.0 0.0 0.0 0.0
1900 41.4 2359 35.9 43.2 0.0 0.0 0.0 0.0 0.0 0.0
2000 40.3 2359 34.9 42.2 0.0 0.0 0.0 0.0 0.0 0.0
2100 39.4 2359 33.9 41.2 0.0 0.0 0.0 0.0 0.0 0.0
2200 38.6 2359 34.1 41.4 0.0 0.0 0.0 0.0 0.0 0.0
2300 37.9 2359 33.1 40.4 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: JUNE


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 38.7 2359 32.9 40.2 0.0 0.0 0.0 0.0 0.0 0.0
0100 38.2 2359 32.3 39.6 0.0 0.0 0.0 0.0 0.0 0.0
0200 37.8 2359 31.8 39.1 0.0 0.0 0.0 0.0 0.0 0.0
0300 37.5 2359 31.3 38.6 0.0 0.0 0.0 0.0 0.0 0.0
0400 37.2 2359 30.8 38.1 0.0 0.0 0.0 0.0 0.0 0.0
0500 37.2 2359 30.0 37.3 0.0 0.0 0.0 0.0 0.0 0.0
0600 37.3 2359 30.3 37.6 0.0 0.0 0.0 0.0 0.0 0.0
0700 37.7 2359 30.3 37.6 0.0 0.0 0.0 0.0 0.0 0.0
0800 38.5 2359 30.2 37.5 0.0 0.0 0.0 0.0 0.0 0.0
0900 39.6 2359 30.6 37.9 0.0 0.0 0.0 0.0 0.0 0.0
1000 40.8 2359 30.7 38.0 0.0 0.0 0.0 0.0 0.0 0.0
1100 42.2 2359 32.0 39.3 0.0 0.0 0.0 0.0 0.0 0.0
1200 43.5 2359 31.8 39.1 0.0 0.0 0.0 0.0 0.0 0.0
1300 44.5 2359 33.9 41.2 0.0 0.0 0.0 0.0 0.0 0.0
1400 45.2 2359 34.1 41.4 0.0 0.0 0.0 0.0 0.0 0.0
1500 45.4 2359 36.0 43.3 0.0 0.0 0.0 0.0 0.0 0.0
1600 45.2 2359 36.3 43.6 0.0 0.0 0.0 0.0 0.0 0.0
1700 44.6 2359 35.6 42.9 0.0 0.0 0.0 0.0 0.0 0.0
1800 43.7 2359 36.4 43.7 0.0 0.0 0.0 0.0 0.0 0.0
1900 42.6 2359 36.4 43.7 0.0 0.0 0.0 0.0 0.0 0.0
2000 41.6 2359 35.2 42.5 0.0 0.0 0.0 0.0 0.0 0.0
2100 40.6 2359 35.3 42.6 0.0 0.0 0.0 0.0 0.0 0.0
2200 39.8 2359 33.9 41.2 0.0 0.0 0.0 0.0 0.0 0.0
2300 39.2 2359 34.0 41.3 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.50 Page 3 of 6


Hourly Air System Design Day Loads for CORRIDOR 4a
Project Name: 21014 BARKA MALL R4 08/01/2017
Prepared by: Amjaad 07:56AM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 39.2 2359 33.8 41.1 0.0 0.0 0.0 0.0 0.0 0.0
0100 38.8 2359 32.5 39.8 0.0 0.0 0.0 0.0 0.0 0.0
0200 38.4 2359 32.0 39.3 0.0 0.0 0.0 0.0 0.0 0.0
0300 38.1 2359 31.5 38.8 0.0 0.0 0.0 0.0 0.0 0.0
0400 37.8 2359 30.6 37.9 0.0 0.0 0.0 0.0 0.0 0.0
0500 37.7 2359 30.9 38.2 0.0 0.0 0.0 0.0 0.0 0.0
0600 37.9 2359 30.7 38.0 0.0 0.0 0.0 0.0 0.0 0.0
0700 38.3 2359 30.7 38.1 0.0 0.0 0.0 0.0 0.0 0.0
0800 39.0 2359 29.4 36.7 0.0 0.0 0.0 0.0 0.0 0.0
0900 40.1 2359 30.8 38.2 0.0 0.0 0.0 0.0 0.0 0.0
1000 41.4 2359 30.7 38.0 0.0 0.0 0.0 0.0 0.0 0.0
1100 42.8 2359 30.9 38.2 0.0 0.0 0.0 0.0 0.0 0.0
1200 44.1 2359 32.7 40.0 0.0 0.0 0.0 0.0 0.0 0.0
1300 45.1 2359 33.1 40.4 0.0 0.0 0.0 0.0 0.0 0.0
1400 45.8 2359 35.0 42.3 0.0 0.0 0.0 0.0 0.0 0.0
1500 46.0 2359 35.0 42.3 0.0 0.0 0.0 0.0 0.0 0.0
1600 45.8 2359 36.5 43.8 0.0 0.0 0.0 0.0 0.0 0.0
1700 45.2 2359 36.1 43.4 0.0 0.0 0.0 0.0 0.0 0.0
1800 44.3 2359 36.9 44.2 0.0 0.0 0.0 0.0 0.0 0.0
1900 43.2 2359 35.8 43.1 0.0 0.0 0.0 0.0 0.0 0.0
2000 42.1 2359 36.2 43.5 0.0 0.0 0.0 0.0 0.0 0.0
2100 41.2 2359 34.6 41.9 0.0 0.0 0.0 0.0 0.0 0.0
2200 40.4 2359 35.0 42.3 0.0 0.0 0.0 0.0 0.0 0.0
2300 39.7 2359 33.3 40.6 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: AUGUST


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 39.2 2359 32.3 39.6 0.0 0.0 0.0 0.0 0.0 0.0
0100 38.8 2359 32.0 39.3 0.0 0.0 0.0 0.0 0.0 0.0
0200 38.4 2359 32.4 39.7 0.0 0.0 0.0 0.0 0.0 0.0
0300 38.1 2359 31.0 38.3 0.0 0.0 0.0 0.0 0.0 0.0
0400 37.8 2359 31.4 38.7 0.0 0.0 0.0 0.0 0.0 0.0
0500 37.7 2359 30.8 38.1 0.0 0.0 0.0 0.0 0.0 0.0
0600 37.9 2359 29.5 36.8 0.0 0.0 0.0 0.0 0.0 0.0
0700 38.3 2359 30.1 37.4 0.0 0.0 0.0 0.0 0.0 0.0
0800 39.0 2359 30.4 37.7 0.0 0.0 0.0 0.0 0.0 0.0
0900 40.1 2359 30.0 37.3 0.0 0.0 0.0 0.0 0.0 0.0
1000 41.4 2359 30.5 37.8 0.0 0.0 0.0 0.0 0.0 0.0
1100 42.8 2359 30.8 38.1 0.0 0.0 0.0 0.0 0.0 0.0
1200 44.1 2359 32.9 40.2 0.0 0.0 0.0 0.0 0.0 0.0
1300 45.1 2359 32.6 39.9 0.0 0.0 0.0 0.0 0.0 0.0
1400 45.8 2359 34.5 41.8 0.0 0.0 0.0 0.0 0.0 0.0
1500 46.0 2359 35.3 42.6 0.0 0.0 0.0 0.0 0.0 0.0
1600 45.8 2359 35.9 43.2 0.0 0.0 0.0 0.0 0.0 0.0
1700 45.2 2359 36.3 43.6 0.0 0.0 0.0 0.0 0.0 0.0
1800 44.3 2359 36.6 43.9 0.0 0.0 0.0 0.0 0.0 0.0
1900 43.2 2359 35.4 42.7 0.0 0.0 0.0 0.0 0.0 0.0
2000 42.1 2359 35.9 43.2 0.0 0.0 0.0 0.0 0.0 0.0
2100 41.2 2359 34.3 41.6 0.0 0.0 0.0 0.0 0.0 0.0
2200 40.4 2359 34.6 42.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 39.7 2359 33.5 40.8 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.50 Page 4 of 6


Hourly Air System Design Day Loads for CORRIDOR 4a
Project Name: 21014 BARKA MALL R4 08/01/2017
Prepared by: Amjaad 07:56AM

DESIGN MONTH: SEPTEMBER


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 38.1 2359 32.2 39.5 0.0 0.0 0.0 0.0 0.0 0.0
0100 37.7 2359 31.4 38.7 0.0 0.0 0.0 0.0 0.0 0.0
0200 37.3 2359 31.0 38.3 0.0 0.0 0.0 0.0 0.0 0.0
0300 36.9 2359 31.1 38.4 0.0 0.0 0.0 0.0 0.0 0.0
0400 36.7 2359 30.4 37.7 0.0 0.0 0.0 0.0 0.0 0.0
0500 36.6 2359 29.9 37.2 0.0 0.0 0.0 0.0 0.0 0.0
0600 36.8 2359 29.2 36.5 0.0 0.0 0.0 0.0 0.0 0.0
0700 37.2 2359 28.6 35.9 0.0 0.0 0.0 0.0 0.0 0.0
0800 37.9 2359 29.5 36.8 0.0 0.0 0.0 0.0 0.0 0.0
0900 39.0 2359 29.3 36.6 0.0 0.0 0.0 0.0 0.0 0.0
1000 40.3 2359 29.2 36.5 0.0 0.0 0.0 0.0 0.0 0.0
1100 41.7 2359 31.0 38.3 0.0 0.0 0.0 0.0 0.0 0.0
1200 43.0 2359 31.3 38.6 0.0 0.0 0.0 0.0 0.0 0.0
1300 44.0 2359 31.8 39.1 0.0 0.0 0.0 0.0 0.0 0.0
1400 44.6 2359 33.5 40.8 0.0 0.0 0.0 0.0 0.0 0.0
1500 44.9 2359 34.3 41.6 0.0 0.0 0.0 0.0 0.0 0.0
1600 44.6 2359 34.9 42.2 0.0 0.0 0.0 0.0 0.0 0.0
1700 44.1 2359 35.6 42.9 0.0 0.0 0.0 0.0 0.0 0.0
1800 43.2 2359 34.6 41.9 0.0 0.0 0.0 0.0 0.0 0.0
1900 42.1 2359 35.0 42.3 0.0 0.0 0.0 0.0 0.0 0.0
2000 41.0 2359 33.8 41.1 0.0 0.0 0.0 0.0 0.0 0.0
2100 40.1 2359 34.3 41.6 0.0 0.0 0.0 0.0 0.0 0.0
2200 39.3 2359 32.9 40.2 0.0 0.0 0.0 0.0 0.0 0.0
2300 38.6 2359 32.4 39.7 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: OCTOBER


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 36.3 2359 30.4 37.7 0.0 0.0 0.0 0.0 0.0 0.0
0100 35.9 2359 29.5 36.8 0.0 0.0 0.0 0.0 0.0 0.0
0200 35.5 2359 29.8 37.1 0.0 0.0 0.0 0.0 0.0 0.0
0300 35.1 2359 29.6 36.9 0.0 0.0 0.0 0.0 0.0 0.0
0400 34.9 2359 28.9 36.2 0.0 0.0 0.0 0.0 0.0 0.0
0500 34.8 2359 28.6 35.9 0.0 0.0 0.0 0.0 0.0 0.0
0600 35.0 2359 28.9 36.2 0.0 0.0 0.0 0.0 0.0 0.0
0700 35.4 2359 28.4 35.7 0.0 0.0 0.0 0.0 0.0 0.0
0800 36.1 2359 28.2 35.5 0.0 0.0 0.0 0.0 0.0 0.0
0900 37.2 2359 28.0 35.3 0.0 0.0 0.0 0.0 0.0 0.0
1000 38.5 2359 28.5 35.8 0.0 0.0 0.0 0.0 0.0 0.0
1100 39.9 2359 29.6 36.9 0.0 0.0 0.0 0.0 0.0 0.0
1200 41.2 2359 30.4 37.7 0.0 0.0 0.0 0.0 0.0 0.0
1300 42.2 2359 31.4 38.7 0.0 0.0 0.0 0.0 0.0 0.0
1400 42.8 2359 32.2 39.5 0.0 0.0 0.0 0.0 0.0 0.0
1500 43.1 2359 32.6 39.9 0.0 0.0 0.0 0.0 0.0 0.0
1600 42.8 2359 32.4 39.7 0.0 0.0 0.0 0.0 0.0 0.0
1700 42.3 2359 33.0 40.3 0.0 0.0 0.0 0.0 0.0 0.0
1800 41.4 2359 33.8 41.1 0.0 0.0 0.0 0.0 0.0 0.0
1900 40.3 2359 32.9 40.3 0.0 0.0 0.0 0.0 0.0 0.0
2000 39.2 2359 32.4 39.7 0.0 0.0 0.0 0.0 0.0 0.0
2100 38.3 2359 31.5 38.8 0.0 0.0 0.0 0.0 0.0 0.0
2200 37.5 2359 32.1 39.4 0.0 0.0 0.0 0.0 0.0 0.0
2300 36.8 2359 30.9 38.2 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.50 Page 5 of 6


Hourly Air System Design Day Loads for CORRIDOR 4a
Project Name: 21014 BARKA MALL R4 08/01/2017
Prepared by: Amjaad 07:56AM

DESIGN MONTH: NOVEMBER


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 33.4 2359 28.9 36.2 0.0 0.0 0.0 0.0 0.0 0.0
0100 33.0 2359 28.1 35.4 0.0 0.0 0.0 0.0 0.0 0.0
0200 32.6 2359 27.8 35.1 0.0 0.0 0.0 0.0 0.0 0.0
0300 32.2 2359 28.1 35.4 0.0 0.0 0.0 0.0 0.0 0.0
0400 32.0 2359 27.0 34.3 0.0 0.0 0.0 0.0 0.0 0.0
0500 31.9 2359 26.4 33.7 0.0 0.0 0.0 0.0 0.0 0.0
0600 32.1 2359 26.9 34.2 0.0 0.0 0.0 0.0 0.0 0.0
0700 32.5 2359 26.4 33.7 0.0 0.0 0.0 0.0 0.0 0.0
0800 33.2 2359 26.6 33.9 0.0 0.0 0.0 0.0 0.0 0.0
0900 34.3 2359 26.3 33.6 0.0 0.0 0.0 0.0 0.0 0.0
1000 35.5 2359 26.7 34.0 0.0 0.0 0.0 0.0 0.0 0.0
1100 36.9 2359 27.3 34.6 0.0 0.0 0.0 0.0 0.0 0.0
1200 38.3 2359 28.3 35.6 0.0 0.0 0.0 0.0 0.0 0.0
1300 39.3 2359 28.6 35.9 0.0 0.0 0.0 0.0 0.0 0.0
1400 39.9 2359 30.3 37.6 0.0 0.0 0.0 0.0 0.0 0.0
1500 40.2 2359 30.8 38.1 0.0 0.0 0.0 0.0 0.0 0.0
1600 39.9 2359 31.0 38.3 0.0 0.0 0.0 0.0 0.0 0.0
1700 39.4 2359 31.6 38.9 0.0 0.0 0.0 0.0 0.0 0.0
1800 38.4 2359 31.1 38.4 0.0 0.0 0.0 0.0 0.0 0.0
1900 37.4 2359 30.2 37.5 0.0 0.0 0.0 0.0 0.0 0.0
2000 36.3 2359 30.8 38.1 0.0 0.0 0.0 0.0 0.0 0.0
2100 35.4 2359 29.3 36.6 0.0 0.0 0.0 0.0 0.0 0.0
2200 34.5 2359 29.5 36.8 0.0 0.0 0.0 0.0 0.0 0.0
2300 33.9 2359 29.3 36.6 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: DECEMBER


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 31.0 2359 26.8 34.1 0.0 0.0 0.0 0.0 0.0 0.0
0100 30.6 2359 27.2 34.5 0.0 0.0 0.0 0.0 0.0 0.0
0200 30.2 2359 27.0 34.3 0.0 0.0 0.0 0.0 0.0 0.0
0300 29.9 2359 25.7 33.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 29.6 2359 25.7 33.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 29.5 2359 26.2 33.5 0.0 0.0 0.0 0.0 0.0 0.0
0600 29.7 2359 25.4 32.7 0.0 0.0 0.0 0.0 0.0 0.0
0700 30.1 2359 24.9 32.2 0.0 0.0 0.0 0.0 0.0 0.0
0800 30.9 2359 25.7 33.0 0.0 0.0 0.0 0.0 0.0 0.0
0900 31.9 2359 26.0 33.3 0.0 0.0 0.0 0.0 0.0 0.0
1000 33.2 2359 26.0 33.3 0.0 0.0 0.0 0.0 0.0 0.0
1100 34.6 2359 26.2 33.5 0.0 0.0 0.0 0.0 0.0 0.0
1200 35.9 2359 25.9 33.2 0.0 0.0 0.0 0.0 0.0 0.0
1300 36.9 2359 27.2 34.5 0.0 0.0 0.0 0.0 0.0 0.0
1400 37.6 2359 28.8 36.1 0.0 0.0 0.0 0.0 0.0 0.0
1500 37.8 2359 29.4 36.7 0.0 0.0 0.0 0.0 0.0 0.0
1600 37.6 2359 30.1 37.4 0.0 0.0 0.0 0.0 0.0 0.0
1700 37.0 2359 30.0 37.3 0.0 0.0 0.0 0.0 0.0 0.0
1800 36.1 2359 29.9 37.2 0.0 0.0 0.0 0.0 0.0 0.0
1900 35.0 2359 29.3 36.6 0.0 0.0 0.0 0.0 0.0 0.0
2000 33.9 2359 28.9 36.2 0.0 0.0 0.0 0.0 0.0 0.0
2100 33.0 2359 28.5 35.8 0.0 0.0 0.0 0.0 0.0 0.0
2200 32.2 2359 28.1 35.4 0.0 0.0 0.0 0.0 0.0 0.0
2300 31.5 2359 27.4 34.7 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.50 Page 6 of 6

You might also like