As there are many different kinds of symbol sets (e.g. VdS, NFPA 170, BS 1675),
we have decided on a clear, simple symbol language based essentially on ISO
6790, adding some enhancements. However, the symbols required locally may
differ ask your fire brigade safety officer.
The meaning of all symbols used on a plan shall be defined in a legend on the
drawing.
295
Extinguishing
296
10.2 Glossary
Alarm state Status of a fire detection system or part thereof (e.g. fire detector) as the
response to the outbreak of a fire.
Alarm valve Device or component that releases the flow of water in the sprinkler pipe
network and triggers an alarm.
Alarm valve station Used for distribution to the sprinkler systems. It is positioned between the water
supply and the pipe work for the sprinkler system.
Algorithm The set of predefined calculation rules for processing signals. Depending on
the algorithm, the detector evaluates the current measured value, compares it
to specifications established with fire tests and generates the appropriate
danger level. This is then sent from the detector to the control unit.
Application How and where which device or system is deployed in practice.
ASAtechnology Successor technology to algorithm technology. It improves detection properties
mainly with real time interpretation of sensor signals and dynamically adapting
the response to the detection.
ASD Aspirating Smoke Detector
Aspirating smoke detector System with one or more smoke detectors which continuously draw in air
(ASD) through a pipe with an integrated fan and conduct it to the sampling chamber
with the built-in detector.
Automatic fire detection System which detects a fire in the incipient stages of an outbreak and triggers
system an alarm without human intervention.
297
Detector line Monitored transmission path which connects the fire detectors with the fire
detector control unit.
Detector zone A collection of detectors for which unique displays such as the location of the
danger are provided in the control unit.
DMS Danger management system. System which manages one or more sub-
ordinate detection systems.
Dry pipe sprinkler system The sprinkler network is filled with compressed air after the alarm valve. When
(dry system) a sprinkler head opens, the pressure in the pipe network falls, the alarm valve
opens and the water flows in.
Dry system Dry pipe sprinkler system
Electromagnetic Intrusion of unwanted signals into an electrical or electronic system.
interference
Electromagnetic Ability of electrical or electronic devices to function correctly without being
compatibility (EMC) influenced by or influencing their environment.
Emergency operation Fail safe mode
Equipment System elements, e.g. devices, appliances, instruments and machines in a
room
Equipment protection System concept to protect individual pieces of equipment with fire detection and
extinguishing systems (unit surveillance, equipment protection).
Evacuation The relocation of endangered persons or animals to a safe area.
Expansion ratio Ratio between the volume of foam and the volume of liquid required to create it
(water and foaming agent solution).
Explosion Rapid burning of a combustible material with air pressure expanding at speeds
of 100 to 1'000m/s.
299
Fail safe mode Fail safe mode of operation is the ability for a control unit to issue an alarm,
(emergency operation) possibly with some limitations, even if primary system elements have broken
down.
False alarm Alarm triggered without an emergency situation. False alarms can be caused
by technical issues, incorrect or malicious operation or by deceptive
phenomena (see also Nuisance alarm).
Fault status signal Signals that indicate faults in the fire detection system as a result of
unauthorized interference or technical defects.
FCU Fire detection control unit
Fire External appearance of combustion, producing heat, flames and smoke.
Fire alarm Warning of an existing danger to persons or property, which allows protective
measures to be initiated.
Fire alarm device (alarm Fire alarm devices call help so that preventative measures can be taken or to
devices, means of alarm) warn people, by acoustic and visual warning devices for example..
Fire alarm signal Procedure which acknowledges the operation of a manual fire detector or the
signal from an automatic fire detector as an alarm and forwards it to specified
locations. These are usually the fire brigade, the DMS and other alarm systems.
Fire compartment Separate area in a building in which constructional measures prevent or delay a
fire spreading to an adjacent area.
Fire control installations Plant and equipment or fire protection facilities controlled either automatically
by the fire detector control unit or manually which reduce both danger to
persons and fire damage.
Fire detection control unit Central component of a fire detector system which supplies the detectors with
(FDCU) power, receives signals, displays these visually and acoustically, forwards them
when necessary and monitors the system for faults.
Fire detection system The functionally matched equipment and components of a fire detection
system.
Fire detector Automatic fire detector
Fire fighting forces Tactical units available for intervention in case of fire.
(Fire service)
Fire load Combustible load
Fire phenomena Physical properties which in the area of a fire are subject to measurable
changes such as temperature increase, smoke and flame development.
Fire precaution Fire precautions are designed to prevent fires and to limit fire damage. They
include constructional, technical and organizational measures.
Fire protection concept A fire protection concept is understood as the harmonized, constructional,
technical and organizational fire protection measures which prevent fire
damage exceeding acceptable levels of damage.
300
Fire-proof seal Constructional measure which prevents flames or smoke spreading through
walls and ceilings via ducts and channels and recesses and openings for power
cables.
Flame detector Fire detector which reacts to the radiation from fires (mostly in the ultra-violet or
infra-red wavelengths).
Flaming fire Open fire
Flash point The flash point of a combustible liquid is the lowest temperature at which under
specified conditions vapor will develop in such quantity that a combustible
mixture of vapor and air is created over the surface of the liquid (saturation
vapor pressure = 100% LEL).
Foaming Process required to create foam (e.g. mixing air with the foaming agent
solution).
Full monitoring Monitoring of all the rooms, corridors and escape routes in a building with
automatic fire detectors. Wet rooms such as toilets, showers and washing
areas can be excluded from full monitoring.
Gas density Vapor density
Gas detector Component of a gas warning system. Gas detectors react to combustible gases
and vapors and usually send their signals to the gas alarm control unit via a
wire-line.
301
303
Open fire Open fires form visible flames, considerable heat and heat radiation. Generally,
(flaming fire) less smoke develops than with smoldering fires and it is often hardly visible.
Combustion is also more complete than with smoldering fires.
Optical smoke detector Scattered-light smoke detector
Light extinction smoke detector
Oxidation Chemical process in which a material gives off electrons. Compounds with
oxygen frequently form in this process.
PA Public address system for transmitting non-safety relevant announcements and
music. With the correct configuration, voice alarm systems can also carry out
PA functions.
Pellistor Two coordinated measuring elements consisting of an active and a passivated,
heated ceramic bead which is used in explosion protection to detect
combustible gases and vapors.
Ppm Parts per million. A specification of concentration which gives information about
the number of particles in question present in a million particles.
Production facilities Facilities that directly or indirectly maintain an operation and which should be
switched on or off in a fire (e.g. conveyor systems or climate control systems).
Rate-of-rise temperature Reacts when the temperature rises at more than a specified rate for a
detector sufficiently long time.
Reset Procedure to end the alarm or malfunction status. Operating one of the
elements provided for the purpose of resetting ends the alarm and or
malfunction status of a control unit.
Response indicator Visual display on the detector to indicate an alarm status.
(alarm indicator)
Ring line Detector line which, to increase operational reliability, runs from the fire detector
(loop line) control unit to the fire detectors and back again (UL864 class A wiring).
Risk Expresses the potential level of danger. Very safe means low risk, low levels of
safety mean high risk.
Scattered-light smoke Reacts to combustion products which affect the scattering of light in the infra-
detector (optical smoke red, visible and / or ultraviolet wavelengths.
detector)
Sensor Component of a detector which, depending on how it works, can detect a
natural phenomenon in its environment.
Server Designation for computers in a network which supply other members of the
network with data and programs ( Client server model).
304