Professional Documents
Culture Documents
How Do I Model Series Counterflow Chillers in TRACE 700
How Do I Model Series Counterflow Chillers in TRACE 700
TRACE 700?
Published 04/19/2016 03:06 PM | Updated 07/01/2016 02:09 PM
In order to create a Series counterflow chiller arrangement in TRACE, the user will have to model the
two chillers in the series-counterflow arrangement as one chiller. After gathering performance data for
each chiller (the upstream and downstream chiller), input the required information into this
spreadsheet. The spreadsheet requires power consumed information at constant condenser entering
temperature and at ARI conditions. Tab 3 of the spreadsheet contains the values needed to build the
power consumed and ambient modification curves in TRACE...
If there are several banks of series-counterflow chillers...
The user models each bank as one chiller. In TRACE, the configuration tab in create plants would
look like...
Notes:
If the information in this solution did not resolve your error or answer your question, please contact the
C.D.S. support center by dialing 608-787-3926 or sending an email to CDSHelp@trane.com.
While using the software, Press the F1 key to obtain filed specific help related to the items displayed
on the screen.
Attachments
File Type xls Duplex-Series-Counterflow_Curve_Fit[1].xls (72 KB)