How do I model series counterflow chillers in

TRACE 700?
Published 04/19/2016 03:06 PM | Updated 07/01/2016 02:09 PM

How do I model series counterflow chillers in TRACE 700?

How do I model several banks of series chillers in parallel?

How do I model series counter flow chillers in TRACE?

In order to create a Series counterflow chiller arrangement in TRACE, the user will have to model the
two chillers in the series-counterflow arrangement as one chiller. After gathering performance data for
each chiller (the upstream and downstream chiller), input the required information into this
spreadsheet. The spreadsheet requires power consumed information at constant condenser entering
temperature and at ARI conditions. Tab 3 of the spreadsheet contains the values needed to build the
power consumed and ambient modification curves in TRACE...
If there are several banks of series-counterflow chillers...
The user models each bank as one chiller. In TRACE, the configuration tab in create plants would
look like...

With each module being in parallel with the others.

Notes:

If the information in this solution did not resolve your error or answer your question, please contact the
C.D.S. support center by dialing 608-787-3926 or sending an email to CDSHelp@trane.com.
While using the software, Press the F1 key to obtain filed specific help related to the items displayed
on the screen.

Attachments
File Type xls Duplex-Series-Counterflow_Curve_Fit[1].xls (72 KB)