Professional Documents
Culture Documents
1VGA671056 - MV Switching Devices Selection For Application and Purpose PDF
1VGA671056 - MV Switching Devices Selection For Application and Purpose PDF
Switching devices with todays technologies are basically SF6 and Vacuum for typical distribution systems with
equal for medium voltage application. standard distribution class circuit breakers can be supplied
SF 6 now being phased out within many organisations with up to 30% DC offset. This is generally acceptable where
due to environmental concerns, and under arcing SF6 there are small generators connected to the system.
by-products found to be of concern, special handling For medium and larger sized generation applications,
disposal requirements. Generator type Vacuum of SF 6 Circuit breakers can be
Vacuum does have slight advantage with respect to life and supplied with up to 130% DC offset.
maintenance due to the lower energy requirement mecha-
nisms, as less force and less contact separation required.
Short Circuit Current Interruption Comparison between Circuit Breaker and Fused Contactor
The short circuit peak current causes the mechanical stress on an installation due to magnetic forces .
Generally if there will be a major failure of the equipment . It will occur in the first two to three cycles.
Without current limiting, circuit breaker protection (CB+CT+MRP) operates at zero current
160 crossover. Need to select the correct CB for purpose ie 30%, 80%, 130% DC offset in some
instances there may be a requirement to use higher rated circuit breakers to cater for high dc
140 component. Alternatively block protection trips under high fault levels eg 200msec to allow
DC offsets to decay away allowing conventional distribution circuit breakers to be utilised .
120
Short Circuit current (kA)
100
80
60
40
20
0
0 0,05 0,1 0,15 0,2 0,25 0,3 0,35 0,4 0,45 0,5
-20
Time (sec)
Current limiting fuse operates on current magnitude only (5msec). Approximately 20 times less
energy fed into a fault situation compare to circuit breaker . Minimal mechanical and thermal
damage as peak short circuit currents never reached . DC offsets catered for by the fuse.
Time
(seconds)
Contactor carries out switching of START, STOP and MPR activated TRIP functions OL, Stall, EF etc.
10,000
OVERLOAD RELAY
MPR
t 6X = 10, MPR provides Motor trip signals to contactor .
I =420A
100
I TO MAX
4.6kA
IM
10
I CN
MPR
Io :Pickup 25A
t :50 TO 1000 MS
Io :BLOCKED >3200A
0.1
0.05
10 2 3 4 5 6 7 8 9 100 1,000 10,000 100,000
For selection of fuses starting current , time and starts per hour need to be considered
As fuse provides full short protection, the contactor mecha- Reduced risk of fire and damage, higher availability with minimal
nisms do not require such extreme energy and force, there- downtime under fault restoration.
fore greatly improved mechanical and electrical endurance. Fuses act as a backup protection to MPR in the event of a failure
Ideal for high switching duty applications such as pumps, of DC or Protection systems.
compressors fans, etc.
As fuse provides current limitation, downstream equipment
has higher degree of protection than over a circuit breaker
solution. Ideal for high short circuit installations or where
high DC offsets may exist on installations.
The data and illustrations are not binding. We reserve the right to make
changes in the course of technical development of the product.
1VGA671056 Rev. A, November 2010