Block 1, Sector 8 Plot 6, Al Khor 1, UAE Section 16850: Diesel Generator
PART 1
TABLE OF CONTENT
1.0 GENERAL
1.1 REFERENCE
1.2 DESCRIPTION OF WORK
1.3 QUALITY ASSURANCE
1.4 SUBMITTALS
2.0 PRODUCTS
2.1 TYPE OF DIESEL ENGINE AND OPERATING CONDITIONS
2.2 FUEL
2.3 ENGINE LUBRICATION
2.4 GOVERNOR
2.5 STARTING SYSTEM
2.6 COOLING SYSTEM
2.7 SAFETY GUARDS
2.8 SILENCERS
2.9 AIR FILTERS
2.10 GENERATOR
2.11 VENTILATION
2.12 VOLTAGE REGULATION
2.13 PULLEY BLOCK
2.14 ENGINE/GENERATOR CONTROL PANEL AND AUTOMATIC TRANSFER
SWITCH
2.15 SET MOUNTINGS
2.16 MODE OF OPERATION
3.0 EXECUTION
3.1 INSTALLATION
3.2 TESTING AND COMMISSIONING
PART 2
TABLE OF CONTENT
1.1 GENERAL
1.2 TYPE OF DIESEL ENGINE AND OPERATING CONDITIONS
1.3 FUEL SYSTEM
1.4 DAILY SERVICE TANK AND STORAGE TANK
1.5 ENGINE LUBRICATION
1.6 CRANKSHAFT
1.7 GOVERNOR
1.8 STARTING SYSTEM
1.9 COOLING SYSTEM
1.10 SAFETY GUARDS
1.11 EXHAUST SYSTEM
1.12 AIR FILTERS
1.13 GENERATOR
1.14 VENTILATION
1.15 VOLTAGE REGULATION
1.16 GENERAL DESCRIPTION FOR MULTI BAY AUTO SYNCHRONIZING
SWITCHGEAR.
1.17 SET MOUNTINGS
1.18 LOCAL REPRESENTATION
1.19 AUTOMATIC TRANSFER SWITCH (A.T.S.)
1.20 INSTALLATION
1.21 SITE TEST
1.22 GENERAL CONDITIONS
1.0 GENERAL
1.1 REFERENCE
1.2.1 This Specification covers the supply, installation and commissioning of diesel
generating plant consisting of diesel generator set, daily tanks; main storage
tanks fuel pumps and related control panel supplied in accordance with the
specification as follows:
a) The generating set shall be provided complete with all ancillary plant and
apparatus, associated control and alarm panels, switchgear, interconnecting
wiring, cabling, and all other equipment required for the operation of the set.
b) The rating of the sets shall be adequate to meet the estimated load as shown
on the drawing while taking into consideration t h e ambient temperature
conditions of 50 deg.C and 100% humidity.
c) The generator shall also be capable of handling the starting current of the
connected equipment with the voltage dip within units acceptable to the
equipment (connected) manufacturers.
The generator rating indicated on the drawings is the power rating of the
diesel generator set after applying the derating factors to compensate for the
ambient temperature and humidity indicated in the specification.
Local Representation
1.4 SUBMITTALS
a) All drawings shall be to scale and fully detailed. All important dimensions shall
be given and the material of which each part is to be constructed shall be
indicated.
iii. Foundation details for diesel generator house floor, including cable and pipe
trenches.
h) Instrument scales.
VOLUME II Part 3 Page No. 6 of 21
DEWAN Building - UAQ Electrical Specifications
Block 1, Sector 8 Plot 6, Al Khor 1, UAE Section 16850: Diesel Generator
i) Materials list.
2.0 PRODUCTS
2.1.1 The engine shall be turbo-charged and after-cooled and shall be capable of
giving prime rated power for standby operation at site not less than the
specified output and an excess 10% overload capacity for one hour in every 12
hours of operation.
2.1.2 Engine shall operate at a maximum speed of 1500 rpm. The site rating shall be
based on the specified site operating conditions. If the site rating is less than
the stated catalogue rating a detailed explanation of the de-rating shall be
submitted for approval.
2.1.3 The site rating of the generator, irrespective of engine rating shall also be
stated and the rating of the set will be based on the lower of the two.
2.2 FUEL
The engine to be supplied shall operate on fuel of the light distillate type.
a) Pipes shall be seamless black steel conforming to ASTM A53 Sch 40.
b) Pipe work shall be all welded construction with socket weld fittings.
c) Pipe work installation shall comply with the relevant clauses of the air
conditioning specifications.
d) Pipe size shall be capable to handle the required fuel to the daily tanks for
continues operation of all the generators.
a) Fill connection coupling shall be quick lock to suite local diesel supply vehicles.
b) The fill point shall include an overfill alarm unit with muting switch operated by
a float switch within the storage tank.
d) The fully weather proof package pump sets including stand by pump shall be
complete with isolating and non return valves, pressure release valve,
pressure gauge and suction strainer all assembled on a bedplate. The pumps
VOLUME II Part 3 Page No. 7 of 21
DEWAN Building - UAQ Electrical Specifications
Block 1, Sector 8 Plot 6, Al Khor 1, UAE Section 16850: Diesel Generator
shall be self priming and shall operate on flooded suction systems. In addition to
the manifold relief valve each pump shall have an integral relief.
The fuel pumps size ( gpm & head ) shall be capable to handle the required fuel
to the daily tanks for continues operation of all the generators.
a) Diesel oil storage tanks shall comply with the requirements of ADNOC and shall
be installed in accordance with ADNOC and the local Civil Defense
requirements.
b) Tank construction shall be of minimum 6mm thick plate steel complying with
ASTM A 283.
c) Tappings shall be provided for fill, vent, suction and drain. Vents shall include
a flame arrestor.
d) A tank mounted oil level gauge shall be provided to monitor fuel level locally and
at a remote location close to the fuel fill point. Remote indicator shall be
housed in a cabinet to the approval of the Consultant.
f) A bulk fuel storage tank with capacity to cover 24 hours consumption at full
load shall be provided in addition to a daily fuel storage tank with capacity to
cover 8 hours consumption.
2.3.1 Lubrication of the engine shall be by means of an engine driven integral pump.
The pump shall have on the suction side a course strainer.
2.3.2 The Contractor shall ensure that the lubricating oil system capacity shall be
sufficient to enable the engine to run continuously for 12 hours at any load
without replenishment.
2.3.3 A semi rotary pump, glob valve and end cap shall be provided to discharge the
oil during maintenance.
2.4 GOVERNOR
The governor shall be of the electronic type. It shall control the speed within
the limits laid down in the respective standards and be capable of adjusting the
engine speed to a minimum of 5% above and below the rated speed. The
engine shall be fitted with a device, which will shut off the fuel supply to the
engine when any of the specified alarm conditions occur. The device shall be
fitted with one normally open and one normally closed contact, which will trip and
lock-out the generator circuit breaker in the event of the automatic device
operating.
b) Not more than two consecutive attempts to start may be made in any period of
1 minute, each starting period and the period between such consecutive
attempts being automatically time controlled by equipment. At the
failure of the second attempt the starter circuit shall be locked out pending
manual re-setting.
2.5.2 The equipment shall include an adequately rated maintenance free lead/acid
starter battery together with a charger. The battery charger will be supplied
from the mains and an engine driven dynamo is also required. Battery rack
shall be provided for the battery and the battery shall be protected against
accidental, mechanical or electrical damage.
2.5.3 The battery charger shall have a continuous output rating sufficient to recharge
the battery from 1.8 V to a fully charged condition in a period of 8 hours
allowing for any steady load on the battery. The characteristics shall be such
as to ensure an automatic voltage charge at 2.3 V/cell provided the input
voltage and frequency shall remain within +/- 6% and +/- 2% respectively of
normal value. The charger shall be mounted remote from the engine and shall
include a battery charge fail alarm. Battery charger shall have automatic
switch to disconnect the charger during engine starting.
2.5.4 Without power supply to the charger, the battery shall be capable of providing no
fewer than four starting cycles within a period of 1 minute. Upon restoring power
supply to the charger immediately thereafter, the charger shall be capable
of restoring the battery, within 30 minutes, to a condition in which one more
starting cycle can be completed.
2.8 SILENCERS
2.8.1 Engine shall be efficiently silenced with residential grade silencer complete
with interconnecting exhaust pipe and fitting. Supports for each complete
system shall be of the anti-vibration type and shall be so arranged that no
weight is carried by the engine set. Due allowance for expansion of the
exhaust system shall be made by the inclusion of expansion bellows if
necessary. Silencer shall be supplied complete with a drain off point. The
complete system including brackets shall be supplied galvanized and shall be
insulated within the building.
2.8.2 The silencers and exhaust pipe work shall be insulated within the building as
follows:-
The silencers and exhaust pipes shall be provided with 25mm stools, welded
on, to accept extruded mesh to provide a 25mm air gap between the hot
surface, and insulation to be applied. The insulation shall be 75mm thick
preformed rigid insulation wired on and then covered with hammered
aluminum sheet.
2.8.3 The Contractor shall be responsible for providing and installing stainless steel
fittings and wall plates necessary to carry the tail pipe through the building
walls.
Provide flap valve at the external end of the exhaust pipe, suitable of the high
temperature range and as per manufacturers recommendation.
Air filters shall be suitable for use in the environmental conditions, which are
likely to arise occasionally, with the atmosphere highly polluted by blown
sand and the same shall be confirmed by manufacturer in writing.
2.10 GENERATOR
2.10.1 General
It shall have screen protection and be drip proof with a large terminal box for
outgoing connections.
2.10.2 The generators shall be star connected, floor mounted panel with suitable
capacity ACB shall be provided adjacent to the generator.
VOLUME II Part 3 Page No. 10 of 21
DEWAN Building - UAQ Electrical Specifications
Block 1, Sector 8 Plot 6, Al Khor 1, UAE Section 16850: Diesel Generator
2.10.3 The generator shall be capable of maintaining its maximum rated output i n
addition to 10% overload capacity for one hour in every 12 hours of operation
when operating within +/- 5% of rated voltage, and at rated power factor of 0.8
(minimum).
2.10.4 The critical speed shall exceed twice the over speed test value.
2.10.5 All windings shall be tropicalised and suitably impregnated to withstand the site
ambient conditions. Minimum of class H protection will be required.
Stator
2.10.6 The stator core shall consist of high permeability, low loss steel stampings,
tightly clamped and securely located within the machine casing.
2.10.8 The windings shall be effectively braced to withstand the maximum forces
arising from any short circuit that may occur at the stator winding terminals.
Any material that is liable to shrink in service shall not be used for bracing,
packing or wedging. The ventilating circuit shall be designed to avoid hot
spots and to permit adequate cleaning by a portable centrifugal blower.
2.10.10 Both ends of each stator winding shall be brought out to terminal positions on
the stator casing, the phase and terminal box being arranged for 3-phase and
neutral connection. The terminal box shall be designed to accept the cables
detailed on the schematic diagram.
2.10.11 All current transformers, including the associated primary connections and
secondary circuit terminal blocks, required for any instruments and/or protection
relays specified or for excitation circuit compounding or compensation, together
with the generator neutral earthing connection shall be supplied and
accommodated within a substantial dust-proof sheet steel enclosure mounted at
the generator neutral terminal position.
2.10.12 Rotor
The rotor shaft and hub shall be of forged steel preferably in one piece. The
rotor poles shall be constructed of steel laminations, keyed and securely fixed to
the rotor hub and fitted with interconnected damper windings to absorb the
cyclic irregularity of the engine.
2.10.13 The field winding shall consist of electrolytic copper conductors insulated
throughout with Class 'H' materials. They shall be fully insulated at all positions of
support, and shall be securely located against movement due to thermal and
rotational cycling and the forces arising during over-speed testing.
VOLUME II Part 3 Page No. 11 of 21
DEWAN Building - UAQ Electrical Specifications
Block 1, Sector 8 Plot 6, Al Khor 1, UAE Section 16850: Diesel Generator
2.10.14 Where a separate exciter is provided, the exciter rotor shall be mounted on the
extended main shaft at the free end of the generator.
2.10.15 The minimum factor of safety of the rotating system shall be not less than 1.5,
based upon the yield point of the part most highly stressed at the stated
over-speed or during a stator 3-phase terminal short-circuit at normal voltage
whichever is the greater.
2.10.16 Exciters
The core and poles of the exciter shall be made of high permeability low loss
steel stampings tightly clamped and secured to minimize magnetic noise. The
characteristics of the exciter shall comply fully with the operational requirements
of the alternator in matching the required loading conditions.
2.11 VENTILATION
The generator and exciter shall incorporate shaft mounted fans of sufficient
capacity to provide the machine cooling effect necessary to comply with the
temperature requirements of the specification when operating in the specified
ambient conditions.
2.12.2 The equipment shall include all selector switches, indicating instruments,
rectifiers, resistors and any other auxiliary components necessary for the
satisfactory operation of the plant.
2.12.3 A voltage setting device capable of adjusting the required voltage in steps of
1% between the limits of 95% and 105% of normal voltage at any load within the
rating of the machine shall be mounted on the control panel.
2.12.4 When the generator maximum continuous load at rated power factor is rejected,
the regulator equipment shall be capable of limiting the generator momentary
over-voltage to a value not exceeding 120% rated voltage and shall restore
the voltage to within 2% of the nominal preset value within three seconds.
2.12.5 Over-voltage protection shall be provided, the voltage setting range being
105% to 125% in steps of 5%, the time setting range being adjustable within
the range 1 second to 5 seconds in steps of 1 second.
A hand-operated lifting block and chain shall be provided for the generator,
capable of lifting the largest item that has to be removed from the plant for
VOLUME II Part 3 Page No. 12 of 21
DEWAN Building - UAQ Electrical Specifications
Block 1, Sector 8 Plot 6, Al Khor 1, UAE Section 16850: Diesel Generator
routine maintenance and overhaul. Detailed shop drawing showing the lifting
block, chain arrangement and calculations for the same shall be submitted for
COMPANY review and approval.
2.14.1 A rigid free-standing, dust protecting sheet steel cubicle shall be provided as
the engine/generator control cubicle. All instruments, control switches, alarm
equipment and relays shall be mounted and wired on the front sheet. All
necessary remote alarm and indication facilities shall be provided. The cubicle
shall be part of the automatic changeover switch and the emergency power
supply distribution panel which shall be constructed to BSEN 60439 Part I
Form 4b type 6 as specified for the switchgear and distribution equipment in
section 16440.
2.14.2 All indicating instruments shall be rear connected and shall comply with the
relevant standards.
2.14.3 The genset control panel shall have following meters, switches, controls, gauges
and indication lamps for each generator set.
a) Indication Lamps:
High engine water temp, high winding temperature, low oil pressure, over
speed, fail to start, not in auto mode, battery charger ON, set on standby, set
in service, set faulty, low fuel in storage tank, 3 lamp for each mains and
emergency supply indication (all indication lamps shall be as specified in the
related section of the specification).
b) Meters/Gauges:
Oil pressure, water temperature, RPM meter, hour run meter, battery charging
ammeter, battery charging voltmeter, generator's and mains voltage meters
with selector switch, generator current and mains current for each phase.
Generator's frequency meters, KW meter, power factor meter (all meter shall be
as specified in the related section of the specification).
For jacket water heater, for anti condensation heater, emergency stop,
generator voltage adjusting rheostat, speed adjusting rheostat, over voltage
protection setting rheostat manual/test/auto/off selector switch, generator. A
programmable microprocessor shall provide control and programming for the
following:
i. Start attempts
ii. Crank time
iii. Cool down
set against low oil pressure, high coolant temperature, crank over speed, crank
over torque, stator/rotor winding temperature rise thermistor, and reverse power
relay,
2.14.4 The following controls shall be provided as part of the main switchgear.
b) Delay time starter adjustable to ensure mains failure is not for very short
period.
d) Overrun timer adjustable providing off-load cooling run before shutting down
the engine.
The automatic transfer and bypass switch shall be four poles complying with
IEC 947-6-1 with rating as shown on the drawings:
The transfer switch shall be electrically operated and mechanically held.
The electrical operator shall be a momentarily energized, single solenoid
mechanism. The switch shall be mechanically interlocked to ensure only two
possible positions, normal or emergency.
All main contacts shall be silver composition and shall have segmented blow on
construction for high withstand and close on capability and be protected by
separate arching contacts.
Inspection of all contacts shall be possible from the front of the switch without
disassembly of operating linkages and without disconnection of power
conductors. Switches shall have front removable and replaceable contacts. All
stationary and movable contacts shall be replaceable without removing power
conductors and/or bus bars.
A two way bypass isolation switch shall provide manual bypass of the load to
either source and permit isolation of the automatic transfer switch from all
source and load power conductors. All main contacts shall be manually driven.
A microprocessor controller and accessories shall be provided to achieve the
required operation as indicated hereunder.
VOLUME II Part 3 Page No. 14 of 21
DEWAN Building - UAQ Electrical Specifications
Block 1, Sector 8 Plot 6, Al Khor 1, UAE Section 16850: Diesel Generator
2.15.2 Suitable anti-vibration mountings shall be supplied for the diesel generator and
all set-mounted ancillary apparatus.
2.15.3 Flexible connections shall be provided to all exhaust, air, fuel and water piping to
avoid fracture due to vibration and to minimise conduction of noise.
2.16.1 Standby
At all times, except during maintenance periods, the battery charger unit and
any engine or panel heaters shall be set at ON.
The AUTO position of the control mode switch is pre-selected for automatic
standby against failure of the main supply.
a) A main failure detection unit shall be provided for each mains feeding essential
load and shall monitor the mains supply and will automatically initiate the start
sequence if the voltage of any phase of the main supply falls below the pre-set
limit.
b) In the event of a main supply failure the generator set will start, and run up
to speed. After a short delay as set on timer the generator set will assume
the load. The delay ensures that the alternator output has stabilised before
feeding the load.
c) When the main supply is restored, the generator set will continue to run and
supply the load for the duration of the time set on timer, the load is then
transferred back to the main supply and the generator set shuts down to
resume the standby condition.
a) The manual setting enables pushbutton start and stop control of the
generator set. Start the set by pressing and releasing the START button at the
control panel. The set will start and run up to speed.
b) The generator set will continue to run until the STOP/RESET push button is
operated, or the control mode switch is set to OFF.
c) Should a mains supply failure occur during a manual run, the generator set will
automatically assume the load. Before terminating a run check that the MAINS
TO LOAD indicator is lit, if not, then stopping the generator set will cause a
break in supply.
2.16.4 Test
The TEST setting simulates a main supply failure condition to enable testing of
the generator auto-start circuits.
The mains fail timer starts when the TEST setting is selected, engine cranking
will commence when the timer times out and the generator set will then start and
run.
No interruption of the mains supply to load will occur, and with the mains supply
healthy (mains breaker closed), breakers interlocks will prevent operation of the
alternator breaker.
Terminate the TEST run by re-setting the Control Mode switch to AUTO. The
engines will run-on for the duration of both the restoration delay and the overrun
timers as set on timer before shutting down and resuming the standby state.
To shut down the engine without an overrun period, set the control mode switch
momentarily to OFF and then to AUTO.
In the event of automatic fault shut down, the engine shuts down immediately.
An appropriate warning lamp is lit at the control panel, the engine controls are
locked out and indication persists until the controls are manually reset.
Check the relevant system and rectify the fault before attempting to restart the
set. To cancel the fault indication and release the engine control circuit press
and release the RESET pushbutton. The generator set will assume the standby
condition.
If the control mode switch is at the AUTO setting and the mains supply has
failed or if the control mode switch is at the TEST setting; engine cranking
will start immediately the RESET pushbutton is operated.
In the event of the engine failing to start within the pre-set cranking period, the
control circuit is automatically latched as in the case of a fault shutdown and
the START FAIL indicator is lit.
When the fault is rectified, press the RESET button to return the set to the
standby condition. If the mains supply is still failed, the automatic engine start
sequence should resume immediately.
2.16.9 All the indications, meters and alarms shall be duplicated as provided for on
the generator control panel also on the main L.V. switchgear (change-over
panel).
2.16.10 All cabling and connections to be carried out under this section contract.
2.16.11 Generator supplier shall ensure that all necessary and appropriate sensors and
contacts are provided for the proper operation in the LV switchgear.
3.0 EXECUTION
3.1 INSTALLATION
During this test the generator set shall run for at least four hours under the
following conditions:
During the load test all engine and generator parameters shall be
recorded. These shall include, but not be limited to:
b) The frequency and voltage regulation of the generator shall be verified. Voltage
and frequency variations shall be recorded on oscillograms. The requirement
for special dynamic load tests to simulate motor starting will be indicated in the
requisition.
c) Functional test
Functional tests shall be performed on the complete generator set including the
generator and engine control panels.
- All generator alarm and trip functions, including the verification of protection
relay operation.
- Operation of the battery charger.
e) Hydrostatic testing
f) Final Inspection
a) The following site tests shall be carried out in order to determine whether
the material and apparatus comply with this specification at site.
b) Not less than seven days notice in writing shall be given to the
COMPANY in order that they may arrange to present if they so desire. The
Contractors shall arrange to conduct as many tests together as are possible in
the opinion of the COMPANY and shall submit three copies of the records
of such tests to the COMPANY within seven days of completion. Two
copies shall be in English and one copy in Arabic language.
c) The contractor shall supply to the site the necessary load bank to test the
generator at full load.
a) Tests shall be carried out on generator set using resistive load bank. For the
purpose of these tests the rated power shall be as specified. All apparatus,
instruments, fuel and lubricating oil for these tests shall be provided by the
Contractor. Tests at various loads shall be made for the following periods and in
the same sequence:-
1/2 hour at ... 25% rated load
1 hour at ... 50% rated load
1 hour at ... 75% rated load
5 hours at ... 100% rated load
1 hour at ... 110% rated load
e) When type tests have previously been carried out, the Contractors may submit
accredited copies of the results instead of carrying out the tests again.
The engine shall be run at full load for a sufficient period of time to enable
steady conditions to be obtained, following which a run at 110% load shall be
carried out.
3.2.5 Ancillary Plant Tests
3.2.6 Electrical
a) Load tests shall be carried out on the diesel generator unit complete to prove
the efficiency at the loads stated in Schedule.
b) A full load rejection test shall be carried out on the set to prove the capability of
the excitation system in limiting the transient voltage swing.
e) Consultant reserves the right to call for such additional tests on any
equipment as may be necessary to prove compliance with the specification.
3.2.8 Testing shall include static load tests, functional tests and visual inspection as
specified.
Load banks shall be used for full load testing of the generator at site without
cost variation.
Load Banks
Unit shall be composed of separate resistive and reactive load banks controlled
by a common control panel.
The Load-Bank heat dissipation shall be carried out by an Integral fan with
totally enclosed motor providing uniform cooling airflow through load
elements.
Airflow and coil operating current shall be such that, at maximum load, with
ambient temperature at the upper end of the specified range, load-bank
elements operate at not more than 50 percent of maximum continuous
temperature rating of the resistance wire.
Power input circuits to load banks shall be fused, and fuses shall be selected to
coordinate with generator circuit breaker.
Cooling airflow and over temperature sensors shall automatically shut down
and lock out load bank until manually reset.
Safety interlocks on access panels and doors shall disconnect load power,
control, and heater circuits. Fan motor shall be separately protected by
overload and short-circuit devices.
- End of Section -