Operation scenario

1-In case full load, all the equiment in running condition

2-In case full load except one of the CM's in stop condition

3-In case raw mill in stop condition and all the plant in running condition

4-In case full load except both CM's in stop condition

5-In case all the plant in running condition except raw mill and one CM in stop condition

6-In case full load except both CM's and raw mill in stop condition ,we have two scenario :
Load in each
Total load (MW) # of running DG DG (MW)

33 5 6.6

25.5 4 6.38

24.2 4 6.05

18 3 6

16.7 3 5.56

2
(the actual required as two DG 4.6
can provide up to 15MW )

9.2 3
which they are following in that
case to protect the kiln from 3.07
tripping in case load shadding
activated
Load factor %

87%

84%

80%

79.50%

73 .7%

61% and If LS crusher in stop


condtion around 600KW reduce ,so
the load factor will be 57 %

41% , and If LS crusher in stop


condtion around 600KW reduce ,so
the load factor will be 38 %