You are on page 1of 4

DIgSILENT Project:

PowerFactory
2017 SP3 Date: 10/25/2017

Harmonics Calculation Balanced, positive sequence Busbars/Terminals


Nominal Frequency 50.00 Hz Output Frequency 50.00 Hz Calculate HD and THD Based on rated voltage/current

Grid: CLUSTERS System Stage: CLUSTERS Study Case: Study Case Annex: / 1
Rated Bus-voltage Distortion
Voltage ( 50.00 Hz) ( 50.00 Hz) RMS Sum ( 50.00 Hz) Total
[kV] [p.u.] [deg] [p.u.] [p.u.] [%] [%]
Single Busbar(1)
PLAT-1 LV 0.41 1.00 0.00 1.00 1.08 4.68 8.02
Single Busbar(10)
PLAT-9 LV 0.41 0.99 0.00 0.99 1.07 5.05 8.17
Single Busbar(11)
PLAT-8 LV 0.41 0.99 0.00 0.99 1.07 4.81 7.91
Single Busbar(15)
PLAT-14 LV 0.41 1.00 0.00 1.00 1.05 2.30 5.62
Single Busbar(16)
PLAT-4 LV 0.41 1.00 0.00 1.00 1.04 1.76 4.25
Single Busbar(17)
PLAT-12 LV 0.41 1.01 0.00 1.01 1.06 2.38 5.75
Single Busbar(2)
PLAT-6_LV 0.41 1.01 0.00 1.01 1.08 4.10 6.99
Single Busbar(3)
PLAT-7 LV 0.41 1.02 0.00 1.02 1.10 5.06 8.40
Single Busbar(4)
PLAT-2 LV 0.41 1.00 0.00 1.00 1.08 4.30 7.29
Single Busbar(5)
PLAT-11 LV 0.41 1.00 0.00 1.00 1.05 1.77 4.29
Single Busbar(6)
PLAT-15_LV 0.41 0.97 0.00 0.97 1.03 2.30 5.64
Single Busbar(7)
PLAT-5_LV 0.41 1.00 0.00 1.00 1.07 2.80 6.11
Single Busbar(8)
L6 LV 0.41 0.98 0.00 0.98 1.06 4.87 8.00
Single Busbar(9)
PLAT-10 LV 0.41 0.99 0.00 0.99 1.07 4.80 7.92
CLS-55_1
3.30 1.01 0.00 1.01 1.06 1.93 4.62
CLS-55_2
3.30 1.01 0.00 1.01 1.06 2.10 4.92
CLS-57_1
3.30 1.00 0.00 1.00 1.07 4.15 6.69
CLS-57_2
3.30 1.01 0.00 1.01 1.08 4.52 7.17
CLS-58_1
3.30 1.02 0.00 1.02 1.05 1.41 3.41
CLS-58_2
3.30 1.02 0.00 1.02 1.05 1.53 3.64
CLS-59_1
3.30 1.02 0.00 1.02 1.05 1.41 3.42
CLS-59_2
3.30 1.02 0.00 1.02 1.05 1.54 3.65
CLS-60_1
3.30 1.00 0.00 1.00 1.04 1.91 4.72
CLS-60_2
3.30 1.00 0.00 1.00 1.05 2.06 5.00
CLS-62_1
3.30 1.00 0.00 1.00 1.07 3.93 6.45
CLS-62_2
3.30 1.00 0.00 1.01 1.07 4.28 6.91
CLS-63_1
3.30 1.01 0.00 1.01 1.06 3.10 5.49
CLS-63_2
3.30 1.01 0.00 1.01 1.07 3.37 5.82
LV_CLS-55
0.41 1.02 0.00 1.02 1.06 1.88 4.47
LV_CLS-57
0.41 0.98 0.00 0.98 1.05 3.93 6.47
LV_CLS-58
Grid: CLUSTERS System Stage: CLUSTERS Study Case: Study Case Annex: / 2
Rated Bus-voltage Distortion
Voltage ( 50.00 Hz) ( 50.00 Hz) RMS Sum ( 50.00 Hz) Total
[kV] [p.u.] [deg] [p.u.] [p.u.] [%] [%]
0.41 1.02 0.00 1.02 1.05 1.37 3.31
LV_CLS-59
0.41 1.02 0.00 1.02 1.05 1.38 3.31
LV_CLS-60(1)
0.41 1.00 0.00 1.00 1.05 1.85 4.57
LV_CLS-62
0.41 1.01 0.00 1.01 1.07 3.82 6.24
LV_CLS-63
0.41 1.01 0.00 1.01 1.07 3.01 5.32
DIgSILENT Project:
PowerFactory
2017 SP3 Date: 10/25/2017

Harmonics Calculation Balanced, positive sequence Busbars/Terminals


Nominal Frequency 50.00 Hz Output Frequency 50.00 Hz Calculate HD and THD Based on rated voltage/current

Grid: TRANSCO GRID System Stage: TRANSCO GRID Study Case: Study Case Annex: / 3
Rated Bus-voltage Distortion
Voltage ( 50.00 Hz) ( 50.00 Hz) RMS Sum ( 50.00 Hz) Total
[kV] [p.u.] [deg] [p.u.] [p.u.] [%] [%]
Double Busbar
AWBU220S_BB1 220.00 0.97 0.00 0.97 1.03 2.03 5.74
AWBU220S_BB2 220.00 0.97 0.00 0.97 1.03 2.03 5.74
Single Busbar with Tie(1)
ADBU33SN_A 33.00 1.01 0.00 1.01 1.08 2.26 6.82
ADBU33SN_B 33.00 1.01 0.00 1.01 1.08 2.26 6.82
Single Busbar with Tie(10)
MSWG-4401_A 0.41 1.00 0.00 1.00 1.04 1.54 3.85
MSWG-4402_B 0.41 1.00 0.00 1.00 1.04 1.54 3.85
Single Busbar with Tie(11)
HSWG-4301-02_A 3.30 1.00 0.00 1.00 1.03 1.38 3.48
HSWG-4301-02_B 3.30 1.00 0.00 1.00 1.03 1.38 3.47
Single Busbar with Tie(12)
MSWG-4401-01_B 0.41 1.00 0.00 1.00 1.04 1.33 3.33
MSWG-4405-01_A 0.41 1.00 0.00 1.00 1.04 1.33 3.34
Single Busbar with Tie(2)
HWSG-4301-01_A 11.00 1.00 0.00 1.00 1.04 1.59 4.00
HWSG-4301-01_B 11.00 1.00 0.00 1.00 1.04 1.59 4.00
Single Busbar with Tie(3)
12-30-HSWG-4303 33.00 1.00 0.00 1.01 1.09 2.87 8.53
12-30-HSWG-4303 33.00 1.00 0.00 1.01 1.09 2.87 8.53
Single Busbar with Tie(4)
12-30-HSWG-4304 33.00 1.00 0.00 1.01 1.09 2.87 8.53
12-30-HSWG-4304 33.00 1.00 0.00 1.01 1.09 2.87 8.53
Single Busbar with Tie(5)
12-30-HSWG-4305 3.30 1.01 0.00 1.01 1.08 2.63 7.81
12-30-HSWG-4305 3.30 1.00 0.00 1.00 1.08 2.70 8.10
Single Busbar with Tie(6)
12-30-MSWG-4408 0.41 1.01 0.00 1.01 1.09 2.57 7.57
12-30-MSWG-4408 0.41 1.00 0.00 1.00 1.08 2.64 7.86
Single Busbar with Tie(7)
12-30-MSWG-4409 0.41 1.01 0.00 1.01 1.09 2.57 7.58
12-30-MSWG-4409 0.41 1.00 0.00 1.00 1.08 2.64 7.86
Single Busbar with Tie(8)
12-30-MSWG-4410 0.41 1.01 0.00 1.01 1.09 2.57 7.59
12-30-MSWG-4410 0.41 1.00 0.00 1.00 1.08 2.65 7.87
Single Busbar with Tie(9)
12-30-MSWG-4411 0.69 1.01 0.00 1.01 1.09 2.57 7.59
12-30-MSWG-4411 0.69 1.00 0.00 1.00 1.08 2.64 7.87
Single Busbar with Tie
ADBU33PSN_A 33.00 1.00 0.00 1.00 1.04 1.76 4.45
ADBU33PSN_B 33.00 1.00 0.00 1.00 1.04 1.76 4.45
Single Busbar(1)
WI_CL-61_1 3.30 1.01 0.00 1.01 1.05 2.16 4.54
Single Busbar(2)
WI_CL-61_2 3.30 1.01 0.00 1.01 1.06 2.34 4.83
Single Busbar(3)
WI_CLS-61 0.41 0.98 0.00 0.98 1.03 2.04 4.40
Single Busbar(4)
WI_CL-56_2 3.30 1.01 0.00 1.01 1.05 2.37 4.76
Single Busbar(5)
PLAT-3 0.41 0.99 0.00 0.99 1.05 2.63 5.53
Single Busbar(6)
WI_CL-56_1 3.30 1.00 0.00 1.01 1.05 2.18 4.53
Single Busbar(7)
WI_CLS-56 0.41 1.01 0.00 1.01 1.05 2.12 4.39
AC Terminal_1
6.60 1.01 0.00 1.03 1.55 18.67 52.54
AC Terminal_2
6.60 1.00 0.00 1.06 1.99 34.59 99.19
AC Terminal_3
Grid: TRANSCO GRID System Stage: TRANSCO GRID Study Case: Study Case Annex: / 4
Rated Bus-voltage Distortion
Voltage ( 50.00 Hz) ( 50.00 Hz) RMS Sum ( 50.00 Hz) Total
[kV] [p.u.] [deg] [p.u.] [p.u.] [%] [%]
6.60 1.01 0.00 1.03 1.55 18.67 52.54
AC Terminal_4
6.60 1.00 0.00 1.06 1.99 34.59 99.19
DC Terminal_1
7.50 0.00 0.00 0.00 0.00 0.00 0.00
DC Terminal_2
7.50 0.00 0.00 0.00 0.00 0.00 0.00
DC Terminal_3
7.50 0.00 0.00 0.00 0.00 0.00 0.00
DC Terminal_4
7.50 0.00 0.00 0.00 0.00 0.00 0.00