Professional Documents
Culture Documents
By Richard Nute
Presented by Jim Bacher
For some kinds of power distribution systems, the resistance of the grounding
circuit in an electrical product is critical to establishing equipotentiality.
Hazardous
Safeguard Electric
Principal Supplementary
Safeguard Safeguard
Concept Energy
Hazardous
Double Electric
Basic Supplementary
Insulation Insulation
Insulation Energy
Hazardous
Protective Electric
Basic Grounded
Insulation Parts
Grounding Energy
Faraday Cage is the name given to a device that shields its inside from electric
fields generated by static electricity. Usually a complete conductive shell, it
collects stray charges and, because like charges repel, stores them on the
outside surface (where they can be further apart than on the inside). The
electric fields generated by these charges then cancel each other out on the
inside of the cage.
(This model assumes the resistance of the conductors and connections that
comprise the cage is negligible.)
For the ungrounded Cage, there is no current return path. Regardless of the
Cage voltage, there is no potential difference within the Cage, and there is no
current in the body.
For the grounded Cage, the current path is that of least resistance (in
accordance with Kirchhoffs Laws). Since there is no resistance in the
conductors that make up the Cage, there is no voltage across the body, and
there is no current in the body.
Notice that the parts need not be connected to ground to create the
equipotential environment.
If the conductive parts are connected only to each other, then in the event of a
fault of Basic Insulation, there is no current as there is no return circuit path.
Hazardous
Load
voltage
In practice, most conductive parts such as water pipes, heating ducts, and
similar parts are connected to ground. So, for convenience, all conductive
parts are connected to ground. The ground provides the common connection
for all conductive parts, and no special connections need be made.
Letter definitions:
T = earth (terra), i.e., grounding rod
N = neutral conductor
I = impedance (to earth)
S = separate (connected to the neutral conductor at the service entrance)
C = combined (connected to the neutral conductor in the equipment)
We would not be concerned with the ground circuit characteristics except that
most power systems are grounded. This means the grounded equipotential
cage provides a current path back to the electric energy source. The design of
the cage must account for fault currents through the cage conductors.
Load
Hazardous
voltage
T
T
The protective conductor is connected to its own ground rod, remote from the
neutral ground rod. In some cases, the ground rod may be the steel frame of
the building. In any case, there is no direct copper connection between the
enclosure and the supply system.
Hazardous
Load
voltage
The neutral is connected through an impedance to its ground rod at the service
entrance.
The protective conductor is connected to its own ground rod, remote from the
neutral ground rod. In some cases, the ground rod may be the steel frame of
the building. In any case, there is no direct copper connection between the
enclosure and the supply system.
Hazardous
Load
voltage
Hazardous
Load
voltage
T N
The neutral conductor is connected to the ground rod located at the service
entrance.
Maximum load
Maximum load is rated load of the overcurrent device.
To analyze the circuit, the various circuit parameters must be known. The
parameters needed are: source resistance, maximum load, and protective
conductor resistance.
Maximum load is the rated load of the overcurrent device (usually a circuit-
breaker).
The protective conductor is the same size as the phase and neutral conductors.
Therefore, for the purposes of this analysis, the protective conductor has the
same resistance as the phase and neutral conductors. (Note that the percent
system voltage drop is comprised of both the generator resistance and the
conductor resistances; for this analysis, we have assumed that all of the
resistance is in the wires.)
Nominal Load
Load
System Voltage
Voltage 1/2 Supply
Source
Resistance
1/2 Supply
Source
Resistance
The load voltage is the nominal system voltage minus the voltage drop across
the source resistance due to the load current.
The supply source resistance is the system voltage drop divided by the
maximum load current. It is attributed to the wires, each wire having half of
the source resistance.
The protective conductor resistance is the same value as the resistance of the
other wires (because it is constructed of the same size wire and is in parallel
with the other wires). The protective conductor normally has zero current.
The first analysis is: What is the equipment resistance that will maintain no
more that 30 volts on accessible parts? The voltage on accessible parts is a
function of both the system voltage drop and the fault current.
The second analysis is: What is the voltage on accessible parts when the
equipment resistance is 0.1 ohm? The voltage is a function of both the fault
current and the source resistance (system voltage drop).
The third analysis is: What is the voltage on accessible parts when the
equipment resistance is 0.1 ohm and when the fault is a short circuit, i.e., when
the fault current is limited only by the resistance of the source and the 0.1 ohm
equipment grounding resistance?
112.8 V
Load
120 V (120 V - 6%)
R = E/I
E =(120-112.8)/2
I = 15
R = 0.24
At maximum current, the load voltage is 120 V minus 6 percent of the supply
voltage, 112.8 volts. This means 7.2 volts (120 - 112.8) is dropped in the
source resistance. One-half of 7.2 volts, 3.6 volts, is dropped in each wire.
The resistance of each wire is 3.6 volts divided by 15 amperes, or 0.24 ohms.
The same calculations can be repeated for the different supply systems, 120 V,
20 A, and 230 V, 16 A.
This table shows some representative source resistances for the different power
sources and for different system voltage drops. Source resistance approaches
0.5 ohm maximum, and 0.1 ohm minimum. As previously mentioned,
engineers design for 3% system voltage drop, or about 0.2 ohm source
resistance.
Note that as system voltage drop goes down, the source resistance goes down.
Logical!
Note also that source resistance is a function of the maximum current of the
system, not the voltage of the system.
Hazardous
Load
voltage
This schematic shows the normal-current (blue) and fault-current paths in the
TN-S system.
The fault current is created by an insulation fault. This fault can be any
resistance from megohms to zero ohms (i.e., short-circuit). For this analysis,
only those resistances that cause fault currents exceeding the circuit-breaker
rating are considered.
The fault current divides, most of it through the protective conductor, and
some through the body to earth. This analysis does not address the current, but
instead examines the voltage at an accessible (grounded) part of the
equipment.
0.12 ohms
Load
120 V
R 30 V
30 A
0.12 ohms
R = E/I
30 A E=30-3.6
E = IR I = 30
E=30x0.12 R = 26.4/30
E= 3.6 V R = 0.88 ohms
The question is: If the insulation fault allows a current of twice the maximum
load current (i.e., twice the rated current of the circuit breaker), what is the
maximum value of equipment resistance that will limit the voltage of an
accessible part to 30 volts?. (At twice rated current, the circuit-breaker will
take up to 2 minutes to operate; so, for those 2 minutes, safety must be assured
by the grounding circuit.)
The system voltage drop in this example is 3%. Therefore, the source
resistance is 0.12 ohms (see #20). The voltage drop across the 0.12 ohm
resistance of the protective conductor is 3.6 V.
For 30 V at accessible grounded parts of the equipment, 30 V is the sum of the
voltage drop across the protective conductor resistance, 3.6 V, and the voltage
drop across the equipment resistance, 30 minus 3.6, or 26.4 volts.
The equipment resistance is 26.4 volts divided by the current, 30 amperes, or
0.88 ohm. This is much greater than the 0.1 ohm required by various safety
standards.
These calculations can be repeated for various system voltage drops, 1% up to
6%.
20 A
1.4
1.2
Equipment Resistance, ohms
1.0
30 A
0.88 ohms
0.8
40 A
0.6
50 A
60 A
0.4
Fault current
0.2
0.1-ohm limit
0.0
0 1 2 3 4 5 6
System Voltage Drop, percent
The resistance for 30 volts for 30-ampere fault current was re-calculated for
system voltage drops from 1% to 6%.
The same calculations are shown for 20- to 60-ampere fault currents. Note
that the maximum resistance for all fault currents up to about 80 amperes is
greater than the 0.1 ohm required by safety standards!
0.12 ohms
I = E/R
Load
120 V E= 120
R = 0.12+0.1+0.12
0.1 E = 33
150 A
0.12 ohms
E = IR
150 A E = 150x0.1
E = IR E = 15
E = 150x0.12
E = 18 V
Once again, the analysis is for a 120-V, 15-A, 3% system voltage drop circuit.
The current is an arbitrary 150 amperes (10 times the circuit-breaker rating).
This current will clearly operate the circuit-breaker in a relatively short time.
Using similar calculations as for the equipment resistance, the accessible part
voltage is 33 volts .
100
1%
90
2%
80 3% nt
rce
5%
4%
, pe
6%
rop
70
eD
ltag
Vo
Accessible Voltage
m
60
ste
Sy
50
40
150 A
30
Limit for electric shock
20
10
0
0 100 200 300 400 500 600 700
Fault Current, Amperes
0.12 ohms
I = E/R
Load
120 V E= 120
R = 0.12+0.1+0.12
0.1 E = 77.7
353 A
0.12 ohms
E = IR
353 A E = 353x0.1
E = IR E = 35.3
E = 353x0.12
E = 42.3 V
Once again, the analysis is for a 120-V, 15-A, 3% system voltage drop circuit.
The current is limited only by the source resistances and the 0.1-ohm
resistance of the equipment. (This current will clearly operate the circuit-
breaker in a relatively short time.)
Using similar calculations as for the 150-ampere fault current, the accessible
part voltage is 77.7 volts volts .
These calculations can be repeated for the three major supply systems, 120 V/
15 A, 120 V/20 A, and 230 V/16 A as a function of system voltage drop.
180
160
140
230 V, 16 A
120
Potential, volts
100
120 V, 20 A
80
77.7 V Short-circuit current
120 V, 15 A
60
40
0
0 1 2 3 4 5 6
System Voltage Drop, percent
The voltage calculated on the previous slide (#26), is 77.7 volts at 3% system
voltage drop.
The voltages for 0.1 ohm resistance and short-cicuit current was re-calculated
as a function of system voltage drop.
The same calculations are shown for 120 V/15 A, 120 V/20 A, and 230 V/16A
supply circuits. Note that the maximum voltage always sexceeds the 30 volts
required by safety standards. Note that circuit-breaker operating time is
minimum under short-circuit conditions. So, the duration of hazardous voltage
is limited by the current-time operating curves of the circuit-breaker.
For higher fault currents, another scheme provides protection against electric
shock: limited duration of the current through the body by means of automatic
disconnection of the supply (operation of the circuit-breaker).
Easily achievable.
Ohms Law allows prediction of the maximum current at which the voltage on
accessible parts will exceed the usual 30-volt electric shock limit. For a
nominal 120-V, 15-A, 3% system voltage drop, the maximum current is about
125 amperes.